1、The Myth of Inertia Matching(Inertia Ratios and Why We Calculate Them)Prof. Nick RepanichCalifornia State University, Chico,USAImagine you have a 50,000 lb load and you place it on a truck, and the tires go flat. To find out what went wrong, you look at the specifications on the truck, and see that

2、it weighs 10,000 lb. You do some quick math to find that the load weighs 5 times the truck. No wonder you say. The correct load to truck ratio is 1:1. So you tell your boss you need a heavier truck to haul the load, one that weighs at least 50000 lb. He gives you a strange look, but gives you a truc

3、k of the requested weight, and what do you know - the truck carries the load easily!Did you use the correct logic to size the truck? Not really, yet this is exactly the logic used by many motion control engineers currently designing machines when it comes to sizing a motor for a particular load. How

4、 did we get here? It is an interesting taleMany technical reference sections found in manufacturers catalogs discuss inertia ratios. They commonly tell you that you should try for a 1:1 match between your motor and your load. They next tell you that you should never go above a 10:1 load-to-motor ine

5、rtia ratio. But the thing they never tell you is why they state this, or what their sources are. They of course do not have to, but ask the authors of those sections, and you will find no further answers. It seems as though one manufacturer read all the other manufacturers application sections, and

6、then wrote theirs as a compilation of the others.There are important things to know that almost seem to be hushed up. Certainly if you ask most of the salespeople who you might buy a motion control system from, they would be able repeat those ratios of “good design”. But ask them why and they stumbl

7、e. The answers are just not published. There have been some excellent articles reviewing the technical details behind the 1:1 ratio. In pure power translations, it is fairly easily shown how a 1:1 ratio gives optimum power transfer, at least in terms of efficiency. As they point out, this is rarely

8、useful in an actual application once cost is factored into the equation, thus the 1:1 ratio merely causes one to buy bigger motors.To get some insight into finding the right size motor for your application, imagine a simple linear motion system. A 1kg block is to be moved back and forth 100 mm on a

9、table top. Your hand is the power behind the system. In your hand is an identical 1 kg block. Initially, the two blocks are securely held together as one solid block. As you move the 1 kg block in your hand, the other block moves with you. As you accelerate your block at a rate of 1g, the other bloc

10、k had the exact acceleration rate as yours, as they are directly connected. As you decelerate, so does the load block. This is an ideal system with infinite stiffness and no non-linearities. You have complete control over the motion of the load without touching the load.Now, between the load block a

11、nd your block, place a very stiff 100mm spring, one similar to a car spring. Move your hand on the same manner. The load again does almost exactly the same motion as your block, because the spring you chose was so stiff. But now, again between the two blocks, place a less stiff 100mm spring, like a

12、bed spring. Again accelerate your hand. Now as you accelerate your block, the spring begins to compress. Once the force in the spring rises (due to Hookes Law) to a force equal to that of the force required to create the acceleration (F = -kx = ma), the other load begins to similar to your hand. But

13、 you have very little control over the position of the load, which was your initial goal.The force on the load rises to 1g as you accelerate. Now begin to decelerate your block to a stop, still in the same direction. The load does not slow at your rate. Instead, the spring begins to stretch, until i

14、t reaches a displacement from equilibrium (the same as it as when compressed). At this point, your load may be stopped, and the load may just be beginning its deceleration. Now as you stay stopped, the load begins to oscillate. It is stable (predictable) oscillation, but none the less, it is not sit

15、ting still like your hand. You could certainly not use loads position for any automated purpose, as it is not sitting still!Now imagine that you want to move the load back. If you begin your acceleration anytime during the deceleration of the load, you will feel a force higher than 1g. In fact, if y

16、ou move at just the wrong time, you could feel up to 2gs at your hand. Why is this significant? Because when you did your sizing to find a motor to move this load, you calculated the needed force based on the commanded profile of your hand, not the actual of the load. You never predicted a force hig

17、her than 1g in your calculations. And now you have up to double that force in your system. Better hope you had plenty of torque margins. Note that just picking a larger motor is much like just picking a bigger truck. Both can pretty expensive solutions.So what happened? You had a 1:1 inertia ratio,

18、supposedly the ideal ratio. You had a 50% torque margin, just what the books say. But yet your system oscillates wildly and is useless. It is because the most important factor in having control over the position of the load is stiffness, not its inertia ratio to the motor. You could probably imagine

19、 what would happen if your load was 100 times as large with the same wimpy spring. Not control at all. But similarly, you can also imagine a load that size is directly connected, or uses a stiff car spring. You would intuitively have quite good control over the load. Of course the system bandwidth d

20、ecreased, but only because of the additional mass. fn = (/2) ( (k/m)Inertia ratio is an indicator of possible stability problems. It is not the cause of the problem. So why do we use the ratio all the time in sizing motors? Because the ideal thing you would like to know in any system is the stiffnes

21、s and linearity of your system. It is simply not usually possible to determine this in a machine, especially one that does not actually exist at the time the motors must be determined and ordered. The inertia ratio is convenient ratio to check, and does give an indication of what may happen if you d

22、esign a wimpy machine.Interestingly, other non-linearities such as backlash cause a similar reaction, (more force/torque needed than predicted), as the spring. Imagine instead of a spring, you used a short chain to move the load around. As you accelerate initially, all is fine, as it is pushing dire

23、ctly on the load. But when you decelerate, the load goes to the end of its tether, and gives a jerk when it stops. Say hello to a big torque spike, an ideal impulse function, the bane of any control system.Back to the truck. What was really wrong? Do you calculate the weight of the truck and compare

24、 it to the weight of the load? Is the ratio the reason the tires went flat? No, but certainly the obvious solution, to either get a bigger truck, or to load it with a lesser weight did work. In fact, the ratio is only an indicator that the tires may have a flatness problem. The solution that only lo

25、oks at the ratio did not factor in the type or number of tires, the type of truck, the stiffness of the frame, to the air pressure in the tires, all of which probably more directly contribute to the ability to hold the load without flat tires.Adding a gear head and/or ball screw give a higher torque

26、 capability on the same motor, using more of the power of the motor by running it at a higher speed. This increases the headroom towards torque saturation, allowing for higher gains. If you go back and calculate the new inertia ratio, you find it to be a smaller ratio (by the ratio or pitch squared). But again, the ratio was not the problem or solution, only an indicator.When you size your motors

溫馨提示

  • 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
  • 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯系上傳者。文件的所有權益歸上傳用戶所有。
  • 3. 本站RAR壓縮包中若帶圖紙,網頁內容里面會有圖紙預覽,若沒有圖紙預覽就沒有圖紙。
  • 4. 未經權益所有人同意不得將文件中的內容挪作商業(yè)或盈利用途。
  • 5. 人人文庫網僅提供信息存儲空間,僅對用戶上傳內容的表現方式做保護處理,對用戶上傳分享的文檔內容本身不做任何修改或編輯,并不能對任何下載內容負責。
  • 6. 下載文件中如有侵權或不適當內容,請與我們聯系,我們立即糾正。
  • 7. 本站不保證下載資源的準確性、安全性和完整性, 同時也不承擔用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。

評論

0/150

提交評論