1、operation of the electric arc furnace with examples author: luis ricardo jaccard .br introduction certain issues related to the operation of electric arc furnaces are well known but others, especially those relating to the effects of electrical parameters on consumption (energy and electrodes) or on
2、 the arc characteristics (stability and length) are frequently cause of misunderstandings. the confusion usually arises from the propaganda of some regulators manufacturers that assign to their equipment the ability to increase power, reduce energy consumption, modify lengths and/or stabilize the ar
3、cs, as if this were not unique consequence of voltage, current and circuit reactance chosen by those responsible for the operation. 2 electrical parameters and energy consumption without doubt, choose the right operating parameters (voltage, current and reactance) is essential for obtaining the requ
4、ired active power and expected productivity with stable arc (appropriate power factor) and with the least possible consumption of electrodes, without excessive erosion of walls and roof of the furnace, avoiding overloading the transformer or disturbing excessively the electrical grid. but, except in
5、 extreme cases, the electrical parameters of operation have little or no influence on the amount of energy needed to produce a given amount of steel. 3 energy consumption energy consumption for producing one ton of steel depends on the size of the furnace, the type of charge, melting and shut down t
6、imes and thermal losses in the environment, in the water cooled walls, in the slag and in the hot heel. also depends on the temperature of tapped steel, on metal yield, and, among other factors, on the electrical losses in the conductors. typical energy balance for a 100-ton furnace which operates w
7、ith scrap loaded with two baskets: 4 energy in steel: 380 kwh/t energy in slag : 55 kwh/t energy in electrical losses: 20 kwh/t energy in gases and panels: 110 kwh/t output: 565 kwh/t input: 565 kwh/t consumption of electrical and chemical energy in modern furnaces, power is supplied not only by ele
8、ctricity but also by the chemistry (oxygen reacting with carbon). in the previous example, the furnace demanded an amount of energy of 565 kwh per ton of product, but that energy could be supplied with different rates of electricity and chemistry, for example: this is the same furnace consuming the
9、same amount of energy but with different percentages of chemical energy. the electrical energy depends on the amount of chemical energy. 5 total energychemical energyelectrical energy 565105460 565145420 565185380 electrical losses the electrical losses (i . r) are those that occur in the conductors
10、 of the furnace according to the current flow. lets see the effect of these losses on the energy consumption for an furnace that has a loss resistance of 0,4 mohm, usually operates with 1200 v, 60 ka and power factor 0,75. we start from the premise that, for the normal type of charge of the furnace,
11、 the power consumption is 565 kwh/t, with 165 kwh/t for chemical energy. it is observed that by reducing current from 60 ka to 50 ka occurs a very small reduction in energy consumption accompanied by a strong reduction of active power (lower productivity). reducing the voltage from 1200 v to 700 v o
12、bviously causes a sharp drop in power with some increase in total energy consumption. 6 v (v) i (ka) p (mw) electrical losses power (mw) electric. losses c. (kwh/t) energy consump. (kwh/t) chemical energy. (kwh/t) electrical energy (kwh/t) 12006093,54,318,4565,0165400,0 12005077,93,015,6562,2165397,
13、2 7006054,54,331,6578,2165413,2 analysis of energy consumption the energy consumption of a furnace depends strongly on the type of load. when the scrap has low density or the furnace has low volume is sometimes necessary to load the furnace with three or four baskets per heat. for loads made with mo
14、re than two baskets, each additional load, increases energy consumption by about 25 kwh/t (for a 50 ton furnace). for our original example, if the load were conducted in four stages, the total energy consumption (electric + chemical) could be increased to 615 kwh/t (a bit less for a 100-ton furnace)
15、. energy consumptions usually are referred to the tons of product and, if the metal yield is low, specific consumption increases. if the furnace consumed 565 kwh per ton of product with yield of 89%, scrap with a lower density that causes a yield of 83% would increase the energy consumption to 606kw
16、h/t. also consider the effect that a dirty scrap causes in energy lost in the slag, by requiring greater amounts of lime used. higher final steel temperature is also an obvious cause of higher energy consumption high tap to tap times, especially when resulting from high power off times, are generall
17、y the main cause of high consumption. 7 active power while the values of voltage, current and reactance do not cause a decisive effect on the energy consumption of the furnace, they are essential to achieving the desired productivity with a stable arc, low consumption of electrodes and normal arc at
18、tack to the walls. to achieve a certain production of steel per hour, it will be required a certain power: p (kw) = cee (kwh/t) x g (t) / power on (h), where cee is the specific consumption of electrical energy, g (t) is the weight of product per heat and power on is the operating time per heat. for
19、 a given process, as seen, the furnace requires a certain total amount of energy that can be provided with greater or lesser proportion of chemical energy. the furnace power on time will always be proportional to the specific consumption of electricity but will decrease when increasing the consumpti
20、on of chemical energy (see example). 8 power on time example: power on times for a 100 tons furnace with total power consumption of 565 kwh / t, using different chemical energy consumption values and different active power values. 9 total energy (kwh/t) chemical energy (kwh/t) electrical energy (kwh
21、/t) power on time for 80 mw (minutes) power on time for 85 mw (minutes) power on time for 90 mw (minutes) 56512544033,031,029,3 56514542031,529,628,0 56516540030,028,226,6 56518538028,526,825,3 56520536027,025,424,0 arc voltage and arc lenght the arc voltage va is equal to v x cos fi / 1.732, where
22、v is the phase to phase voltage and cos fi is the operational cosine fi at the infinite bus. be a furnace that operates with 75 mw active power and operational power factor of 0,75, powered by a 100 mva transformer with taps of 1300 v, 1100 v and 900 v: for these three alternatives productivity will
23、 be almost equal. the main difference is that with higher voltages are needed lower currents (lower consumption of electrodes) and, also, higher arc lengths (more heat radiation to the walls). arc length is proportional to arc voltage (usually 1 mm/v) 10 power (mw)applied voltage (v) current (ka) ar
24、c voltage (v) 75130044,4563 75110052,5476 7590064,1390 to keep the true power factor of 0,75 for the three alternatives of the previous example certainly had to be modified the value of the reactance of the circuit for each case. from the equivalent circuit of the furnace can be deduced that the sin
25、e of the angle is directly proportional to the product of current and reactance and inversely proportional to the applied voltage: sine = i. x. 1.73 / v. for a power factor of 0,75, the sine must be equal to 0.66. the actual values (considering the effect of harmonics) of the reactance for the examp
26、le would be: for a given power factor, increasing the voltage must be increased the reactance. 11 power (mw) applied voltage (v) current (ka) operational reactance (mohm) 75130044,411,2 75110052,58,0 7590064,15,3 reactance of the circuit operational reactance xop is greater than the sine wave reacta
27、nce x due to the effect of harmonics. “xop / x” factor increases as the cosine phi. as the current decreases, the cosine phi increases and the arc voltage (va v . cos fi) also increases. but beyond a certain value, a further decrease in current causes a very strong increase of the reactance of the c
28、ircuit, causing a decline in operational cos phi and also in arc voltage. this point is known as stability limit. for the regulator be able to maintain a certain current value is necessary that a decrease in current causes an increase in arc voltage and, therefore, for currents below the limit of st
29、ability the regulator fails to maintain expected current value. 12 reactance and arc stability 150 200 250 300 350 400 450 500 550 051015202530354045505560657075808590 arc voltage (v) ka when a decrease in current causes a decrease in arc voltage (rather than an increase, as would be normal), the re
30、gulator fails to maintain constant current, the electrodes go up and down without stopping. stable arc electrode unstable arc stable and unstable arc for 1000 v and reactance of 6 mohm stable and unstable arc explanation of the previous graphic: to reduce the current is necessary to increase the arc
31、 length, raising the electrodes. under normal conditions, the decrease in current causes a decrease in voltage drop and, consequently, the arc voltage increases. we have then a stable condition, because the arc length was increased by the regulator and the arc voltage also increased as the effect of
32、 the circuit. but when it is made an attempt to regulate a current lower than the corresponding to the stability limit, the distance between the electrodes and the load is greater than necessary to maintain the arc with the available voltage and extinction occurs. due to the interruption of the curr
33、ent, the regulator lower the electrodes to cause re- ignition. but the resulting current will be higher than expected and the regulator raises the electrodes until a new arc extinction occurs. thus, the electrode will remain up and down without stopping. this phenomenon is known as pumping. in this
34、case there is an incompatibility between the selected voltage and current, that in addition to greatly reduction of the active power, can cause vibrations in the arms and jerking of electrodes and water cooled cables. 14 long arc and unstable arc it is quite common to associate an unstable arc with
35、a long arc. but, in reality, an arc can be very long and perfectly stable. the arc length is defined by the arc voltage but stability is defined by the sinusoidal cosine phi which can not exceed a certain value (approximately 0,85 for the period of boring, 0,88 for melting and 0,90 for refining). th
36、e values of the following table were calculated for the boring-down period and for a sinusoidal reactance of 6 mohm: 15 vi (ka)cos fi sinus.cos fi realvaarc stability 1200650,8260,670464stable 1200600,8540,686475+/- stable 1200550,8790,695481unstable 1200500,9010,699484much unstable 1200450,9210,698
37、483much unstable clearly define if an arc is long or short is a relative matter. from a practical point of view one could say that for a modern high-capacity furnace, an arc of 250 mm is a short arc, an arc of 450 mm is long and one of 650 mm is much long. in fact, as was seen, it is possible to sta
38、bilize any length and constraints to further increase the length of the arc are: the erosion of the walls and foamy slag height. however, in relation to this topic there are also some misunderstanding. some manufacturers place on their electrode current controllers an option to short arc or “l(fā)ong ar
39、c which in reality corresponds to “higher current or “l(fā)ower current. in fact, as can be seen in the previous table, a decrease in current causes a very small increase in the arc voltage and below a certain point (stability limit) destabilizes the arc. in addition, the power drops vertiginously. 16 l
40、ong arc and short arc electrode consumption 17 electrode consumption (kg / t), for the same electricity consumption (kwh / t) is proportional to the ratio between the current and arc voltage i / va (tip consumption) and a slightly more complex relationship corresponding to consumption by oxidation b
41、ut that basically shows a dependence on (h x d / i ), where h x d is the oxidation of the electrode surface (h is the height of oxidation and d is the diameter of the electrode). based on the formula we conclude that the use of electrodes is inversely proportional to the arc voltage, as long as the
42、diameter of the electrode adapts to the current (with decreasing current, lower electrode diameter). not always a reduction in current causes a decrease in electrode consumption because when the current is too low in relation to the diameter of the electrodes a current reduction causes an increase i
43、n consumption by oxidation higher than the reduction of the tip consumption. this effect is heightened even more when the current falls below the stability limit (see figure). 18 electrode consumption 19 0.9 1.2 1.4 1.7 1.9 2.2 2.4 2.7 2.9 3.2 3.4 3.7 3.9 4.2 4.4 4.7 4.9 5.2 202530354045505560657075
44、80 kg/t corriente (ka) electrode consumption (kg/t), for 700 v yand1100 v, reactance 4 mohm, electrodes 600 mm, electrical energy consumption 415 kwh/t 700 v 1100 v low impedance furnace 43 mw 95 mw electrode consumption flicker and harmonic distortion 20 briefly, without going deeply into this impo
45、rtant issue, we can say that the levels of flicker and harmonic distortion are proportional to the short- circuit power of the furnace scf (reactive power when the electrodes are in direct contact with metal). from an operational perspective what can be done to decrease by approximately 20% the leve
46、ls of disturbance (flicker and harmonics), without reducing the active power is to operate with low real power factor (about 0,63/0,65) because with this condition the relation scf / p is lower, and, also, because the arc is more stable (see figure). flicker 21 0.75 0.80 0.85 0.90 0.95 1.00 1.05 0.3
47、60.390.420.450.480.510.540.570.600.630.660.690.720.750.780.81 real power factor “actual short circuit power/maximum short circuit power”, for the same active power, vs. real power factor lowest flicker summary for maximum productivity (t/h) is required to operate at maximum value of active power tha
48、t is compatible with the dimensions of the furnace and with the characteristics of the transformer and power circuit. the active power is the product arc voltage x current“. for a given active power, the higher the arc voltage, the greater the aggression of the arc to the walls and, in general, the
49、lower electrode consumption. the power on time is proportional to the specific consumption of electrical energy and inversely proportional to the active power. a greater proportion of chemical energy reduces electrical energy consumption and indirectly reduces the power on time. 22 large furnaces op
50、erated under normal conditions like, low downtime, scrap charge density sufficient to allow a few number of charges and high metal yield (0,89/0,90), also clean charge that reduces the amount of slag and pouring temperature of 1620/1640 c usually require an amount of specific energy of about 545 to 565 kwh per tonne of product (billets) or 485 to 508 kwh per tonne of metal charge. a portion of the energy supplied is of chemical origin. the specific consumption of electricity depends on the amount of chemical energy provided. if a particular furnace operates with power consumpt
溫馨提示
- 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請(qǐng)下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請(qǐng)聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
- 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
- 5. 人人文庫網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對(duì)任何下載內(nèi)容負(fù)責(zé)。
- 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請(qǐng)與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶因使用這些下載資源對(duì)自己和他人造成任何形式的傷害或損失。
最新文檔
- 2025版1A13365國際貿(mào)易實(shí)務(wù)操作手冊(cè)授權(quán)合同3篇
- 二零二五版海外科技園區(qū)勞務(wù)派遣與研發(fā)支持協(xié)議2篇
- 2025年房屋代持合同樣本與資產(chǎn)評(píng)估協(xié)議4篇
- 個(gè)性化私人借貸合同(2024版)版B版
- 2025版國家級(jí)屠宰場(chǎng)高品質(zhì)牛肉供貨合同范本下載3篇
- 2025年離職后研發(fā)成果保密及競(jìng)業(yè)限制協(xié)議
- 2025年度路燈廣告合作營銷策劃合同4篇
- 二零二五年度輔導(dǎo)班學(xué)生安全協(xié)議及學(xué)業(yè)輔導(dǎo)合同
- 二零二五年度智慧城市建設(shè)融資租賃合同主體權(quán)益與智慧應(yīng)用
- 2025年度法拍房屋拍賣議價(jià)及附屬設(shè)施維修保養(yǎng)合同
- 中國成人暴發(fā)性心肌炎診斷和治療指南(2023版)解讀
- 新生兒低血糖課件
- 自動(dòng)上下料機(jī)械手的設(shè)計(jì)研究
- 電化學(xué)儲(chǔ)能電站安全規(guī)程
- 幼兒園學(xué)習(xí)使用人民幣教案教案
- 2023年浙江省紹興市中考科學(xué)真題(解析版)
- 語言學(xué)概論全套教學(xué)課件
- 大數(shù)據(jù)與人工智能概論
- 《史記》上冊(cè)注音版
- 2018年湖北省武漢市中考數(shù)學(xué)試卷含解析
- 《腎臟的結(jié)構(gòu)和功能》課件
評(píng)論
0/150
提交評(píng)論