1、中海紫御公館安裝工程施工組織設(shè)計(jì)目 錄1、編制依據(jù)····································21.1、詢價(jià)文件········
2、183;·················································
3、183;······21.2、施工圖紙··········································
4、;························21.3:煙建質(zhì)安2006-1煙臺(tái)市住宅工程質(zhì)量通病防治辦法·····················
5、;···21.4、安裝工程主要采用規(guī)范、標(biāo)準(zhǔn)、圖集································22、工程概況··········&
6、#183;·························33、施工部署·······················
7、·············94、施工準(zhǔn)備工作··································115、主要分部分
8、項(xiàng)工程施工方法····························126 質(zhì)量保證措施與體制··················
9、3;············417.質(zhì)量通病的防治措施································428. 成品保護(hù)措施·
10、3;································439. 冬雨季施工措施···············
11、3;·················4410.安全生產(chǎn)和文明施工管理····························4611. 環(huán)保施工管理
12、及技術(shù)措施·····························47·附圖一 項(xiàng)目管理控制圖 ·················
13、;········································48附圖二 安全管理控制圖·······
14、3;·····················491、編制依據(jù)1.1、詢價(jià)文件1.2、施工圖紙:電氣、給排水及暖通空調(diào)圖紙。1.3:煙建質(zhì)安2006-1煙臺(tái)市住宅工程質(zhì)量通病防治辦法1.4、安裝工程主要采用規(guī)范、標(biāo)準(zhǔn)、圖集:高層民用建筑設(shè)計(jì)防火規(guī)范GB50045-2005年版建筑設(shè)計(jì)防火規(guī)范GB50016-2006供配電系統(tǒng)設(shè)計(jì)規(guī)范GB50052-2009低壓配電設(shè)計(jì)規(guī)范GB50054-
15、95民用建筑電氣設(shè)計(jì)規(guī)范JGJ16-200810KV及以下變電所設(shè)計(jì)規(guī)范GB50053-94建筑照明設(shè)計(jì)標(biāo)準(zhǔn)GB50034-2004;建筑物防雷設(shè)計(jì)規(guī)范GB50057-94(2000版)火災(zāi)自動(dòng)報(bào)警系統(tǒng)設(shè)計(jì)規(guī)范GB50116-98人民防空地下室設(shè)計(jì)規(guī)范 GB50038-2005人民防空工程設(shè)計(jì)防火規(guī)范GB50098-2008公共建筑節(jié)能設(shè)計(jì)標(biāo)準(zhǔn)GB50189-2005綜合布線系統(tǒng)工程設(shè)計(jì)規(guī)范GB50311-2007民用閉路監(jiān)視系統(tǒng)工程技術(shù)規(guī)范GB50198-94有線電視系統(tǒng)工程技術(shù)規(guī)范GB50200-94視頻安防監(jiān)控系統(tǒng)工程設(shè)計(jì)規(guī)范GB50395-2007安全防范工程技術(shù)規(guī)范GB50348-2
16、004電子信息系統(tǒng)機(jī)房設(shè)計(jì)規(guī)范GB50174-2008智能建筑設(shè)計(jì)標(biāo)準(zhǔn)GBT50314-2006建筑給水排水設(shè)計(jì)規(guī)范GB50015-2003(2009年版)室外給水設(shè)計(jì)規(guī)范GB50013-2006室外排水設(shè)計(jì)規(guī)范GB50014-2006二次供水設(shè)施衛(wèi)生規(guī)范GB1705-97住宅設(shè)計(jì)規(guī)范GB500961999(2003年版)住宅建筑規(guī)范GB503682005工程建設(shè)標(biāo)準(zhǔn)強(qiáng)制性條文-房屋建筑(設(shè)備)(2009年版)全國(guó)民用建筑工程設(shè)計(jì)技術(shù)措施-給水排水(2009年版)高層民用建筑設(shè)計(jì)防火規(guī)范GB50045-95(2005年版)自動(dòng)噴水滅火系統(tǒng)設(shè)計(jì)規(guī)范GB50084-2001(2005年版)汽車庫(kù)、
17、修理庫(kù)、停車場(chǎng)設(shè)計(jì)防火規(guī)范GB50067-97火災(zāi)自動(dòng)報(bào)警系統(tǒng)設(shè)計(jì)規(guī)范GB50116-98建筑滅火器配置設(shè)計(jì)規(guī)范GB50140-2005大空間智能型主動(dòng)噴水滅火系統(tǒng)設(shè)計(jì)規(guī)范DBJ15-34-2004氣體滅火系統(tǒng)設(shè)計(jì)規(guī)范DB50370-2005采暖通風(fēng)與空氣調(diào)節(jié)設(shè)計(jì)規(guī)范GB50019-2003集中采暖住宅分戶熱計(jì)量系統(tǒng)設(shè)計(jì)與安裝DBJT14-7-2002(山東省)全國(guó)民用建筑工程設(shè)計(jì)技術(shù)措施(暖通空調(diào) 動(dòng)力)2009版實(shí)用供熱空調(diào)設(shè)計(jì)手冊(cè)(第二版)2、工程概況本工程設(shè)計(jì)包括以下強(qiáng)電系統(tǒng):220/380V配電系統(tǒng)、應(yīng)急電源系統(tǒng)、照明系統(tǒng);建筑物防雷、接地系統(tǒng)及安全措施;本工程設(shè)計(jì)包括以下弱電系統(tǒng):
18、安全技術(shù)防范系統(tǒng),有線電視系統(tǒng),綜合布線系統(tǒng),可視對(duì)講系統(tǒng),信息發(fā)布系統(tǒng)、公共廣播系統(tǒng)、智能照明系統(tǒng)、電房管理系統(tǒng),智能化系統(tǒng)集成,機(jī)房工程?;馂?zāi)自動(dòng)報(bào)警系統(tǒng),緊急廣播系統(tǒng)(消防電氣系統(tǒng)見專篇)室外中、高壓送電線路及變配電所不在我公司設(shè)計(jì)范圍內(nèi);弱電系統(tǒng)分施工設(shè)計(jì)階段及深化設(shè)計(jì)階段,其深化設(shè)計(jì)階段由專業(yè)單位提供。變配電所低壓出線開關(guān)由變配電所設(shè)計(jì)單位設(shè)計(jì),其保護(hù)整定應(yīng)可靠的保護(hù)由我公司設(shè)計(jì)的低壓出線線纜。本工程負(fù)荷有動(dòng)力,照明,空調(diào)、及附屬設(shè)備等。人防區(qū)負(fù)荷分級(jí)另詳人防篇。本工程電氣安裝容量為_12289_Kw,計(jì)算容量_8594_kW,變壓器總安裝容量9350kVA確定本工程的供電電壓等級(jí)為
19、10KV,在地下室設(shè)置高壓開關(guān)房,要求電業(yè)提供一路10KV電源另設(shè)置柴油發(fā)電機(jī)作為備用電源。另外通訊,安保,消防等機(jī)房均需配備一定容量的不間斷電源,以保證主機(jī)的安全運(yùn)行和數(shù)據(jù)的不丟失。專變及公變配電房設(shè)置在地下一層;當(dāng)變電房與上、下或貼鄰的為居住、辦公房間僅有一層樓板或墻體相隔時(shí),變電房?jī)?nèi)采取屏蔽。降噪等措施。一級(jí)負(fù)荷采用雙路電源供電,其中消防水泵、消防風(fēng)機(jī)、消防電梯和消防控制中心在末端自動(dòng)切換。消防應(yīng)急電源由柴油發(fā)電機(jī)應(yīng)急母線供電,非消防備用電源由柴油發(fā)電機(jī)備用母線供電,備用母線和應(yīng)急母線之間的斷路器平時(shí)處于斷開位置,消防時(shí)切斷,平時(shí)可以手動(dòng)/自動(dòng)合閘。動(dòng)力照明配電箱、控制箱按需要選用掛墻式
20、、落地式及嵌入式箱,墻內(nèi)暗裝;開關(guān)插座選用86系列,墻內(nèi)暗裝。不超過30KW的電動(dòng)機(jī)直接啟動(dòng),其余電機(jī)采用星角或軟啟動(dòng)器啟動(dòng)。消防泵、噴淋泵除現(xiàn)場(chǎng)手動(dòng)控制外,還可通過碎玻按鈕、壓力開關(guān)或消防中心聯(lián)動(dòng)柜自動(dòng)控制;消防風(fēng)機(jī)除現(xiàn)場(chǎng)手動(dòng)控制外,還可通過防火閥或消防中心聯(lián)動(dòng)柜自動(dòng)控制;潛水泵除現(xiàn)場(chǎng)手動(dòng)控制外,還可通過液位自動(dòng)控制;電梯等機(jī)電一體化設(shè)備自帶控制設(shè)備。抑制諧波措施:在低壓電容補(bǔ)償柜內(nèi)設(shè)置14%電抗器住宅配電干線:住宅配電干線從公變低壓房穿金屬橋架引出至各住宅強(qiáng)電井內(nèi);線纜的選擇:非消防配電干線選用阻燃銅芯交聯(lián)銅芯電纜;非消防支線采用阻燃銅芯銅芯電線;消防負(fù)荷供電干線選用阻燃銅芯交聯(lián)銅芯電纜;
21、消防負(fù)荷末端支線選用A類耐火銅芯塑料電線穿金屬電線管明敷/暗敷或金屬橋架、線槽明敷,穿管暗敷設(shè)時(shí),不燃燒體保護(hù)層厚度不小于30mm;明敷設(shè)時(shí)外涂防火漆;豎井處用金屬橋架保護(hù)。橋架、線槽、線管穿越樓板及隔墻處均用防火膠泥封堵;穿越人防地下室防護(hù)結(jié)構(gòu)的線路在穿越處作防護(hù)密閉處理。本工程主干電纜均采用五芯電纜敷設(shè),另沿主干橋架及電氣豎井敷設(shè)ZRBV作為PE線;PE線規(guī)格不小于最大相線的1/2。照度標(biāo)準(zhǔn)按現(xiàn)行國(guó)家標(biāo)準(zhǔn)建筑照明設(shè)計(jì)標(biāo)準(zhǔn)執(zhí)行。主要場(chǎng)所照明功率密度值按現(xiàn)行國(guó)家標(biāo)準(zhǔn)建筑照明設(shè)計(jì)標(biāo)準(zhǔn)GB50034-2004執(zhí)行。有裝修處,將有機(jī)結(jié)合裝修設(shè)計(jì),確定照明方式及燈具形式。應(yīng)急照明設(shè)計(jì)見消防專篇,建筑物
22、另設(shè)景觀照明。本工程按第二類防雷建筑設(shè)計(jì)。1防直擊雷措施:(1) 在屋面設(shè)置由避雷短針和避雷網(wǎng)混合組成的接閃器,避雷網(wǎng)由在女兒墻暗裝的避雷帶和屋面結(jié)構(gòu)主筋組成,并在整個(gè)屋面形成不大于10MX10M或12MX8M的網(wǎng)格。(2) 利用砼柱主筋作引下線,相鄰兩條引下線的平均間距不大于18M。(3) 利用砼基礎(chǔ)作自然接地體。防雷接地、安全接地、工作接地共用接地體,接地電阻不大于1歐。(4) 屋面的金屬物與屋面防雷裝置連接。2防側(cè)擊雷措施:(1) 由45米起隔層利用建筑物圈梁內(nèi)結(jié)構(gòu)主筋設(shè)置一圈均壓環(huán)。(2) 由45米起外墻上的金屬欄桿、金屬門窗等較大的金屬物直接或通過金屬門窗埋鍍鋅鐵與防雷裝置連接。(3
23、) 豎直敷設(shè)的金屬管道及金屬物的頂端和底端與防雷裝置連接。3防感應(yīng)雷及雷電波侵入措施:(1) 凡進(jìn)出建筑物的鎧裝電纜金屬外皮,金屬線槽和金屬管道在進(jìn)出建筑物處就近與防雷接地裝置連接。(2) 變壓器高低壓側(cè)各相裝設(shè)避雷器。4防雷擊電磁脈沖措施:(1) 各層配電箱及重要設(shè)備配電箱進(jìn)線或跨越防雷區(qū)的線路裝設(shè)電涌保護(hù)器并在防雷區(qū)分界處作等電位連接。(2) 電話系統(tǒng)、有線電視系統(tǒng)和電腦系統(tǒng)等弱電系統(tǒng)的強(qiáng)電,弱電進(jìn)線端裝設(shè)電涌保護(hù)器。(3) 信息設(shè)備置于安全磁場(chǎng)強(qiáng)度區(qū)內(nèi)。5低壓供電采用TNS接地系統(tǒng),所有用電設(shè)備非帶電的金屬外殼構(gòu)架均應(yīng)與專用保護(hù)線作可靠的電氣連接。6預(yù)留地極引出線用于接地電阻測(cè)量和電氣安
24、全接地。7在總配電房處設(shè)總等電位聯(lián)接端子盒,將各局部等電位聯(lián)接端子盒、各PE線,建筑主筋、各種金屬管道等金屬部件,都接到總等電位連接端子盒上。在各設(shè)備機(jī)房?jī)?nèi)設(shè)局部等電位聯(lián)接端子盒,將PE線,建筑主筋、各種金屬管道等金屬部件,都接到局部等電位連接端子盒上。公寓式辦公樓內(nèi)的衛(wèi)生間應(yīng)設(shè)局部等電位聯(lián)結(jié)。8移動(dòng)式設(shè)備的電源插座線路均帶漏電保護(hù),其動(dòng)作電流為30mA。在層總配電箱中裝設(shè)300mA的防電氣火災(zāi)漏電保護(hù)裝置。消防電氣專篇1防護(hù)等級(jí):本工程為 一類防火建筑。火災(zāi)自動(dòng)報(bào)警系統(tǒng)的保護(hù)對(duì)象分級(jí)為 一級(jí)。2系統(tǒng)由觸發(fā)器件、火災(zāi)報(bào)警裝置、火災(zāi)警報(bào)裝置、圖形顯示裝置、漏電報(bào)警裝置、可燃?xì)怏w探測(cè)裝置、氣體滅火
25、裝置、大空間噴淋滅火裝置以及其他一些輔助功能的裝置組成。3火災(zāi)自動(dòng)報(bào)警系統(tǒng)設(shè)計(jì)范圍:火災(zāi)自動(dòng)報(bào)警系統(tǒng)、消防聯(lián)動(dòng)控制系統(tǒng)、火災(zāi)應(yīng)急廣播系統(tǒng)、火災(zāi)警報(bào)裝置及消防通信、 應(yīng)急照明控制及消防系統(tǒng)接地、電氣火災(zāi)報(bào)警、可燃?xì)怏w報(bào)警。4消防控制室設(shè)在 地下層,其入口處設(shè)置明顯的標(biāo)志;隔墻的耐火極限不低于2h,樓板的耐火極限不低于1.5h,并與其他部位隔開和設(shè)置直通室外的安全出口。5消防控制室內(nèi)設(shè)有火災(zāi)報(bào)警控制器、消防聯(lián)動(dòng)控制臺(tái)、應(yīng)急廣播設(shè)備、中央電腦、CRT顯示器、打印機(jī)、電梯運(yùn)行監(jiān)控盤及消防專用電話總機(jī)、UPS電源設(shè)備等。6消防控制室內(nèi)設(shè)有直接報(bào)警的外線電話。自動(dòng)報(bào)警系統(tǒng) 1本工程為 控制中心 報(bào)警系統(tǒng),
26、對(duì)全樓的火災(zāi)信號(hào)和消防設(shè)備進(jìn)行監(jiān)視及控制。2電梯機(jī)房、風(fēng)機(jī)房、水泵房、變配電房、各梯廳等處設(shè)置感煙探測(cè)器。3在地下停車場(chǎng)、廚房和鍋爐房設(shè)置感溫探測(cè)器;防火卷閘兩側(cè)、電氣主設(shè)備房、發(fā)電機(jī)房和發(fā)電機(jī)房?jī)?chǔ)油間等需要?dú)怏w滅火的場(chǎng)合設(shè)置感煙探測(cè)器和感溫探測(cè)器組。廚房還需設(shè)置可燃?xì)怏w探測(cè)器。4點(diǎn)型感溫探測(cè)器、感煙探測(cè)器、可燃?xì)怏w探測(cè)器的設(shè)置要滿足火災(zāi)自動(dòng)報(bào)警系統(tǒng)設(shè)計(jì)規(guī)范GB 50116-98的要求。5在本建筑每個(gè)防火分區(qū)的公共走道 、 樓梯入口 、 值班室 等處設(shè)置手動(dòng)報(bào)警按鈕,在同一防火分區(qū)的任何位置到最鄰近的一個(gè)按鈕的距離不大于30m。6在消火栓箱內(nèi)設(shè)置消火栓按鈕。7火災(zāi)自動(dòng)報(bào)警控制器可接收感煙、感溫
27、、可燃?xì)怏w等的火災(zāi)報(bào)警信號(hào)及水流指示器、檢修閥、濕式報(bào)警閥、手動(dòng)報(bào)警按鈕、消火栓按鈕等的動(dòng)作信號(hào);還可接收排煙閥、加壓閥的動(dòng)作信號(hào)。給排水系統(tǒng)設(shè)計(jì)項(xiàng)目范圍:建筑用地紅線內(nèi)的室外給排水系統(tǒng)、室內(nèi)給排水系統(tǒng)、室內(nèi)外消火栓給水系統(tǒng)、自動(dòng)噴水滅火系統(tǒng)、氣體滅火系統(tǒng)、建筑滅火器配置,以及各系統(tǒng)所需的設(shè)備用房。室內(nèi)外消火栓給水系統(tǒng)、自動(dòng)噴水滅火系統(tǒng)、氣體滅火系統(tǒng)、建筑滅火器配置詳消防設(shè)計(jì)說明專篇。建筑室內(nèi)給水排水設(shè)計(jì)(一)生活給水系統(tǒng)1、水源本工程供水水源為市政自來水。2、給水用水量本項(xiàng)目最高日總用水量為1972.58m3/d,最大時(shí)用水量為196.42m3/h。 3、室內(nèi)給水系統(tǒng) 根據(jù)建筑高度、水源條件
28、、防二次污染、節(jié)能和供水安全原則,給水系統(tǒng)設(shè)計(jì)如下: (1) 給水系統(tǒng)豎向分區(qū)的壓力控制參數(shù)為:各區(qū)最不利點(diǎn)的出水壓力不小于0.1Mpa,最低用水點(diǎn)的最大靜水壓力(0流量狀態(tài))不大于0.45Mpa。住戶的供水方式采用每層集中抄表供水,給水主立管及每戶分表設(shè)于水管井內(nèi),再引支管沿地面入戶,至戶內(nèi)每個(gè)用水點(diǎn)。當(dāng)入戶管的水壓大于0.35Mpa時(shí),在入戶水表前設(shè)支管減壓閥。 本工程別墅及住宅六層以下和地下室由市政直接供水,住宅塔樓由地下室無負(fù)壓供水系統(tǒng)加壓供水。生活熱水系統(tǒng)住宅部分采用太陽(yáng)能輔助電加熱熱水器,向廚房和衛(wèi)生間供應(yīng)熱水,太陽(yáng)能集熱板設(shè)在每戶南面的陽(yáng)臺(tái)外墻上,熱水器設(shè)于陽(yáng)臺(tái)內(nèi)。并按當(dāng)?shù)亟ㄔO(shè)部
29、門要求本項(xiàng)目50%的住戶安裝太陽(yáng)能熱水器,其余住戶預(yù)留位置,由住戶自行安裝。管材管材、接口及敷設(shè)方式室內(nèi)生活給水系統(tǒng)的干管、立管采用鋼塑管,管道接口采用絲扣或卡箍連接;支管采用PP-R冷水管,管道接口采用熱熔連接。室內(nèi)生活熱水支管采用PP-R熱水管,管道接口采用熱熔連接。塔樓管道敷設(shè)要求:衛(wèi)生間、廚房?jī)?nèi)的管道暗裝;穿越前室、廳房的管道埋在地板找平層內(nèi)。暖通系統(tǒng)采暖系統(tǒng)本工程采暖系統(tǒng)為集中供熱系統(tǒng),由市政熱力管網(wǎng)引入,沿各主樓夾層至管道井引入各樓層,分高低區(qū),1-16層為低區(qū),17-32層為高區(qū),立管采用無縫鋼管,在各層由管井內(nèi)引入戶內(nèi)分集水器。室內(nèi)采暖為地暖,管線采用PE-X管沿地面敷設(shè)。通風(fēng)
30、系統(tǒng)地下車庫(kù) 按6次/h換氣設(shè)計(jì)排風(fēng)及排煙系統(tǒng),同時(shí)按不小于3次/h設(shè)置機(jī)械補(bǔ)風(fēng)系統(tǒng)。設(shè)備用房設(shè)置機(jī)械通風(fēng)系統(tǒng)。車庫(kù)通風(fēng)采用風(fēng)機(jī)通風(fēng)方式。住戶的廚房通風(fēng)按目前廚房大小,常規(guī)通風(fēng)量預(yù)留廚房排油煙井(由建筑專業(yè)設(shè)置),至主樓屋頂排至室外。裙樓廚房通風(fēng)需配合專業(yè)廚房廠家做。目前廚房大小,常規(guī)通風(fēng)量預(yù)留廚房排風(fēng)井,排油煙井,補(bǔ)風(fēng)井。廚房井道均在建筑內(nèi),至裙樓屋頂排至室外.3、施工部署3.1、施工目標(biāo)根據(jù)安裝工程的總體質(zhì)量、環(huán)境、職業(yè)健康安全目標(biāo)原則,并結(jié)合安裝工程的實(shí)際情況制定質(zhì)量、環(huán)境、職業(yè)健康安全目標(biāo)如下表3.1:采暖安裝工程質(zhì)量、環(huán)境、職業(yè)健康安全目標(biāo) 表3.1序 號(hào)類 別總 體 目 標(biāo)安 裝
31、工 程 的 目 標(biāo)備注1質(zhì) 量 目 標(biāo)工程一次交驗(yàn)合格率100%,安裝工程檢驗(yàn)批一次交驗(yàn)合格率100%。2環(huán) 境保 護(hù)目 標(biāo)噪聲投訴處理率100%;噪聲投訴率年平均降低率20%、爭(zhēng)取降低30%。攪拌站封閉率100%;易飛揚(yáng)材料入庫(kù)率100%。主要污染物品達(dá)標(biāo)排放率100%;垃圾、廢棄物品分類管理100%;水消耗下調(diào)率5%,爭(zhēng)取6%;電消耗下調(diào)率5%,爭(zhēng)取6%?,F(xiàn)場(chǎng)加工庫(kù)房封閉率100%以盡量降低現(xiàn)場(chǎng)噪聲,并盡量減少樓層管材加工量,安裝工程的噪聲投訴處理率100%;安裝工程的噪聲投訴率年平均降低30%、爭(zhēng)取降低40%;現(xiàn)場(chǎng)施工后所剩余的零星安裝材料及時(shí)入庫(kù),現(xiàn)場(chǎng)臨時(shí)用水的龍頭和閥門使用完畢后隨手
32、關(guān)閉,避免長(zhǎng)流水;施工用電做到人走閘斷;3職 業(yè)健 康安 全管 理目 標(biāo)嚴(yán)格控制死亡、重傷、火災(zāi)、設(shè)備等重大事故和職業(yè)病的發(fā)生;事故負(fù)傷頻率控制在1.5以內(nèi)。無業(yè)主、社會(huì)相關(guān)方和員工的重大投訴;施工現(xiàn)場(chǎng)安全檢查必須全部達(dá)到JGJ59-99合格以上標(biāo)準(zhǔn),確保優(yōu)良率達(dá)到40,爭(zhēng)取達(dá)到50。杜絕安裝工程中死亡事故和職業(yè)病的發(fā)生;安裝工程中的輕傷事故頻率控制在1以內(nèi);3.2、施工組織機(jī)構(gòu)制定本工程的安裝工程施工組織機(jī)構(gòu)框圖如下圖3.2: 安裝工程施工組織機(jī)構(gòu) 圖3.2電氣工長(zhǎng)FANGXUEFAENG 項(xiàng)目生產(chǎn)經(jīng)理項(xiàng)目經(jīng)理技術(shù)負(fù)責(zé)人管道工長(zhǎng)暖通工長(zhǎng)質(zhì)檢員專業(yè)施工班組3.3、施工進(jìn)度計(jì)劃安排根據(jù)本工程的安
33、裝部分的實(shí)際情況,結(jié)合土建的進(jìn)度要求,制定施工進(jìn)度目標(biāo)見土建進(jìn)度計(jì)劃。 為了確保該工程保質(zhì)保量的按計(jì)劃進(jìn)行,必須組織一支強(qiáng)有力的技術(shù)過硬的施工隊(duì)伍,并保證有良好的設(shè)備和施工機(jī)具。具體計(jì)劃如下:表3.4(1)勞動(dòng)力計(jì)劃見土建勞動(dòng)力計(jì)劃。表3.4(2) 施工機(jī)具序號(hào)名稱規(guī)格型號(hào)數(shù)量功率產(chǎn)地備注1交流焊機(jī)B*3-500(或300)4臺(tái)16KW上海2套絲機(jī)Z3T-R44臺(tái)3KW杭州3臺(tái)鉆DP-252臺(tái)1.5KW杭州4沖擊鉆TE-24、TE-4212臺(tái)上海5電鉆6-13mm4臺(tái)上海6電動(dòng)試壓泵SY-52臺(tái)山西7彎管機(jī)SYM-3A2套8切割機(jī)J3G2-4004臺(tái)表3.4(3)主要檢測(cè)和試驗(yàn)設(shè)備序號(hào)名稱規(guī)格
34、型號(hào)序號(hào)名 稱規(guī)格型號(hào)1游標(biāo)卡尺0.02mm/0-30042鋼卷尺203壓力表64、施工準(zhǔn)備工作4.1、施工平面布置 本工程的施工平面布置由土建平面布置圖配置。 4.2、現(xiàn)場(chǎng)作業(yè)條件準(zhǔn)備 主要現(xiàn)場(chǎng)作業(yè)條件準(zhǔn)備工作,(見表4.2)安裝工程的主要現(xiàn)場(chǎng)作業(yè)條件準(zhǔn)備工作 表4.2工作內(nèi)容基本要求完成時(shí)間負(fù)責(zé)人員備注堆場(chǎng)設(shè)置在安裝工程施工以前,先在現(xiàn)場(chǎng)設(shè)置好材料堆場(chǎng),以便于能夠及時(shí)讓材料進(jìn)場(chǎng)安裝工程開工前材料員組織材料進(jìn)場(chǎng)在安裝工程施工前,組織材料進(jìn)場(chǎng),便于作好安裝工程施工的準(zhǔn)備安裝工程開工前材料員安全及技術(shù)交底正式圖紙到場(chǎng),工人進(jìn)場(chǎng)技術(shù)負(fù)責(zé)人施工材料到場(chǎng)工長(zhǎng)安裝配合土建主體結(jié)構(gòu)、砌體、抹灰施工、衛(wèi)生間
35、防水施工工長(zhǎng)系統(tǒng)調(diào)試安裝工程施工完畢工程竣工驗(yàn)收前技術(shù)負(fù)責(zé)人4.3、技術(shù)措施準(zhǔn)備 主要技術(shù)措施準(zhǔn)備工作見下表4.3。安裝工程的主要技術(shù)措施準(zhǔn)備工作 表4.3工作內(nèi)容基本要求完成時(shí)間負(fù)責(zé)部門/人員備注施工方案編制在安裝工程正式施工以前,先安排專人編制安裝施工方案; 安裝工程開工前技術(shù)負(fù)責(zé)人技術(shù)交底項(xiàng)目部技術(shù)負(fù)責(zé)人將安裝施工方案向主要管理人員交底安裝工程開工前技術(shù)負(fù)責(zé)人針對(duì)分項(xiàng)工程,在其正式施工以前進(jìn)行專門的技術(shù)交底分項(xiàng)工程施工前技術(shù)負(fù)責(zé)人現(xiàn)場(chǎng)工長(zhǎng)向作業(yè)班組進(jìn)行交底分項(xiàng)工程施工前工長(zhǎng)5、主要分部分項(xiàng)工程施工方法5.1、電氣工程主要施工工藝一、 關(guān)鍵施工技術(shù)本專業(yè)的施工技術(shù)關(guān)鍵主要有鋼管敷設(shè)、管內(nèi)穿
36、線、配電箱、柜安裝、燈具、開關(guān)、插座安裝、電纜敷設(shè)、橋架安裝、防雷接地系統(tǒng)安裝、送配電調(diào)試等。二、 主要施工程序三、 主要施工方法及技術(shù)措施1、 預(yù)留預(yù)埋、電氣配管所有配管工程必須以設(shè)計(jì)圖紙為依據(jù),嚴(yán)格按圖施工不得隨意改變管材材質(zhì)、設(shè)計(jì)走向、連接位置,如果需改變位置走向的,應(yīng)辦理有關(guān)變更手續(xù)。(1) 工藝流程:預(yù)制加工測(cè)定盒、箱位置固定盒、箱管路連接變形縫處理接地線焊接a、 現(xiàn)澆混凝土墻體上的電盒預(yù)留可隨結(jié)構(gòu)施工直接將盒子安裝到位,所有開關(guān)、插座盒預(yù)留時(shí)標(biāo)高宜比設(shè)計(jì)標(biāo)高高2cm。為了控制盒與墻面距離,施工時(shí)可根據(jù)墻體保護(hù)層厚度和電盒尺寸,利用鋼筋套子與墻體鋼筋采用綁接固定,通過墻體模板與鋼筋套
37、子將電盒夾緊夾牢,以防盒子移位。具體做法見下圖:b、墻體管進(jìn)頂板做根據(jù)管子材質(zhì)、板厚和燈位的位置不同, 可選用 a.煨彎法 b.直上法 c.煨燈叉彎法c 、現(xiàn)澆混凝土樓板與隔墻間的配管主要有兩種:上引管和下引管,如圖(a)、 (b)所示。a 上引管b 下引管d、 后砌隔墻上的開關(guān)、插座盒配管做法見圖:2、 鋼管施工要求:(1)、固定間距:明配管應(yīng)排列整齊,固定點(diǎn)的距離應(yīng)均勻;管卡與終端、轉(zhuǎn)彎中點(diǎn)、電氣器具或接線盒邊緣的距離為150-500mm,中間的管卡最大間距應(yīng)符合下表規(guī)定:管內(nèi)徑(mm)管卡最大間距(m)20以下1.025-401.550以上2.0(2)、鋼管布線施工時(shí),應(yīng)使用套管焊接連接
38、,套管長(zhǎng)充不小于連接管外徑的2倍,接口處焊接牢固(3)、鋼管的彎曲半徑不小于管外徑的6倍。當(dāng)線路直線段的長(zhǎng)度超過30m或一個(gè)直角彎超過15米、三個(gè)直角彎超過8米時(shí),均應(yīng)裝設(shè)接線盒。3、電氣配管(1)、所有配管工程必須以本工程設(shè)計(jì)圖紙為依據(jù),不得隨意改變管材材質(zhì)、設(shè)計(jì)走向、連接位置。根據(jù)現(xiàn)場(chǎng)情況,如果需改變位置走向的,應(yīng)及時(shí)取得設(shè)計(jì)院認(rèn)可,辦理有關(guān)變更手續(xù)。配合土建結(jié)構(gòu)澆筑時(shí)預(yù)埋管及后砌墻時(shí)的配管,要及時(shí)緊根土建進(jìn)度,不得漏配少配。確保配管質(zhì)量。本工程鍍鋅鋼管的連接方式:采用套絲管箍連接,專用接地線卡跨接接地,如圖所示。2電管接地跨接示意圖由于本工程建筑面積大,結(jié)構(gòu)施工時(shí)存在大量的后澆帶,當(dāng)鋼管
39、管路敷設(shè)到建筑物的后澆帶時(shí),一般應(yīng)設(shè)補(bǔ)償盒。在補(bǔ)償盒的側(cè)面一長(zhǎng)孔,將管端插入長(zhǎng)孔內(nèi),管可在長(zhǎng)孔內(nèi)伸縮,而另一端與接線盒固定,如下圖所示:線管經(jīng)過后澆帶補(bǔ)償裝置示意圖(2)、接線盒及配電箱的預(yù)埋現(xiàn)澆混凝土柱、墻、樓板上的接線盒預(yù)埋采用帶耳朵后開蓋的深型接線盒,先定位,再配管,配管時(shí)將插入接線盒的管端向模板面煨彎,保證接線盒緊貼模板.管口有效封堵后,接線盒內(nèi)裝入鋸木屑,以防止砂漿進(jìn)入接線盒,最后蓋上接線盒后蓋,并在模板上做出標(biāo)記。暗裝在墻體等部位的箱、盒、管,必須密切配合土建預(yù)埋或預(yù)留孔洞,對(duì)于大尺寸安裝配電箱,必須事先向土建專業(yè)提供詳細(xì)的預(yù)留孔洞尺寸圖。(3)、砌體配管及明裝配電箱的安裝加氣砼砌
40、體內(nèi)的安裝配管:砌體前配合土建先配管,由土建砌筑時(shí)將穿線管砌進(jìn)去;預(yù)留孔洞:將橋架、線槽等穿墻的洞口尺寸提供給土建,在砌筑時(shí),將洞口留出;明裝配電箱在空心磚墻處掛裝:采用對(duì)拉螺桿進(jìn)行固定,預(yù)留出螺絲接頭,待粉刷完工后進(jìn)行配電箱的安裝。四、防雷接地1、防雷接地施工本工程為二級(jí)防雷,共用接地。在屋頂采用10熱鍍鋅圓鋼作避雷帶接閃器?;炷羶?nèi)用作接地焊接的鋼筋搭接長(zhǎng)度、倍數(shù)應(yīng)按國(guó)家規(guī)范執(zhí)行,用做防雷引下線的結(jié)構(gòu)主筋應(yīng)用統(tǒng)一顏色做好明顯的標(biāo)識(shí)。接地鋼筋焊接示意圖建筑物內(nèi)的設(shè)備(如噴淋泵、消防泵等)、管道、電纜橋架等主要金屬物,應(yīng)與接地裝置或等電位帶相連;金屬管道在進(jìn)出建筑物處就近與接地裝置相連。引下線
41、:利用結(jié)構(gòu)剪力墻內(nèi),柱內(nèi)兩根直徑不小于16mm的主筋上下焊通,作引下線。引下線間距不大于18m。2、防雷電感應(yīng)在建筑物內(nèi)設(shè)置防雷接地預(yù)埋件,建筑內(nèi)的設(shè)備、管道、構(gòu)架、電纜金屬處皮等主要金屬物,應(yīng)就近與防雷接地預(yù)埋件相連。 3、防雷電波侵入進(jìn)出建筑物的各種線路及管道,采用全線埋地引入(出),在入戶端將電纜金屬外皮、金屬管道、金屬套管等與室外墻上的預(yù)埋件相連。4、均壓網(wǎng)利用地下室結(jié)構(gòu)板或剪力墻內(nèi)兩根水平鋼筋焊通,形成均壓網(wǎng),各引下線與均壓網(wǎng)相連。5、接地裝置利用結(jié)構(gòu)樁基內(nèi)多根(兩根以上)主筋上下焊通,同時(shí)利用地下室底部結(jié)構(gòu)梁或底板內(nèi)兩根主筋與錨桿樁焊通作接地裝置,防雷接地與強(qiáng)弱電電氣設(shè)備共用基礎(chǔ)接
42、地裝置,沖擊接地電阻要求不大于1歐姆。基礎(chǔ)施工完畢后,實(shí)測(cè)各引下點(diǎn)的接地電阻值,如不滿足要求,應(yīng)由室外預(yù)埋件外引人工接地體。6、等電位聯(lián)結(jié)總等電位聯(lián)結(jié):總等電位聯(lián)結(jié)板將變配電所的PE母排、各進(jìn)出建筑的電纜金屬外皮、金屬管道、建筑物的金屬結(jié)構(gòu)、及防雷預(yù)埋件均應(yīng)與總等電位聯(lián)結(jié)板連接。局部等電位聯(lián)結(jié):分別在衛(wèi)生間、桑拿房、淋浴間、游泳池設(shè)局部等電位聯(lián)結(jié)。7、各避雷帶、避雷網(wǎng)、均壓環(huán)、防雷引下線、接地預(yù)埋件、接地裝置等必須相互連接,連接點(diǎn)均為焊接,焊接應(yīng)滿足焊縫長(zhǎng)度的要求,外露防雷裝置做防腐處理。具體見示意圖: 柱內(nèi)引下主筋焊接長(zhǎng)度不小于6D基礎(chǔ)梁主筋12圓鋼跨接焊接,焊接長(zhǎng)度不少于6D,雙面焊五、盤
43、柜安裝盤柜安裝施工工藝流程如下圖所示:基礎(chǔ)驗(yàn)收基礎(chǔ)槽鋼制作安裝盤柜開箱檢查儀表送檢運(yùn)輸就位調(diào)整固定二次接線及檢查調(diào)試、試運(yùn)行制作安裝水平誤差不超過1mm/m,全長(zhǎng)總誤差不超過5mm技術(shù)資料是否齊全,配件與設(shè)備清單是否相符,外形有無損傷,元器件有無破損1、測(cè)試每條回路的絕緣電阻必須大于0.5 兆歐。2、有集成電路和電子元件時(shí),用萬用表測(cè)試回路是否接通。3、接通臨時(shí)電源進(jìn)行模擬試驗(yàn)。落地式配電箱采用XL-21型箱體,安裝于10#槽鋼底上;掛墻式配電箱、控制箱底邊距地1.4m,住宅用戶配電箱底邊距地1.7m。配電箱、柜安裝前應(yīng)對(duì)箱體進(jìn)行檢查,箱體應(yīng)有一定的機(jī)械強(qiáng)度,周邊平整無損傷,油漆無脫落,箱內(nèi)元
44、件安裝牢固,導(dǎo)線排列整齊,壓接牢固,并有產(chǎn)品合格證。配電箱、柜安裝時(shí)應(yīng)對(duì)照?qǐng)D紙的系統(tǒng)原理圖檢查,核對(duì)配電箱內(nèi)電氣元件、規(guī)格名稱是否齊全完好。暗裝箱體在土建施工是預(yù)留孔洞,各箱備用回路從箱頂?shù)皆搶訕前宓谆蛄旱组g的墻內(nèi)預(yù)留SC20或PVC25管一根,并在管頂做暗裝出線盒。暗裝配電箱安裝時(shí),預(yù)先了解墻面粉刷層厚度,使盤面板緊貼墻面,橫平豎直。明裝箱采用金屬膨脹螺絲固定。在陽(yáng)臺(tái)等潮濕場(chǎng)所裝設(shè)的配電箱采取有效的防水措施。消防配電箱在電氣豎井、配電室、風(fēng)機(jī)房等設(shè)備房間外面安裝時(shí),其外壁刷防火涂料保護(hù)。 電線管進(jìn)配電箱開孔要排列整齊,用開孔鉆開孔,電管進(jìn)入箱內(nèi)要絞絲,并加鎖母、護(hù)口,箱內(nèi)排線應(yīng)整齊綁扎成束,
45、扎帶距離相等,保持工藝美觀。在活動(dòng)的部位應(yīng)該兩端固定,盤面孔出線及引進(jìn)導(dǎo)線應(yīng)留有適當(dāng)余量,以便于維修。 配電箱內(nèi)接線前應(yīng)對(duì)每個(gè)回路絕緣進(jìn)行測(cè)試,并記錄數(shù)值,出線回路應(yīng)按圖紙的標(biāo)注套上相應(yīng)的塑料套管,標(biāo)明回路編號(hào);配電柜內(nèi)出線回路采用永久性塑料標(biāo)牌予以回路標(biāo)注。配電箱、柜本體要安裝好保護(hù)接地線,箱門及金屬外殼應(yīng)有明顯可靠的PE線接地。導(dǎo)線剝削處不應(yīng)傷線芯過長(zhǎng),導(dǎo)線連接時(shí)宜采用壓接帽壓接。配電箱在強(qiáng)電井內(nèi)安裝時(shí),因強(qiáng)電井常有雜物墜落,安裝固定后,應(yīng)進(jìn)行防護(hù),可采用硬紙板、塑料紙、粘膠帶等,綁扎牢固,以防混凝土濺入損壞箱面及箱內(nèi)元器件。配電箱通電試運(yùn)行:配電箱安裝完畢,且各回路的絕緣電阻測(cè)試合格后方
46、允許通電試運(yùn)行。通電后應(yīng)仔細(xì)檢查和巡視,檢查燈具的控制是否靈活、準(zhǔn)確,開關(guān)與燈具控制順序相對(duì)應(yīng)。如果發(fā)現(xiàn)問題,必須先斷電,然后查找原因進(jìn)行修復(fù)。配電箱、柜安裝調(diào)試完畢后,最后在箱內(nèi)分配開關(guān)下方用標(biāo)簽標(biāo)上每個(gè)回路所控制的具體負(fù)荷、設(shè)備名稱、位置,以便用戶使用檢修方便。六、 線槽安裝施工程序見下圖:定位固定支架線槽安裝保護(hù)接地槽內(nèi)配線線路檢查及絕緣搖測(cè)1、橋架之間連接采用半圓頭鍍鋅螺栓,半圓頭應(yīng)在橋架內(nèi)側(cè),接口應(yīng)平整、無扭曲、凸起和凹陷。2、橋架轉(zhuǎn)彎及分支處必須使用成品配件;彎曲半徑由最大電纜的外徑?jīng)Q定。3、橋架之間應(yīng)用軟銅接地專用線將兩段橋架的接地端子跨接。橋架穿越防火分區(qū)時(shí)需用防火材料填實(shí);吊
47、頂內(nèi)橋架均為開蓋式。4、橋架應(yīng)平直整齊,直線段的水平和垂直允許偏差應(yīng)不超過長(zhǎng)度的2%0,全長(zhǎng)允許偏差不超過20mm。七、管內(nèi)穿線施工程序:選擇導(dǎo)線穿帶線掃管放線導(dǎo)線與帶線綁扎帶護(hù)口導(dǎo)線連接線路檢查絕緣搖測(cè)導(dǎo)線包扎 管內(nèi)掃管穿帶線:管內(nèi)掃管穿帶線其目的是檢查管路是否暢通、準(zhǔn)確,清掃管內(nèi)積水和雜物,用空壓機(jī)吹掃后,用棉布條兩端牢固的綁扎在帶線上來回拖拉。穿線時(shí)須放適量滑石粉,以便線路滑行。 選擇導(dǎo)線:根據(jù)設(shè)計(jì)圖紙要求選擇導(dǎo)線。為保證相線、零線、地線不致混淆,應(yīng)采用不同顏色的導(dǎo)線,本工程統(tǒng)一規(guī)定A相為黃色,B相為綠色,C相為紅色,N線為淡藍(lán)色,PE線為黃綠雙色線。管內(nèi)穿線帶護(hù)口:導(dǎo)線在管內(nèi)嚴(yán)禁有接頭
48、,導(dǎo)線應(yīng)按標(biāo)準(zhǔn)留足接線長(zhǎng)度。線路檢查及絕緣檢測(cè):管內(nèi)穿線結(jié)束后,應(yīng)按規(guī)范及質(zhì)量驗(yàn)評(píng)標(biāo)準(zhǔn)進(jìn)行自檢互檢,不符合規(guī)定時(shí)應(yīng)立即糾正,檢查導(dǎo)線的規(guī)格和根數(shù),檢查無誤后再進(jìn)行絕緣檢測(cè)。其絕緣電阻值應(yīng)符合規(guī)范和設(shè)計(jì)規(guī)定的要求。八、電纜安裝準(zhǔn)備工作電纜沿橋架、管道敷設(shè)水平敷設(shè)垂直敷設(shè)掛標(biāo)志牌管口防水處理剝麻刷油掛標(biāo)志牌1、電纜敷設(shè)前應(yīng)對(duì)電纜進(jìn)行詳細(xì)檢查,規(guī)格、型號(hào)、截面、電壓等級(jí)均要符合設(shè)計(jì)要求,外觀無扭曲、損壞現(xiàn)象。2、施工前,應(yīng)對(duì)電纜進(jìn)行絕緣搖測(cè)或耐壓試驗(yàn),在橋架上多根電纜敷設(shè)時(shí),應(yīng)根據(jù)現(xiàn)場(chǎng)實(shí)際情況,事先將電纜的排列用表或圖的方式畫出來,并計(jì)算出電纜長(zhǎng)度,以防電纜的交叉和混亂。3、電纜盤選擇時(shí),應(yīng)考慮實(shí)際
49、長(zhǎng)度是否與敷設(shè)長(zhǎng)度相符,并繪制電纜排列圖,減少電纜交叉。敷設(shè)電纜時(shí),按先大后小、先長(zhǎng)后短的原則進(jìn)行,排列在底層的先敷設(shè)。4、電纜沿支架、托盤、橋架敷設(shè)時(shí)應(yīng)根據(jù)現(xiàn)場(chǎng)情況決定具體敷設(shè)方式,電纜敷設(shè)不應(yīng)交叉,應(yīng)排列整齊,敷設(shè)一根應(yīng)即時(shí)卡固一根。在支架上敷設(shè)時(shí),支架間距不得大于1.5m,要綁扎牢固,托盤上安裝要排列順直。電纜終端頭的引出線應(yīng)保持固定位置,引出線和絕緣包扎長(zhǎng)度,不應(yīng)小于270mm。敷設(shè)于電纜橋架內(nèi)不同系統(tǒng)的線纜中間應(yīng)加隔板。5、垂直敷設(shè)時(shí),采用由上到下的方法:敷設(shè)時(shí)利用總包塔吊將電纜盤放置在最高處,將電纜松開并彎直,然后慢慢沿垂直部分放下去。6、水平敷設(shè)時(shí)將電纜放置在的轉(zhuǎn)盤式放線架上,沿
50、水平方向彎直并逐漸拉放出去。7、無論水平敷設(shè)還是垂直敷設(shè)時(shí),視電纜截面大小,每35米站一人,協(xié)助電纜敷設(shè)直到電纜敷設(shè)到位。采用機(jī)械法敷設(shè)電纜時(shí)應(yīng)事先編制詳細(xì)的施工方案。8、電纜敷設(shè)應(yīng)及時(shí)進(jìn)行標(biāo)識(shí),標(biāo)志牌規(guī)格應(yīng)一致,并有防腐性,掛裝應(yīng)牢固;標(biāo)志牌上應(yīng)注明線路編號(hào)、電纜型號(hào)、規(guī)格、電壓等級(jí)、起止點(diǎn),電纜始端、終端、拐彎處、交叉處應(yīng)掛標(biāo)志牌,直線段每20米設(shè)標(biāo)志牌。電纜敷設(shè)好后,要檢查回路編號(hào)是否正確,完整做好相關(guān)資料。9、垂直電纜穿樓板保護(hù)管時(shí),保護(hù)管的彎曲半徑應(yīng)當(dāng)符合穿入電纜的規(guī)定,管口應(yīng)脹成喇叭形狀,管口磨光無毛刺。10、由于地溝內(nèi)電纜較多,我們將在施工前繪制詳圖,經(jīng)報(bào)審?fù)ㄟ^后予以實(shí)施。11、
51、電纜進(jìn)入建筑物內(nèi)的保護(hù)管必須符合防水要求,安裝見下圖 12、電纜敷設(shè)完畢后,所有電纜通道口均可靠封堵以防鼠害。九、燈具、開關(guān)安裝 1、所有插座均帶安全保護(hù)門,連接單相三孔插座接地插孔的PE線應(yīng)從配電箱引接,不能與插座的N線并接。在衛(wèi)生間、陽(yáng)臺(tái)等潮濕場(chǎng)所應(yīng)采用密閉性能良好插座開關(guān),配帶防油面蓋。2、同一室內(nèi)成排安裝的開關(guān)、插座的高差不應(yīng)大于0.5mm,暗開關(guān)之間留有一定的距離,并距門框0.15-0.20m。開關(guān)位置應(yīng)與燈位相對(duì)應(yīng),開關(guān)向上為開,向下為關(guān),暗裝插座、開關(guān)的面板應(yīng)端正、并緊貼墻面,開關(guān)距地1.3米,插座距地0.3米。3、電器燈具的相線應(yīng)經(jīng)開關(guān)控制,插座的接線孔為單相三孔插座,上孔為保
52、護(hù)接地線,左孔為工作零線,右孔為相線。 4、先將盒內(nèi)甩出的導(dǎo)線留出維修長(zhǎng)度,注意不要碰傷線芯,再將線芯直接接入線孔內(nèi),并用頂絲將其壓緊,然后將開關(guān)或插座推入盒內(nèi),并與墻面平齊,并上緊固定螺絲。 5、在裝修墻面上安裝開關(guān)插座,應(yīng)與裝修工作配合進(jìn)行。十、燈具安裝1、安裝程序燈具檢查燈具組裝燈具安裝通電試運(yùn)行2、燈具的型號(hào)、規(guī)格必須符合設(shè)計(jì)要求和國(guó)家標(biāo)準(zhǔn)的規(guī)定。燈內(nèi)配線嚴(yán)禁外露,燈具配件齊全,無機(jī)械損傷、變形、油漆脫落,燈罩破裂、燈箱歪翹等現(xiàn)象。所有的燈具應(yīng)有產(chǎn)品合格證。3、照明燈具使用的導(dǎo)線其電壓等級(jí)不得低于交流500伏,其最小線芯截面應(yīng)符合規(guī)范要求。4、燈具的安裝嚴(yán)格按說明書、標(biāo)準(zhǔn)圖進(jìn)行,必須格
53、外注意觀感質(zhì)量、標(biāo)高位置要正確可靠,安裝應(yīng)牢固。5、管吊及鏈吊燈具均與所在部位主梁底平,吸頂燈在無吊頂部位安裝時(shí)應(yīng)避開梁邊、墻邊,壁燈安裝高度為2.5m,出口疏散燈安裝于疏散門上方0.1m處,疏散走道的疏散指示燈安裝于走道距地面高度0.5m墻上或柱上。安裝時(shí)可根據(jù)現(xiàn)場(chǎng)實(shí)際裝修及其它已安裝設(shè)備的情況,對(duì)燈具位置作相應(yīng)調(diào)整,不能將燈具裝于風(fēng)管、水管、橋架正上方。十一、調(diào)試1、照明調(diào)試要求a、絕緣電阻測(cè)試:在各回路送電之前進(jìn)行一次絕緣電阻測(cè)試工作,確認(rèn)各回路絕緣電阻達(dá)致規(guī)范要求。b、分支回路送電:每次送電只送一個(gè)回路,不能各回路同時(shí)送電。送電前,關(guān)閉所有開關(guān)。送電后,逐個(gè)打開開關(guān),觀察燈具是否工作正
54、常。檢查完該開關(guān)控制的燈具后即關(guān)上該開關(guān),然后對(duì)下一個(gè)開關(guān)進(jìn)行檢查,依此類推。c、分部分項(xiàng)送電:各回路送電檢查完畢,確認(rèn)無誤后,方可對(duì)該部分燈具進(jìn)行統(tǒng)一送電。每完成一部分調(diào)試,即切斷該部分電源,進(jìn)入下一部分的調(diào)試工作。 調(diào)試準(zhǔn)備a、進(jìn)行各照明線路的絕緣檢查及配電箱和控制柜的接線檢查,確保各送電回路符合送電要求;b、對(duì)其它動(dòng)力線路的絕緣及配電箱和控制柜的接線進(jìn)行檢查,確保送電回路符合送電要求; 2、調(diào)試步驟a、樓層主電源供電電纜絕緣檢查后,通知低壓配電房可以送電,配電房電工確認(rèn)可以送電后,合閘后掛上通電標(biāo)識(shí);b、樓層主電源箱受電后,參照上面的步驟對(duì)各支回路配電,配電至各分配電箱完畢后,掛上送電標(biāo)
55、識(shí);c、電源送至各配電箱后,對(duì)各燈具插座回路再次絕緣檢查后,開始送電,送電完畢后掛上送電標(biāo)識(shí);以上工作必須在專業(yè)施工員的監(jiān)督檢查下進(jìn)行。5.2、給排水工程主要施工工藝.一、管材的選用及連接、 根據(jù)設(shè)計(jì)圖紙要求,管材及連接方式如下表:管道系統(tǒng)管道部位管道材料接口方式備注生活給水、熱水管道干管、立管鋼塑復(fù)合管絲扣或卡箍連接生活給水支管PPR冷水管熱熔連接生活熱水支管PPR熱水管熱熔連接污水泵排水管集水坑熱鍍鋅鋼管絲扣或卡箍連接消火栓管道室內(nèi)消火栓管道熱鍍鋅鋼管溝槽卡箍連接DN150熱鍍鋅鋼管絲扣DN100自動(dòng)噴淋管道室內(nèi)自動(dòng)噴淋管道熱鍍鋅鋼管溝槽卡箍連接DN150熱鍍鋅鋼管絲扣DN100冷凝水管室
56、內(nèi)UPVC塑料管粘接采暖管道地板輻射PE-RT卡套污水排水管道立管鑄鐵管法蘭污水排水管道橫干管UPVC柔性擴(kuò)口排水管橡膠圈管箍連接二、主要施工工序安裝準(zhǔn)備 材料檢查預(yù)留預(yù)埋管道預(yù)制加工干立管安裝閥件安裝支管安裝管道防腐保溫管道沖洗管道試壓系統(tǒng)調(diào)試竣工驗(yàn)收(1)給水管道安裝施工程序:安裝準(zhǔn)備材料檢查預(yù)留預(yù)埋支架安裝管道預(yù)制加工干管安裝立管安裝管道試壓支管安裝管道試壓管道防腐管道沖洗(2)排水管道安裝施工程序:安裝準(zhǔn)備材料檢查預(yù)留預(yù)埋支架安裝立管安裝導(dǎo)管安裝干管安裝通球、灌水試驗(yàn)支管安裝灌水試驗(yàn)承管安裝灌水試驗(yàn)。三、 主要施工方法及技術(shù)措施管道安裝本著“先干管、后支管”的原則進(jìn)行,統(tǒng)一用吊線安裝卡
57、件,支管甩口處應(yīng)加臨時(shí)管堵,立管閥門的朝向應(yīng)便于操作和維修,安裝完后用線墜找正,用卡件固定。安裝時(shí)應(yīng)根據(jù)規(guī)范要求,保持適當(dāng)?shù)钠露龋⒘糇銐虻目臻g以供維修和滿足保溫、裝修等要求。1、 預(yù)留預(yù)埋預(yù)留預(yù)埋是給排水專業(yè)在主體施工中的工作重點(diǎn),它主要包括屋面、地下室水池等的防水套管、穿墻和梁的鋼套管,衛(wèi)生潔具排水預(yù)留洞,管道穿樓板孔洞,設(shè)備基礎(chǔ)預(yù)留孔洞及預(yù)埋件等。預(yù)留預(yù)埋準(zhǔn)確與否對(duì)整個(gè)安裝工程至關(guān)重要。它將直接影響給排水工程施工的順利進(jìn)行。為了保證給排水工程預(yù)留預(yù)埋工作的準(zhǔn)確性,在施工過程中應(yīng)從以下幾個(gè)方面進(jìn)行控制:(1)施工準(zhǔn)備期間,專業(yè)工長(zhǎng)認(rèn)真熟悉施工圖紙,找出所有預(yù)埋預(yù)留點(diǎn),并統(tǒng)一編號(hào),在預(yù)留預(yù)埋
58、圖中標(biāo)注清晰,以便于各專業(yè)的預(yù)留預(yù)埋.同時(shí)與其他專業(yè)溝通,以避免今后安裝有沖、交叉現(xiàn)象,減少不必要的返工。(2)嚴(yán)格按標(biāo)準(zhǔn)圖集加工制作防水套管、穿墻套管,套管長(zhǎng)度按結(jié)構(gòu)施工圖尺寸確定,套管管徑參照下列標(biāo)準(zhǔn):管徑(mm)50-7575-100125-150200-300留洞尺寸(mm)100*100200*200300*300400*400防水套管(mm)114140-159180-219273-325(3)套管安裝a、剛性套管安裝:主體結(jié)構(gòu)鋼筋綁扎好后,按照給排水施工圖標(biāo)高幾何尺寸找準(zhǔn)位置,然后將套管置于鋼筋中,焊接在鋼筋網(wǎng)中,如果需割斷結(jié)構(gòu)鋼筋安裝的,安裝后必須用加強(qiáng)筋加固,并做好套管的防堵
59、工作。b、穿墻套管安裝:土建專業(yè)在砌筑隔墻時(shí),按專業(yè)施工圖標(biāo)高、幾何尺寸將套管置于隔墻中,用砌塊找平后用砂漿固定,然后交給土建隊(duì)伍繼續(xù)施工。c、穿樓板孔洞預(yù)留:預(yù)留孔洞根據(jù)尺寸做好木盒子或鋼套管,確定位置后預(yù)埋,并采用可靠的固定措施,防止其移位。 套管安裝套管安裝位置套管安裝樣圖符號(hào)說明穿地下室建筑外墻柔性防水套管(B型)710984536211-鋼管2-法蘭套管3-密封圈4-法蘭壓蓋5-螺柱6-螺母7-法蘭8-柔性防水樹脂9-建筑外墻10-內(nèi)側(cè)地下水池壁柔性防水套管(A型)1-鋼管2-法蘭套管3-密封圈4-法蘭壓蓋5-螺柱6-螺母7-法蘭8-柔性防水樹脂9-迎水面穿頂板剛性防水套管(鑄鐵管)
60、剛性防水套管(鋼管)1-鑄鐵管2-翼環(huán)3-鋼套管4-柔性防水樹脂1-鋼管2-鋼套管3-翼環(huán)4-擋圈5-柔性防水樹脂穿建筑內(nèi)隔墻套管1-鋼管2-鋼套管3-密封填料4-隔墻5-不銹鋼裝飾板(明露管道適用)穿樓板套管1-鋼管2-鋼套管3-翼環(huán)4-擋圈5-石棉水泥(過衛(wèi)生間樓板時(shí)采用柔性防水樹脂 )6-油麻2、 管道的絲扣連接絲扣連接工藝流程及注意事項(xiàng)如下:斷管套絲配裝管件管段調(diào)直安裝1 管徑在1532mm之間套2次,在4050mm之間套3次,70以上套34次。2 螺紋長(zhǎng)度要符合規(guī)范要求。1 對(duì)小管徑管道可用調(diào)直機(jī)調(diào)直。2 對(duì)于聯(lián)接點(diǎn)彎曲過死或管徑較大的管道采用氣焊加熱調(diào)直。3 鍍鋅鋼管不允許用加熱法
61、調(diào)直。4 管段調(diào)直不允許損壞管材。3、 排水塑料管的承插口連接a、管材或管件在粘合前將承口內(nèi)側(cè)和插口外側(cè)擦拭干凈,無塵砂與水跡。當(dāng)表面沾有油污時(shí),采用清潔劑擦凈。b、管材根據(jù)管件實(shí)測(cè)承口深度在管端表面劃出插入深度標(biāo)記。c、膠粘劑涂刷先涂管件承口內(nèi)側(cè),后涂管件插口外側(cè)。插口涂刷為管端至插入深度標(biāo)記范圍內(nèi)。膠粘劑涂刷應(yīng)迅速、均勻、適量,不得漏涂。d、承插口涂刷膠粘劑后,即找正方向?qū)⒐茏硬迦氤锌冢菏构芏瞬迦胫令A(yù)先劃出的插入深度標(biāo)記處。插入粘接時(shí)將插口稍作轉(zhuǎn)動(dòng),粘接時(shí)要注意預(yù)留方向。擦凈擠出的膠粘劑,靜置至接口固化。e、排水塑料管必須按設(shè)計(jì)要求的位置和數(shù)量裝設(shè)伸縮器。伸縮節(jié)之間的最大距離不得超過4
62、m.管端插入伸縮節(jié)處預(yù)留的間隙應(yīng)為:夏季5-10mm;冬季15-20mm。立管穿越樓層處伸縮節(jié)設(shè)置于水流匯合管件之下。4、 排水立管中心與墻面的距離排水管中心距墻面距離管徑(mm)5075100150距離(mm)608090120 嚴(yán)格按設(shè)計(jì)和規(guī)范要求做好排水管道的坡度,以保證污水暢通排出排水塑料管的坡度管徑(mm)5075100150坡度25151275、 鍍鋅鋼管溝槽連接溝槽連接工藝(1)工藝流程 :安裝準(zhǔn)備滾槽檢查管端檢查橡膠安裝橡膠密封圈連接管端和外殼插螺栓緊螺母(2)安裝準(zhǔn)備.材料準(zhǔn)備:待裝管子(符合國(guó)家標(biāo)準(zhǔn))、施工機(jī)具、安裝腳手架等。.按管路設(shè)計(jì)要求裝好待裝管子的支架、托架。(3)滾槽:.滾槽機(jī)是在使用溝槽接頭作為管道連接件時(shí),對(duì)管子進(jìn)行預(yù)處理的專用工具。操作原理是利用轉(zhuǎn)動(dòng)的壓輪帶動(dòng)管子轉(zhuǎn)動(dòng),管子的徑向方向的隨動(dòng)壓輪徑向施加壓力,從而利用壓輪的結(jié)構(gòu)在管子的固定位置冷壓制一個(gè)規(guī)定的溝槽。滾槽機(jī)應(yīng)放置在一塊寬敞平整的地方,避免機(jī)器在滾槽時(shí)震動(dòng)而影響壓槽質(zhì)量,如機(jī)器不水平,則可通過調(diào)節(jié)地腳螺絲進(jìn)行調(diào)整,直到機(jī)器水平為止。根據(jù)管子大小制作好管子支架,要求能上下伸縮,且擺放平整,并能通過支腳螺絲調(diào)整水平,管子轉(zhuǎn)動(dòng)部位要安裝軸承。壓制管子時(shí)要調(diào)試油壓,一般壓制一個(gè)溝槽按如下時(shí)間控制。規(guī) 格DN80DN100DN125
溫馨提示
- 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請(qǐng)下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請(qǐng)聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁(yè)內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
- 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
- 5. 人人文庫(kù)網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對(duì)任何下載內(nèi)容負(fù)責(zé)。
- 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請(qǐng)與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶因使用這些下載資源對(duì)自己和他人造成任何形式的傷害或損失。
最新文檔
- 換熱器安裝施工方案
- 假言判斷詳解
- 2024-2025學(xué)年河北省廊坊市八年級(jí)(上)期中生物試卷(含解析)
- 【道路運(yùn)輸企業(yè)安全生產(chǎn)管理人員】考試試卷及答案
- 2025年ai易面面試題及答案
- 2025年領(lǐng)導(dǎo)接待面試題及答案
- 6年級(jí)上冊(cè)第5單元單詞
- 5年級(jí)下冊(cè)英語(yǔ)書常用表達(dá)法
- cip號(hào)編碼專著和教材
- 4年級(jí)下冊(cè)語(yǔ)文350字日記怎么寫
- 三峽大壩介紹課件
- 《休閑學(xué)概論》-課程教學(xué)大綱
- 衛(wèi)生部手術(shù)分級(jí)目錄(2023年1月份修訂)
- 2023年廣西水土保持監(jiān)測(cè)站招考聘用模擬檢測(cè)試卷【共500題含答案解析】
- 2023年韶關(guān)北江實(shí)驗(yàn)學(xué)校小升初招生數(shù)學(xué)題
- 眼科學(xué)基礎(chǔ)本科
- 小沈陽(yáng)《四大才子》歡樂喜劇人臺(tái)詞
- 交通安全設(shè)施作業(yè)指導(dǎo)書
- 優(yōu)秀員工榮譽(yù)證書模板
- 城南舊事讀書匯報(bào)教學(xué)課件
- 不銹鋼容器制造通用標(biāo)準(zhǔn)工藝守則
評(píng)論
0/150
提交評(píng)論