1、一、商業(yè)和公共建筑物的空調(diào)設(shè)計(jì)參數(shù)ASHRAE 建筑物室內(nèi)設(shè)計(jì)參數(shù)室內(nèi)空氣流速m/s 循環(huán)空氣 1/h最小新風(fēng) 1/s每人噪聲NC空氣過(guò)濾器效率年能耗MJ/m夏季冬季溫度相對(duì)濕度溫度相對(duì)濕度飲食娛樂(lè)中心 咖啡室 26 40 2123 2030 0.25(1.8m) 1215 5 4050 >35 5704500 餐廳23265560212320300.130.158122.53540>355705700酒吧23265060212320300.15(1.8m)152053550>355704500夜總會(huì)2326506021232030<0.13(1.5m)20301235
2、45>352302800廚房293121230.150.251215全新風(fēng)4050101511404500辦公樓23264050212320300.130.23(410I/s m )4102.5(0.031.3l/sm )304535602803400圖書(shū)館、博物館 檔案室2022 個(gè) 4055 別2022 考4055 慮0.13 <0.13812 8122.5 9143540 353560 1.35 11.85951702800 2801140保齡球中心24265055212320300.25(1.8m)101554050101511402300電訊中心電話 22264050 2
3、126 40500.130.15820 5 60 >85 17005700 電報(bào)23264555212340500.130.1582054050855701700電視臺(tái)2326455523263040<0.13(3.7m)154051525>3511402300運(yùn)輸中心車(chē)房26364130.150.38467.5355010152302300空港大樓 2326 50602123 20300.130.15(1.8m) 812 2.53550>35 11401700海港大樓 23265060212320300.130.15(1.8m)8122.535501015280114
4、0公車(chē)站23265060212320300.130.15(1.8m)8122.535503517002800倉(cāng)庫(kù)個(gè)別考慮142.5 (0.05l/s m)7510352304000二、舒適空調(diào)之室內(nèi)設(shè)計(jì)參數(shù) 日本人體活動(dòng)房間用途夏季冬季運(yùn)行控制條件(冬-夏)Clo等效溫度 。C溫度。C濕度%Clo等效溫度。C溫度。C濕度%Clo等效溫度。C溫度。C濕度%靜坐、輕度活動(dòng)會(huì)場(chǎng)、宴會(huì)廳、禮堂、劇院0.60.925242550700.8122222430501.00.6222522253070坐、輕度活動(dòng)辦公室、銀行、旅館、餐廳、學(xué)校、住宅0.20.428272850701.01.21818
5、2030501.20.2182818283070中等活動(dòng)百貨公司、商店、快餐、打字0.20.416.5252650701.01.216.516.518.530501.20.216.52616.5263070觀覽場(chǎng)所體育館、展覽館0.20.415272850701.11.315151830501.30.2151815283070三、新風(fēng)量1、每人的新風(fēng)標(biāo)準(zhǔn)ASHRAE應(yīng)用場(chǎng)所吸煙程度風(fēng)量1/s單位地板面積1/sm2推薦最小辦公室一般個(gè)人個(gè)人少許無(wú)頗重712145712-1.31.3會(huì)議室銀行經(jīng)紀(jì)董事室極重偶然極重極重245242414414146.0-理發(fā)室美容室、藥室試驗(yàn)室吧臺(tái)頗重偶然少許重7
6、591454712-公寓一般豪華少許少許914712-1.7飯店房間零售店百貨公司小攤重?zé)o無(wú)7-0.3-餐廳自助式餐室頗重頗重6756-廚房在餐廳在住宅-2010醫(yī)院手術(shù)室特別房病房無(wú)無(wú)無(wú)全新風(fēng)149全新風(fēng)127100.7-戲院無(wú)少許4735-工廠走廊廁所(排風(fēng))車(chē)庫(kù)無(wú)-5-4-1.31052、最小新風(fēng)量和推薦新風(fēng)量UK每人所占地板面積m2最小1/s推薦1/s不吸煙吸煙3691211.37.15.24.017.010.77.86.022.614.210.48.03、各類(lèi)建筑物的換氣次數(shù) UK建筑物換氣次數(shù)h-1圖書(shū)館書(shū)架房圖書(shū)館公共場(chǎng)所辦公室、試
7、驗(yàn)室銀行大廳、停車(chē)場(chǎng)、浴室電影院、戲院衛(wèi)生間(排風(fēng))餐廳修車(chē)場(chǎng)(排風(fēng))舞廳 宴會(huì)廳、洗衣店、廚房洗滌(排風(fēng))鍋爐房、發(fā)電機(jī)室廚房(排風(fēng))1-23-44-666-106-88-121010-1210-15153020-604、各場(chǎng)所每小時(shí)換氣次數(shù)場(chǎng)所種類(lèi)次數(shù)場(chǎng)所種類(lèi)次數(shù)一般家庭廚房15戲院觀覽室12寢室6放映室20客廳6病院等候室10廁所10診療室6浴室8手術(shù)室15旅館及大飯店餐廳10消毒室12廚房15工場(chǎng)一般作業(yè)室6大食堂8涂裝室20廁所10一般建筑事務(wù)室6浴室8會(huì)議室12飲食店飲食室6暗室沖洗片室10廚房20宴會(huì)室10公共廁所20學(xué)校禮堂6體育館8有害氣體塵埃發(fā)出地方20以上廁所1
8、2教室6依人數(shù)計(jì)算換氣量換氣對(duì)象換氣量m3/min男人1.41婦女1.16小孩0.75牛馬3.835、每人的新風(fēng)標(biāo)準(zhǔn)UK逗留者密度每人所占地板面積m2吸煙程度風(fēng)量1/s單位地板面積風(fēng)量1/sm2換氣次數(shù)h-1稀8 無(wú)少許重69121.01.41.81.01.52.0密3-7無(wú)少許重912152.83.74.63.04.05.0擠2 無(wú)少許重1215186.78.310.07.09.011.06、考慮節(jié)能的基本新風(fēng)量(1/s人)(日本)主要負(fù)荷房間基本風(fēng)量1/s人體活動(dòng)房間用途無(wú)吸煙有吸煙人體為主要負(fù)荷近于安靜輕活動(dòng)中等活動(dòng)重活動(dòng)辦公室、教室、走廊、大廳、會(huì)議室、百貨店、餐廳、觀眾廳、輕工作舞廳
9、、游戲場(chǎng)、打字室、中等勞動(dòng)體育館、重勞動(dòng)車(chē)間8.5101530 30405060其它美容室、理發(fā)室、吸煙室30-60907、辦公室環(huán)境衛(wèi)生標(biāo)準(zhǔn) 日本溫度相對(duì)濕度%室內(nèi)空氣流速m/s浮游粉塵量mg/m二氧化碳含有率PPM一氧化碳含有率PPM夏季冬季22-2817-2240-700.05-0.02< 0.15< 10<10008、民用建筑最小新風(fēng)量空調(diào)通風(fēng)工程系統(tǒng)運(yùn)行管理規(guī)范(征求意見(jiàn)稿):空調(diào)通風(fēng)系統(tǒng)運(yùn)行期間,新風(fēng)量宜滿足下表的規(guī)定值,或者滿足空氣調(diào)節(jié)房間內(nèi)二氧化碳濃度小于0.1%。民用建筑主要房間人員所需新風(fēng)量m3/(h·P) 房間類(lèi)型新風(fēng)量旅游旅館客房35星級(jí)30
10、2星級(jí)以下22餐廳、宴會(huì)廳、多功能廳35星級(jí)302星級(jí)以下20辦公樓30住宅30中小學(xué)教室小學(xué)11初中14高中17文化娛樂(lè)場(chǎng)所影劇院、音樂(lè)廳、錄像廳20游藝廳、舞廳30酒吧、茶座、咖啡廳10圖書(shū)館、博物館、美術(shù)館30展覽館20體育館觀眾席20商場(chǎng)(店)、書(shū)店設(shè)有空調(diào)裝置20飯店(餐廳) 20公共交通工具旅客列車(chē)車(chē)廂20輪船客艙20飛機(jī)客艙25公共交通等候室侯車(chē)室、侯船室(二等以上)20侯機(jī)室20醫(yī)院侯診室30采暖通風(fēng)與空氣調(diào)節(jié)設(shè)計(jì)規(guī)范(報(bào)批稿)第3.1.9條:(強(qiáng)制性條文)建筑物室內(nèi)人員所需最小新風(fēng)量,應(yīng)符合以下規(guī)定: 民用建筑人員所需最小新風(fēng)量按現(xiàn)行有關(guān)衛(wèi)生標(biāo)準(zhǔn)確定; 工業(yè)建筑應(yīng)保
11、證每人 少于30 m3/h的新風(fēng)量。表3.1.9 民用建筑主要房間人員所需的最小新風(fēng)量參考值m3/(h·P) 房間類(lèi)型新風(fēng)量參考依據(jù)旅游旅館、飯店客房35星級(jí)30GB9663-19962星級(jí)以下20GB9663-1996餐廳、宴會(huì)廳、多功能廳35星級(jí)30GB9663-19962星級(jí)以下20GB9663-1996會(huì)議室、辦公室、接待室35星級(jí)50GB9663-19962星級(jí)以下30GB9663-1996醫(yī)院病房大35GB9663-1996小50GB9671-1996診室25GB9671-1996手術(shù)室60GB9671-1996辦公樓辦公室(無(wú)煙)高級(jí)3550室內(nèi)空氣質(zhì)量標(biāo)準(zhǔn)一般2530
12、室內(nèi)空氣質(zhì)量標(biāo)準(zhǔn)會(huì)議室(無(wú)煙) 3050室內(nèi)空氣質(zhì)量標(biāo)準(zhǔn)學(xué)校教室小學(xué)11GB/T17226-1998初中14GB/T17226-1998高中17GB/T17226-1998文體建筑影劇院、音樂(lè)廳觀眾廳20GB 9664-1996體育館觀眾廳20GB 9668-1996室內(nèi)游泳池 1015GB 9668-1996展覽館、博物館展廳、觀眾廳1015GB 9669-1996圖書(shū)館閱覽室15GB 9669-1996商店 1020GB 9670-1996注 :大學(xué)教室可參照會(huì)議室標(biāo)準(zhǔn)第二章 空調(diào)負(fù)荷計(jì)算一、不同窗面積下,冷負(fù)荷之分布%玻璃窗所占面積%255075人體、燈光、
13、辦公室設(shè)備窗戶新鮮空氣墻362623312274317211225314110二、負(fù)荷指標(biāo)(估算)(僅供參考)建筑類(lèi)型冷負(fù)荷 W/m2(Cal/m2)住宅、公寓、標(biāo)準(zhǔn)客房114138(98118)西餐廳200286(170246)中餐廳257438(220376)火鍋城、燒烤465698(400600)小商店175267(150230)大商場(chǎng)、百貨大樓250400(215344)理發(fā)、美容150225(129193)會(huì)議室210300(180258)辦公室128170(110146)中庭、接待112150(97129)圖書(shū)館90125(77108)展廳、陳列室130200(112172)劇場(chǎng)1
14、80350(154310)計(jì)算機(jī)房、網(wǎng)吧230410(200350)有潔凈要求的廠房、手術(shù)室等300500(258430)三、空調(diào)冷負(fù)荷法估算冷指標(biāo)??照{(diào)冷負(fù)荷法估算冷指標(biāo)(W/m2空調(diào)面積)見(jiàn)下表序號(hào)建筑類(lèi)型及房間名稱(chēng)空調(diào)建筑面積平方米/人建筑負(fù)荷人體負(fù)荷照明負(fù)荷新風(fēng)量W/m新風(fēng)負(fù)荷總負(fù)荷1客房106072050271142宴會(huì)廳1.253013430251903603小會(huì)議室360434025922354大會(huì)議室1.5408840251903585健身房保齡球5358720601302726舞廳3209720331192567科研辦公樓54028402043151商場(chǎng)8底層1.035160
15、40121303659二層1.235128401210430710三層及三層以上24080401265225圖書(shū)館11閱覽室105014302527121展覽廳12陳列室45831202568177會(huì)堂13報(bào)告廳23558402513626914公寓住宅107014205054158硬劇院15觀眾廳0.53022815817444716休息廳27064204021637017化妝室44035502055180體育館18比賽館2.5356540156520519休息廳57027.520408620320貴賓廳85817305068173醫(yī)院21高級(jí)病房11022一般手術(shù)室15023潔凈手術(shù)室30
16、024X光CTB超15025餐館300注:本表為最大負(fù)荷,在求建筑總冷負(fù)荷時(shí),應(yīng)考慮空調(diào)房間同時(shí)使用系數(shù)0.7-0.9四、按建筑面積冷指標(biāo)進(jìn)行估算 建筑面積冷指標(biāo) 建筑名稱(chēng)冷負(fù)荷指標(biāo)W/m²建筑面積建筑名稱(chēng)冷負(fù)荷指標(biāo)W/m建筑面積旅館80-90體育館100-135200-350(按人員座位數(shù))辦公樓85-100圖書(shū)館35-40計(jì)算機(jī)房190-380醫(yī)院80-90數(shù)據(jù)處理320-400商店105-125營(yíng)業(yè)廳設(shè)空調(diào)時(shí),200-250按營(yíng)業(yè)廳面積劇院126-160200-300(按觀眾廳面積)會(huì)堂180-225注:l、上述指標(biāo)為總建筑面積的冷負(fù)荷指標(biāo):建筑面積的總建筑面積小于5000平米
17、時(shí),取上限;大于l0000平米,取下限值。 2、按上述指標(biāo)確定的冷負(fù)荷,即是制冷機(jī)的容量,不必再加系數(shù)。 3、由于地區(qū)差異較大,上述指標(biāo)以北京地區(qū)為準(zhǔn)。南方地區(qū)可按上限采取。熱負(fù)荷估算(l)按建筑面積熱指標(biāo)進(jìn)行估算注:總建筑面積、大外圍結(jié)構(gòu)熱工性能好、窗戶面積小,采用較小的指標(biāo);反之采用較大的指標(biāo)。(2)窗墻比公式法: q=(7a+1.7)W/F(tn-tw)W/m;說(shuō)明:q建筑物的供熱指標(biāo),W/m²。 a 外窗面積與外墻面積(包括窗之比); W一外墻總面積(包括窗),m² F一總建筑面積, m tn一室內(nèi)供暖設(shè)計(jì)溫度, tw一室外供暖設(shè)計(jì)溫度,五、建筑物冷負(fù)荷概算指標(biāo)香港
18、建筑物冷負(fù)荷W/m2逗留者m2/人照明W/m2送風(fēng)量L/sm2顯冷負(fù)荷總冷負(fù)荷辦公室 中部區(qū)周邊個(gè)人辦公室會(huì)議室 65110160185 95160240270 1010153 60606060 5689 學(xué)校 教室圖書(shū)館自動(dòng)餐廳 130130150 190190260 2.561.5 403030 9910 公寓 高層、南向高層、北向 11080 160130 1010 2020 109 戲院、大會(huì)堂試驗(yàn)室圖書(shū)館、博物館 11015095 260230150 11010 205040 12108 醫(yī)院 手術(shù)室公共場(chǎng)所 11050 380150 610 2030 88 衛(wèi)生所、診所理發(fā)室、美容
19、院 130110 200200 104 4050 1010 百貨公司 地下中間層上層 150130110 250225200 1.523 406040 12108 藥店零售店精品店酒吧餐廳 110110110130160 210160160260320 32.5522 3040301517 1010101012 飯店 房間公共場(chǎng)所 80110 130160 1010 1515 78 工廠 裝配室輕工業(yè) 150160 260260 3.515 4530 910 室內(nèi)場(chǎng)所 會(huì)客室一般比賽公開(kāi)比賽 160110110 240220240 653 204080 81212 六、各類(lèi)建筑物鍋爐負(fù)荷估算W
20、/m3建筑物W/m3辦公室劇院觀眾席百貨商店旅館紡織廠0.6-1.20.5-0.90.5-1.11.1-2.01.5-3.00.5-1.2七、熱損失概算W/m3建筑物W/m混凝土建筑(全部)混凝土建筑(最上層)混凝土建筑(中間各層)木結(jié)構(gòu)建筑(全部)木結(jié)構(gòu)建筑(各房間)0.8-1.11.3-2.10.8-1.31.1-1.31.3-1.7W/m一每m3房間容積,室內(nèi)外溫差1時(shí)的熱量W。八、冷庫(kù)冷負(fù)荷概算指標(biāo)冷庫(kù)容積m3KW/100m33100mm隔熱-10150mm隔熱-18200mm隔熱14-3031-6061-120121-220221-440441-900901-14003.73.02.
21、42.11.81.51.23.93.12.52.21.91.61.53.83.12.52.21.91.61.4第三章 風(fēng)管系統(tǒng)設(shè)計(jì)一、通風(fēng)管道流量阻力表1、縮伸軟管摩擦阻力表圓形風(fēng)管v=2 m/sv=3 m/sv=4 m/sv=5 m/sv=6 m/s150127/0.43190/0.98254/1.8318/3.23381/4.46200226/0.32339/0.73452/1.30565/2.03678/2.92250353/0.26530/0.558707/1.04883/1.621060/2.33300509/0.21764/0.951018/1.621273/2.441521/3.
22、582、鍍鋅板風(fēng)管摩擦阻力表矩型風(fēng)管mm風(fēng)量(m3/h)/摩擦阻力(Pa)v=2m/sv=3 m/sv=4 m/sv=5 m/sv=6 m/s120x120104/0.61156/1.27207/2.15259/3.25311/14.57160x120138/0.51207/1.07277/1.8346/2.75415/3.86160x160184/0.42277/0.78369/1.49461/2.26553/3.17200x120173/0.46259/0.95346/1.62432/2.45734/3.44200x160230/0.36346/0.77461/1.3576/1.79691
23、/2.78250x120216/0.41324/0.87432/1.47540/2.23648/250x160288/0.32432/0.69576/1.17720/1.77864/2.48250x200360/0.27540/0.58720/0.99900/1.501080/2.11320x120269/0.38403/0.79537/1.34672/2.03806/2.86320x160369/0.29553/0.61737/1.04922/1.581106/2.22320x200461/0.25691/0.519221/0.871152/1.311382/1.85320x250576/0
24、.21864/0.431152/0.741440/1.121728/1.57400x120336/0.35504/0.74673/1.25841/1.901009/2.67400x160461/0.27691/0.56922/0.951152/1.451382/2.03400x200576/0.22864/0.461152/0.781440/1.201728/1.68400x250720/0.191080/0.381440/0.661800/1.002160/1.40500x160576/ 0.25864/0.521152/0.891440/1.341728/1.89500x200720/0.
25、211080/0.421440/0.731800/1.12160/1.54500x250900/0.171350/0.351800/0.602250/0.902700/1.28500x3201152/0.141728/0.282304/0.492880/0.753456/1.05500x4001440/0.122160/0.252880/0.423600/0.644320/0.89630x160726/0.221089/0.481452/0.841814/1.122177/1.98630x200907/0.191361/0.391814/0.672268/1.022722/1.43630x25
26、01134/0.161701/0.322268/0.552835/0.833402/0.19630x3201452/0.132177/0.262903/0.443629/0.674355/0.94630x4001814/0.112722/0.223629/0.374536/0.565443/0.79630x5002268/0.13402/0.194536/0.315670/0.486804/0.68800x160922/0.201382/0.421843/0.672304/1.022765/2.15800x2001152/0.181728/0.372304/0.632880/0.953456/
27、1.34800x2501440/0.142160/0.32880/0.513600/0.774320/1.08800x3201843/0.12765/0.233686/0.404608/0.605530/0.851000x2001440/0.162160/0.352880/0.603600/0.904320/1.301000x2501800/0.132700/0.283600/0.484500/0.725400/1.021000x3202304/0.113456/0.234608/0.375760/0.576912/0.80圓形風(fēng)管v=2 m/sv=3 m/sv=4 m/sv=5 m/sv=6
28、 m/s10055/0.7683/1.58111/2.68139/4.05166/5.69140109/0.49164/1.03219/1.75273/2.64328/3.72200224/0.31336/0.66448/1.12560/1.69672/2.382503.49/0.24524/0.5698/0.85873/1.281048/1.80360727/0.151090/0.321454/0.541817/0.822180/1.15400898/0.131347/0.281796/0.472245/0.722694/1.015001405/0.12108/0.212811/0.3635
29、13/0.554216/0.77說(shuō)明(1).軟管采用荷蘭數(shù)據(jù)時(shí),上述數(shù)據(jù)乘以下系數(shù):150 x2; 200 x1.8; 250 x1.5; 300 x1.3(2).局部摩擦阻力:散流器喉徑(mm)P (Pa)v=2m/sv=3 m/sv=4 m/sv=5 m/sv=6m/s200x20015.935.763.499.1142.7300x30023.853.595.1148.7214.1400x40029.466.0117.3183.2263.9(3)與散流器的摩擦阻力:接管規(guī)格(mm)P (Pa)v=2m/sv=3 m/sv=4 m/sv=5 m/sv=6m/s鍍鋅管200x2002.45.3
30、9.414.721.2鍍鋅管400x4006.414.3225.539.857.3軟管15010.822.328.841.354.1軟管35010.122.740.463.190.8 (4).保持風(fēng)速必須的動(dòng)壓:當(dāng)v=2m/s時(shí), P=2.4Pa; 當(dāng)v=3m/s時(shí), P=5.4Pa當(dāng)v=4m/s時(shí), P=9.6Pa; 當(dāng)v=5m/s時(shí), P=15Pa當(dāng)v=6m/s時(shí), P=21PaV2(5).其他局部阻力的計(jì)算按下式: 2gP=二、室內(nèi)送回風(fēng)口尺寸表1、風(fēng)口風(fēng)量冷量對(duì)應(yīng)表冷量風(fēng)量m/h送風(fēng)口mm回風(fēng)口mmRTkw1.03.5750700x150800x1501.55.3800700x1508
31、00x1502.071000900x1501000x150/800x2002.58.714501000x2001200x2003.010.516001100x2001300x2003.512.218001250x200/1000x2501500x200/1200x2504.01419501000x2501300x2505.017.5830001600x250/1360x3002、不同送風(fēng)方式的風(fēng)量指標(biāo)和室內(nèi)平均流速ASHRAE送風(fēng)方式單位地板面積的送風(fēng)量l/sm2工作區(qū)平均流速m/s換氣次數(shù)h-1側(cè)送百葉風(fēng)口條形風(fēng)口局部孔板送風(fēng)頂棚散流器頂棚孔板送風(fēng)3-64-105-155-255-500.1
32、3-0.180.10-0.180.10-0.180.10-0.250.05-0、室內(nèi)風(fēng)管風(fēng)速選擇表1、低速風(fēng)管系統(tǒng)的推薦和最大流速m/s應(yīng)用場(chǎng)所住宅公共建筑工廠推薦最大推薦最大推薦最大 室外空氣入口 空氣過(guò)濾器 加熱排管 冷卻排管 淋水室 風(fēng)機(jī)出口 主風(fēng)管 支風(fēng)管(水平) 支風(fēng)管(垂直)2.51.32.32.32.56.04.03.02.54.01.52.52.32.58.56.05.04.02.51.52.52.52.59.06.04.03.54.51.83.02.52.511
33、.08.06.56.02.51.83.03.02.510.09.05.04.08.01.83.53.02.514.011.09.08.02、低速風(fēng)管系統(tǒng)的最大允許速m/s應(yīng)用場(chǎng)所以噪聲控制主風(fēng)管以摩擦阻力控制送風(fēng)主管回風(fēng)主管送風(fēng)支管回風(fēng)支管 住宅 公寓、飯店房間 辦公室、圖書(shū)館 大禮堂、戲院 銀行、高級(jí)餐廳 百貨店、自助餐廳 工廠3.05.06.04.07.59.012.55.07.510.06.510.012.015.04.06.57.55.57.57.59.03.06.08.05.08.08.011.03.05.06.1
34、4.06.06.07.53、通風(fēng)系統(tǒng)之流速m/s系統(tǒng)商業(yè)工業(yè)低 速送風(fēng)、最大流速送風(fēng)、一般流速回風(fēng)、最大流速回風(fēng)、一般流速136-11107.591311-13139-13高速、一般1313-25室內(nèi)允許噪聲dB(A)主管風(fēng)速m/s支管風(fēng)速m/s25-353-4235-504-62-3注:民用住宅35dB(A),商務(wù)辦公45dB(A)。四、室內(nèi)風(fēng)口風(fēng)速選擇表1、送風(fēng)口風(fēng)速臥 室 1.5-2m/s (風(fēng)口在上部時(shí))起 居 2-3m/s (風(fēng)口在上部時(shí))辦 公 室 3m/s (風(fēng)口距地2.5m) 4m/s (風(fēng)口距地4.5m)商場(chǎng)、娛樂(lè) 3-5m/s2、以噪音標(biāo)準(zhǔn)控制的允許送風(fēng)流速m/s應(yīng)用場(chǎng)所流
35、速m/s圖書(shū)館、廣播室住宅、公寓、私人辦公室、醫(yī)院房間銀行、戲院、教室、一般辦公室、商店、餐廳工廠、百貨公司、廚房1.75-2.52.5-4.04.0-5.05.0-7.53、推薦的送風(fēng)口流速m/s應(yīng)用場(chǎng)所流速m/s 播音室 戲院 住宅、公寓、飯店房間、教室 一般辦公室 電影院 百貨店、上層 百貨店、地下1.5-2.52.5-3.52.5-3.8
36、2.5-4.05.0-6.05.07.510.04、送風(fēng)口之最大允許流速m/s應(yīng)用場(chǎng)所盤(pán)形送風(fēng)口頂棚送風(fēng)口側(cè)送風(fēng)口 廣播室 醫(yī)院療房 飯店房間、會(huì)客室 百貨公司、劇場(chǎng) 教室、圖書(shū)館、辦公室3.0-3.54.0-4.54.0-4.56.0-7.55.0-6.04.0-4.54.5-5.05.0-6.06.2-7.56.0-7.52.52.5-3.02.5-4.05.0-7.03.5-4.55、回風(fēng)口風(fēng)速房間凈高風(fēng)口位置風(fēng)速3.5-4上部3-4m/s3-3.5上部2-3m/s2.5-3上部1.5-2m/s人不常停留處下部3m/s人常停留處
37、下部1.5-2m/s走廊回風(fēng)下部1-1.5m/s6、回風(fēng)格柵的推薦流速m/s位置近座位逗留區(qū)以上門(mén)下部門(mén)上部工業(yè)用流速m/s2-33-44347、百葉窗的推薦流速m/s位置新風(fēng)回風(fēng)減溫器正面減溫器旁通加熱器旁通流速m/s2.5-44-62-47.5-125-7.58、逗留區(qū)流速與人體感覺(jué)的關(guān)系流速m/s人體感覺(jué)-0-0.080.1270.127-0.250.380.380.38-1.52 不舒適,停滯空氣的感覺(jué) 理想,舒適 基本舒適 不舒適,可以吹動(dòng)薄
38、紙 對(duì)站立者為舒適感之上限 用于工廠和局部空間9、頂棚散流器送風(fēng)量尺寸mm送風(fēng)流速 m/s1.01.52.02.53.755.0250*250507095120175235300*30070100135170255340350*35090140185230350465400*400120180240295440590500*500190280380470710945600*6002704105456801020136010、側(cè)送風(fēng)口送風(fēng)量送風(fēng)口尺寸mm送風(fēng)口流速m/s1.52.02.53.755.0250*10030405
39、07095300*10035455585115400*100456075115150500*100557595145190600*1007090115170230750*10085115145215285900*100100135170255340250*150455570105145300*150507085130170400*1507090115170230500*15085115145215285600*150100135170255340750*150130170215320430900*150155205255385515400*20090120150230305500*200115
40、150190285380600*200135180230340455750*200170230285430570900*200205275340415685400*250115150190285380500*250145190240355475600*250170230285430570750*250215285355535715900*2502553404306408551000*505575951451901000*75851151452152851000*1001151501902853801000*1251451902403554751000*150170230285430570100
41、0*1752002653305006651000*200230305380570760五、通風(fēng)系統(tǒng)設(shè)計(jì)1、送風(fēng)口布置間距辦 公 室2.5-3.5m商場(chǎng)、娛樂(lè)4-6m回風(fēng)口應(yīng)根據(jù)具體情況布置一般原則:(1)人不經(jīng)常停留的地方; (2)房間的邊和角; (3)有利于氣流的組織。2、標(biāo)準(zhǔn)型號(hào)風(fēng)盤(pán)所接散流器的尺寸表-辦公室風(fēng)盤(pán)型號(hào)風(fēng)量方散尺寸FPm3/hmm3.5350200*2005500200*2006.3630250*2508800250*250101000300*30012.51250300*300161600350*350202500450*450252500450*450注:辦公室推薦送風(fēng)口
42、流速:2.5-4.0m/s風(fēng)機(jī)盤(pán)管接風(fēng)管的風(fēng)速:通常為1.52.0m/s之間,不能大于2.5m/s,否則會(huì)將冷凝水帶出來(lái)。3、散流器布置 散流器平送時(shí),宜按對(duì)稱(chēng)布置或者梅花型布置,散流器中心與側(cè)墻的距離不宜小于1000mm;圓形或方形散流器布置時(shí),其相應(yīng)送風(fēng)范圍(面積)的長(zhǎng)寬比不宜大于1:1.5,送風(fēng)水平射程與垂直射程(平頂至工作區(qū)上邊界的距離)的比值,宜保持在0.51.5之間。實(shí)際上這要看裝飾要求而定,如250*250的散流器,間距一般在3.5米左右,320*320在4.2米左右。4、空調(diào)房間允許最大送風(fēng)溫差送風(fēng)方式下列房間高度m23456側(cè)送、大風(fēng)量側(cè)送、小風(fēng)量頂棚散流器6.59.09.5
43、8.31116101317121518141718舒適性空調(diào)的送風(fēng)溫差送風(fēng)高度H小于等于5m,送風(fēng)溫差小于等于10度;送風(fēng)高度H大于5m,送風(fēng)溫差小于等于15度。為防止出風(fēng)口結(jié)露,應(yīng)使送風(fēng)干球溫度高于室內(nèi)空氣的露點(diǎn)溫度2-3度。5、工藝性空氣調(diào)節(jié)空調(diào)房間允許最大送風(fēng)溫差.室溫允許波動(dòng)范圍(ºC)送風(fēng)溫差(ºC)>±1.0<=15±1.0610±2.036±1.00.223注:生活區(qū)或工作區(qū)處于下送氣流的擴(kuò)散區(qū)時(shí),送風(fēng)溫差應(yīng)通過(guò)計(jì)算確定。6、廚房通風(fēng)問(wèn)題飲食建筑設(shè)計(jì)規(guī)范(JGJ 64-89)對(duì)廚房操作間通風(fēng)作了明確規(guī)定:(1
44、)計(jì)算排風(fēng)量的65%通過(guò)排氣罩排至室外,而由房間的全面換氣排出35%;(2)排氣罩口吸氣速度一般不應(yīng)小于0.5 m/s,排風(fēng)管內(nèi)速度不應(yīng)小于10 m/s;(3) 熱加工間補(bǔ)風(fēng)量宜為排風(fēng)量的70%左右,房間負(fù)壓值不應(yīng)大于5 Pa。然而,有的工程的廚房未設(shè)排氣罩,僅在外墻上設(shè)幾臺(tái)排氣扇;有的雖然設(shè)置了排氣罩,但罩口吸氣速度遠(yuǎn)小于0.5 m/s,選配的排風(fēng)機(jī)風(fēng)量不足。大多工程未設(shè)置全面換氣裝置,亦未考慮補(bǔ)風(fēng)裝置,難以保證室內(nèi)衛(wèi)生環(huán)境要求及負(fù)壓值要求。如何確定廚房的通風(fēng)量公共建筑中的廚房,是一個(gè)很重要的組成部分,但在設(shè)計(jì)上通常是一個(gè)薄弱環(huán)節(jié),一方面,在施工圖紙?jiān)O(shè)計(jì)階段,往往得不到有關(guān)廚房的詳細(xì)工藝資料,在建
溫馨提示
- 1. 本站所有資源如無(wú)特殊說(shuō)明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請(qǐng)下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請(qǐng)聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁(yè)內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒(méi)有圖紙預(yù)覽就沒(méi)有圖紙。
- 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
- 5. 人人文庫(kù)網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對(duì)任何下載內(nèi)容負(fù)責(zé)。
- 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請(qǐng)與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶因使用這些下載資源對(duì)自己和他人造成任何形式的傷害或損失。
最新文檔
- 勞務(wù)合同補(bǔ)充協(xié)議合同范本
- 單位房屋借用合同范本
- 勞動(dòng)使用期合同范本
- 利用合同范本掙錢(qián)
- 上海徐匯金杯租車(chē)合同范本
- 監(jiān)控弱電維護(hù)合同范本
- 醫(yī)院電動(dòng)車(chē)租售合同范本
- 備案的借住合同范本
- 單位之間借支合同范本
- 2003勞務(wù)合同范本
- 2024年湖南環(huán)境生物職業(yè)技術(shù)學(xué)院高職單招職業(yè)技能測(cè)驗(yàn)歷年參考題庫(kù)(頻考版)含答案解析
- 《化工流程教案》課件
- 后循環(huán)缺血治療
- 體育學(xué)科核心素養(yǎng)解析
- 2024年浙江紹興杭紹臨空示范區(qū)開(kāi)發(fā)集團(tuán)有限公司招聘筆試真題
- 2025年體檢科醫(yī)療質(zhì)量控制工作計(jì)劃
- 2024年萍鄉(xiāng)衛(wèi)生職業(yè)學(xué)院?jiǎn)握新殬I(yè)適應(yīng)性測(cè)試題庫(kù)參考答案
- 飛行器小學(xué)生課件
- 無(wú)人機(jī)法律法規(guī)與安全飛行 第2版2-2 領(lǐng)空
- 《單片機(jī)應(yīng)用實(shí)訓(xùn)教程》課件第4章
- 應(yīng)急突發(fā)處置
評(píng)論
0/150
提交評(píng)論