已閱讀5頁,還剩2頁未讀, 繼續(xù)免費(fèi)閱讀
高度對(duì)低壓開關(guān)設(shè)備和控制設(shè)備部件運(yùn)行性能的影響.pdf.pdf 免費(fèi)下載
版權(quán)說明:本文檔由用戶提供并上傳,收益歸屬內(nèi)容提供方,若內(nèi)容存在侵權(quán),請(qǐng)進(jìn)行舉報(bào)或認(rèn)領(lǐng)
文檔簡介
The Effect of Altitude on the Operation Performance Of Low Voltage Switchgear and Controlgear Components ALTITUDE (m) G. Erich Heberlein Jr. Senior Member, IEEE Director of Engineering Packaged Control Products Rockwell Automation 788 North Jefferson St. Milwaukee, WI 53202 USA Phone: 414.382.2004 Fax: 414.382.0273 VOLTAGE CURRENT Chester Malkowski, Jr. Member, IEEE Senior Principal Engineer Packaged Control Products Rockwell Automation 788 North Jefferson St. Milwaukee, WI 53202 USA Phone: 414.382.3054 Fax: 414.382.0273 Cmalkowski 2600 Michafel J. Cibulka Member, IEEE Project Engineer High Current Laboratory Rockwell Automation 1201 outh 2“d Street Milwaukee, WI 53204, USA Phone: 414.382.4627 Fax: ,414.382.2255 Micibulka 0.95 0.99 Abstract- Decreased air density due to increased altitude can have an effect on the operation performance of low voltage switchgear and controlgear components. For applications at high altitude little is known about this effect on the operation performance of these components. Characteristics such as dielectric voltage-withstand, thermal ampacity, overload calibration, contact life and interruption capability can be affected by the decreased air density. Tests were conducted in an electrical laboratory capable of producing needed electrical circuit parameters. The testing was conducted using a vacuum chamber to artificially lower the air density to simulate altitudes up to 6000 m A fact finding study was developed defining the operation performance capabilities for low voltage components at higher altitudes. 1500 I. INTRODUCTION 0.95 0.99 There is little technical guidance for high altitude applications, e.g. altitudes from 1000 m to 6000 m, of low voltage switchgear and controlgear components (LVCs) used in low voltage switchgear assemblies, motor control centers and panels. These LVCs include: molded case circuit breakers, disconnect switches, fuses, starters, contactors, soft start solid state starters, variable frequency drives, overload relays, control relays, and transformers. Since the air pressure and density decrease as the altitude increases the operation performance for LVCs is affected, in theory, the dielectric voltage withstand is reduced, thermal ratings are reduced, calibration is affected, contact life is affected, contactor interruption performance is reduced, and short-circuit interrupting capability is reduced. There is some guidance based on IEEE Std. 27 which provides empirical correction factors for the voltage rating (dielectric withstand) and current rating (thermal ampacity) l. See Table I. An example of how these altitude correction factors can be applied is shown in Table 11, However, information is not provided on operation performance criteria such as current interruption, which may also be affected by the reduction I 3000 0.80 TABLE I ALTITUDE CORRECTION FACTORS FROM IEEE STD. 27 0.96 I CORRECIION FACTORS ALL OTHER TYPES OF SWITCHGEAR ASSEMBLIES I CORRECTION FACTORS CURRENT VOLTAGE, ALTITUDE (m) loo0 I 1 .w I 1 .XI ALTITUDE (m) BUS AMPACITY (A) “1 3 m 768 I152 1536 1920 2400 of the dielectric and thermal characteristics at higher altitudes. Thus, engineers applying equipment at high altitudes have little guidance for properly selecting LVCs, and in reality, no guidance at all is provided for applications at altitudes above 3000 m. An example of LVC industry standards where altitude requirements are found is the NEMA Standard ICs 1-1993 2. This NEMA standard defines two altitude classes. Class 1 Km is for equipment installations that do not exceed an altitude of 1000 m. Systems using power semiconductor equipment are usually Class 1 Km. 0-7803-6401-5/00/$10.00 0 2000 IEEE 2688 Class 2 Km is for equipment installations that do not exceed an altitude of 2000 m. Electromagnetic and manual devices are Class 2 Km. However, guidance is not given in this standard for qualifying LVCs above these altitudes. Also, the International Electrotechnical Commission (EC) Standard, IEC 60947-1, includes a restriction that LVCs should not be applied above 2000 m 3. However, included in IEC 60947-1 is a note that permits LVCs to be used at higher altitudes, but the reduction of dielectric strength and cooling effects of the air must be addressed. As in the NEMA standard, guidance is not provided in IEC 60947-1 for qualifying LVCs for use above 2000 m nor is there guidance on how, at higher altitudes, the reduction of dielectric strength and cooling effects can be addressed. Thus, in order to address these LVC performance and application issues at different altitudes, a research program was initiated. This program was designed to investigate, not only, the effects caused by reduction of dielectric strength (dielectric withstand performance) and cooling effects (thermal capacity) of air at higher altitudes, but also investigate other operation performance criteria to determine if there were any significant performance changes, e.g., calibration, overload interruption, contact life, and short- circuit interruption. To investigate the affect on the operation performance for LVCs at increasing altitude, tests were conducted using a vacuum chamber to simulate the air densities normally found at the corresponding altitudes. See Fig. 1. The LVCs tested consisted of components qualified or addressed by IEC Standards, NEMA Standards, and Underwriters Laboratory Standards (Standards, et al) 3141516171 8191 l0lU 11. 11. TEST PROGRAM COMMENTS It must be noted that this investigation was not meant to be a qualifying type test program but a program to establish if there is significant change in the performance data due to changes in air density. Therefore, the test parameters, at times, were more severe than the norm in order to make this determination. Also, the test devices were selected as representative samples of LVCs and with the hope that the testing of these particular samples might demonstrate significant findings. This program is a first step process to determine which operational performances would indicate significant trends. Further testing may be required to more accurately determine the exact impact that altitude has on the operational performances. The altitude stated as 0 m in this investigation, air pressure norm 101.3 kPa, was not actually at sea level, but at the altitude of the test laboratory which is approximately 200 m 12. The air pressure of the laboratory was recorded before each test series and ranged from 99.9 kPa to 103.3 kPa. The air pressure in the test chamber was set at Fig. 1. Test Setup 47.1 kPa for the maximum test altitude of 6000 m. Fig. 2 shows the correlation of air pressure to altitude and was used for establishing the pressure for the testing with the base of 101.3 kPa for the air pressure at sea level 12. Although humidity was not considered in the study, it may have had some effect on certain tests. The humidity was monitored throughout the testing and the humidity did change at the different altitudes, e.g., 0 m to 6000 m altitudes, the humidity decreased from 17% RH to 12% RH respectively. 120 100 20 0 0 1500 3000 4500 6000 Altitude (m) Fig. 2. Air Pressure at Altitude 2689 111. DIELECTRIC WITHSTAND PERFORMANCE The Standards, et al, require through air and over surface requirements as well as a dielectric withstand test. These dielectric performance requirements are conservative and the LVCs have a very high dielectric withstand capability. Therefore, performing dielectric withstand tests on a product may not indicate any significant correlation to field usage at high altitude. Factors of material selection, the porosity of the materials used, and the design configuration may be more significant on LVC dielectric withstand performance than the reduction in dielectric strength due to the effects of lower air density at higher altitudes. However, to address the effects in dielectric withstand performance at higher altitudes, LVC samples were tested in a devised circuit based on Standards, et al. The dielectric withstand test was as follows: The three line terminals were connected together by jumpers. The three load terminals were also connected together by jumpers. A dielectric withstand test voltage of 2200 V was applied between the line and load terminals, with the device contacts open. See Fig. 3a. The air pressure was gradually decreased until the air pressure corresponding to an altitude of 6000 m was attained, i.e. altitude from 0 m to 6000 m. The circuit was changed. The jumpers were removed. The B phase line terminal was connected to earth by a jumper. The A and C phase load terminals were connected together by a jumper. The device contacts are closed and a dielectric withstand test voltage of 2200 V was applied between the B and the C phase line terminals. See Fig 3b. The air pressure was gradually increased until the air pressure corresponding to an altitude of 0 m was attained, i.e., altitude from 6000 m to 0 m. The duration of the test for each LVC was approximately 4 minutes. The current of the high voltage source was monitored throughout the duration of the test and set to trip at 50 mA leakage current. The following LVCs were subjected to dielectric withstand tests: IEC contactor, NEMA contactor, IEC circuit breaker, NEMA circuit breaker. All the devices successfully withstood 2200 V without breakdown at all altitudes. The findings indicated that there is sufficient margin in the design of the devices so that de-rating is not required for dielectric withstand performance at higher altitudes. IV. THERMAL AMPACITY It is known that for bus bar systems in open air the cooling and resultant thermal ampacity is adversely affected due to the lower air density at higher altitudes. Thus, IEEE Std. 27, as indicated in Table I, provides guidance regarding current de-rating based on altitude 11. However, lower air density at higher altitudes, should have less effect on LVCs since the internal components current carrying parts f“f“r-1 Fig. 3a. Dielectric performance (Contacts Open) Fig. 3b. Dielectric performance (Contacts Closed) are in contact with component moldings. Substantial cooling occurs by the conduction of heat through the molding material, which in turn, distributes the heat to the mounting plate. The effect on thermal ampacity for the LVCs was evaluated by placing the devices in the altitude test chamber and conducting a temperature: rise test at the simulated altitude air pressures. However, because the vacuum test chambers thick aluminum walls might act as a heat sink and effect the test results, the test.s samples were not mounted directly to the chamber but were suspended by wires. Thus, the change to the air density should be the only variable which would affect the temperamre test results. The following LVCs were subjected to a temperature test: IEC contactor, NEMA circuit breaker, HRC fuse. All the temperature tests were run at the maximum rated current for the LVC. The findings of the tcmperature rise test are shown in Fig. 4. The tests indicate that thermal capacity is significantly affected by altitude. The tests also indicate that devices with thermal elements., such as circuit breakers and fuses, are affected more significantly than devices without 35 , - 1 , 15 10 0 m 6030 Alutude (m) 1.1 IEC Contactor - - Thermal Magnetic Cllrlut Breaker IEEEStd 27 - HRC Fuses - Fig. 4. Ternperamre Test 2690 thermal elements, such as contactors. Interestingly, fuses were affected to such a great degree that this performance would need to be addressed when applying fuses at high altitudes. Also, plotted in Fig. 4 for comparison, is the thermal correction factor for 0 m to 3000 m based on IEEE Std. 27 with 3000 m to 6000 m extrapolated. ; 1 0 - f 9 n s - c 00 V. COMPONENT CALIBRATION PERFORMANCE T LVCs that provide overload current protection contain bimetallic, eutectic, or electronic elements for monitoring the current. This being the case, the decreased air densities at higher altitudes can have an effect on the calibration because the load current or 12R is actually monitored through heat transfer, e.g., convection and radiation of the heat to a bimetal. Also, the electronic devices often contain heat sensing elements, e.g., thermistors. These elements are used for monitoring the ambient, the circuit board, reset time, etc., and may affect the operation performance at lower air densities. A comparison of the calibration at different altitudes was evaluated by conducting an overload calibration test at 300% of the overloads trip setting and monitoring the trip time. The following LVCs were subjected to the overload calibration test: NEMA eutectic overload relay, IEC bimetal overload relay, IEC electronic overload relay with current transformers, IEC electronic overload relay with hall effect current monitors. The findings of the calibration performance tests are shown in Fig. 5. The tests show that the eutectic and bimetal overload relays are affected by the air density at higher altitudes and that the electronic overload relays are not adversely affected. Therefore, it would be necessary to use altitude correction factors with the eutectic and bimetal overload relays in order to avoid nuisance tripping. The findings support the use of electronic overload relays for applications above 2000 m. I I I n 3 m 6wO Altitude (m) -. Eutectic Alloy Heater - IEC Electronic (CT) 7 - - IEC Electranic (Hall Effect) - IEC Bimetalhc Element Fig. 5, Overload Calibration VI. CONTACT LIFE PERFORMANCE Contact life is a part of the application requirements for motor contactors. The type of operation affects the selection and sizing of the contactor for a given application, e.g., number of normal start and stop operations (AC3), percent of inching and plugging duty (AC4), etc. 3. Manufacturers supply contactor life curves and formulas to assist the application engineer in selecting the appropriate size contactor for the application. However, should there be a significant change to contact life at higher altitudes, the application engineer would have to address this change. A contactor with well known contact life was chosen for this testing. The contactor samples were disassembled and each of the contacts were carefully weighed. The contactors were then reassembled and a contact life performance test at the various altitudes was run. The contacts were re-weighed upon conclusion of the testing. Using this data, the altitude effect on contact life performance was evaluated. NEMA contactors were subjected to the contact life test. An example of the findings of the contact life test are shown in Fig. 6. The findings indicate there is no significant effect on the contact life caused by lower air densities at higher altitudes. To the contrary, the findings indicate that the contact life is slightly improved at higher altitudes. Therefore, it would not be necessary to change the contact life criteria used for selecting and sizing contactors at altitudes up to 6000 m. 0 1000 2000 3000 4000 SO00 6000 Altitude (m) Fig 6. Loss of Contact Material VII. CONTACTOR OVERLOAD INTERRUPTION PERFORMANCE Switching devices with limited interrupting capacity, such as contactors and disconnects, may be required to interrupt currents of ten to twenty times their ratings, e.g., lock rotor currents, inrush currents, etc. This interruption capacity is not a normal duty requirement, but a requirement under an overload condition. Thus, it is essential that the interrupting capacity should not be reduced with the increase in altitude. A contactor with well documented interruption capacity was chosen for this testing. The starting test current for each test 269 1 altitude was 50 A less than the known maximum interruption current of the contactor at sea level. Understandably, there is some variation in the interruption performance level, therefore, five test trials were conducted at each current level. The current level was increased 50 A if the device passed, and the test series repeated until the maximum interruption level was determined. To keep the test conditions as constant as possible, the tests were conducted as opening (0 shots) only. Thus, on these tests an external close-in contactor was used to eliminate any influence on the test sample interruption performance. IEC contactors were subjected to the contactor overload interruption test. The findings of the interruption performance tests are shown in Fig. 7. The findings indicate that the contactor interruption is improved at higher altitudes. The amount of current the contactor could successfully interrupt, increased as the altitude increased. Therefore, the interrupting rating of the contactors would not require de-rating at altitudes up to 6000 m. ,-. 40 E 2 35 E 6 30 .g 25 a $ 20 . . 5 I 5 10 c U 0 0 1 5 W 3oM 45cQ 6wO Altitude (m) - IEC Contactor - - . IEC Conmtor(Trend) Fig. 7. Contactor Overload Interruption closing angle is a difficult case for interruption by current limiting breakers as well. The following LVCs were subjected to a short-circuit interruption test: IEC circuit breaker, NEMA circuit breaker, HRC fuse. The short-circuit interruption tests were run at the rated short-circuit current and1 voltage for the LVC. Examples of the findings for the interruption performance tests are shown in Fig. 8 through Fig. 10. The findings indicate that all the LVCs appear to have sufficient margin in the design of the devices enabling them to interrupt their rated interrupting current at higher altitudes. However, the findings also indicate that while the peak currents remain fairly constant, the clearing times are longer and, in some cases, let-thru values increase at higher altitudes. The fuses appear to be more affected, especially at higher fault currents, than the circuit breakers by this trend. In a combination starter this may result in more damage to the
溫馨提示
- 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請(qǐng)下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請(qǐng)聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
- 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
- 5. 人人文庫網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對(duì)任何下載內(nèi)容負(fù)責(zé)。
- 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請(qǐng)與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶因使用這些下載資源對(duì)自己和他人造成任何形式的傷害或損失。
最新文檔
- 金融市場(chǎng)拓展與發(fā)展
- 二零二五年度入學(xué)新生教育法律權(quán)益保障書3篇
- 化妝品銷售保安工作總結(jié)
- 二零二五版小學(xué)校內(nèi)食堂食材供應(yīng)合同3篇
- 二零二五年度商業(yè)廣告攝影師雇傭合同(廣告創(chuàng)意拍攝)3篇
- 二零二五年度農(nóng)業(yè)產(chǎn)品銷售代表渠道拓展勞務(wù)合同
- 2025版旅游行業(yè)數(shù)據(jù)采集與旅游市場(chǎng)分析合同3篇
- 2025版石料場(chǎng)倉儲(chǔ)管理承包服務(wù)協(xié)議3篇
- 二零二五年度社區(qū)老年大學(xué)教學(xué)服務(wù)合同模板3篇
- 二零二五版實(shí)習(xí)生勞動(dòng)合同(含實(shí)習(xí)期間加班費(fèi)計(jì)算與支付)3篇
- 2025開工大吉蛇年大吉開門紅模板
- 鍋爐、壓力容器制造質(zhì)量手冊(cè)含程序文件-符合TSG07-2019《許可規(guī)則》
- 邏輯思維訓(xùn)練500題(帶答案)
- 2025年日歷表(A4版含農(nóng)歷可編輯)
- 人工智能大模型
- 極簡統(tǒng)計(jì)學(xué)(中文版)
- 2024年資格考試-對(duì)外漢語教師資格證筆試參考題庫含答案
- 2024年4月自考02382管理信息系統(tǒng)答案及評(píng)分參考
- (蘇版)初三化學(xué)上冊(cè):第2單元課題1空氣
- 2023年12月廣東珠海市軌道交通局公開招聘工作人員1人筆試近6年高頻考題難、易錯(cuò)點(diǎn)薈萃答案帶詳解附后
- 專題23平拋運(yùn)動(dòng)臨界問題相遇問題類平拋運(yùn)和斜拋運(yùn)動(dòng)
評(píng)論
0/150
提交評(píng)論