ICS29.240.01

F24

RecordNo.44815-2014DL

ElectricPowerIndustryStandardofthePeople’sRepublicofChina

DL/T1341—2014

TechnicalGuideforLiveWorkingon

±660kVDCTransmissionLine

IssueDate:March18,2014ImplementationDate:August1,2014

IssuedbyNationalEnergyAdministrationofthePeople’sRepublicofChina

I

Foreword

ThisstandardwascompiledinaccordancewiththetaskarrangedbyNoticeoftheNationalEnergy

AdministrationonIssuingtheFirstBatchofIndustryStandardFormulation(Revision)PlansintheEnergy

Sectorin2010(No.320oftheDepartmentofScienceandTechnologyoftheNationalEnergy

Administration).

ThisstandardwasproposedbytheChinaElectricityCouncil.

ThisstandardwaspreparedbytheNationalTechnicalCommitteeofStandardizationforLiveWorking.

Maindraftingorganizationsofthisstandard:ChinaElectricPowerResearchInstitute,StateGridShandong

ElectricPowerCompany,andStateGridShanxiElectricPowerCompany.

Maindraftersofthisstandard:LIUKai,HUYi,XIAOBin,LIUHongzheng,LIUTing,MENGHailei,YONG

Jun,NIUBiao,DONGYanwu,LIUYan,PENGYong,andSUZiming.

Duringtheprocessofimplementingthisstandard,relevantopinionsoradvicecanbefedbacktothe

StandardizationManagementCenteroftheChinaElectricityCouncil(No.1,Lane2,BaiguangRoad,Beijing,

100761).

II

TechnicalGuideforLiveWorkingon±660kVDCTransmissionLine

1Scope

Thisstandardspecifiesthetechnicalrequirementsandmattersneedingattentionforliveworkingon±660kVDC

transmissionlines,aswellasthetest,transportationandstorageoftheworkingtools.

Thisstandardisapplicabletoliveworkingon±660kVDCtransmissionlinesinareaswithanaltitudeof2000m

andbelow.

2Normativereferences

Thefollowingreferenceddocumentsareindispensablefortheapplicationofthisdocument.Fordatedreferences,

onlytheeditioncitedapplies.Forundatedreferences,thelatesteditionofthereferenceddocument(includingany

amendments)applies.

GB/T2900.55ElectrotechnicalTerminology—LiveWorking(eqvIEC60050—651)

GB/T6568ScreenClothesforLiveWorking(GB/T6568—2008,IEC60895:2002,MOD)

GB/T13035LiveWorking—InsulatingRopes

GB13398InsulatingHollowTubesandFoam-FilledTubesandSolidRodsforLiveWorking

GB/T14286LiveWorking—TerminologyforTools,EquipmentandDevices(GB/T14286—2008,IEC60743:

2001,MOD)

GB/T18037TechnicalRequirementsandDesignGuideforLiveWorkingTools

GB26859SafetyCodeofElectricPowerIndustry—PartofElectricLines

DL/T463InsulatorHolderforLiveWorking

DL/T876GuideofInsulationCoordinationforLiveWorking

1

DL/T878TestGuideoftheInsulatingToolforLiveWorking

DL/T966TechnicalGuideforLiveWorkinginTransmissionLine

DL/T974DepotofToolsforLive-Working

DL/T976PreventiveTestCodeofTools,DevicesandEquipmentforLiveWorking

3Termsanddefinitions

Forthepurposesofthisstandard,thetermsanddefinitionsgiveninGB/T2900.55andGB/T14286aswellasthe

followingapply.

3.1liveworkingonDCtransmissionline

live-linerepair,maintenance,andreplacementofpartscarriedoutonDCtransmissionlines

3.2potentialrod

metaltoolusedbyanequipotentialworkerwhenenteringorleavingequipotential,inordertoreducetheimpactof

dischargearconthehumanbodyandavoidpossibledamagetoconductiveclothingcausedbypulsedcurrent

3.3electricfieldshieldmask

maskmadeofconductivematerials,usedforelectricfieldprotectionoftheworker'sface,andconnectedwithother

screentoolsforintegraluse

4Generalrequirements

4.1Personnelrequirements

4.1.1Liveworkingworkersshallbeingoodhealthandfreefromphysicalandpsychologicalobstaclesthathinder

work.Theyshallhaveabasicknowledgeofelectricalprinciplesandpowerlines,masterthebasicprinciplesand

operatingmethodsofliveworking,andbefamiliarwiththescopeofapplicationandusingmethodsoftheworking

2

tools.TheyshallbefamiliarwithGB26859,DL/T966andthisstandard.Theyshallmasteremergencyrescue

methods,especiallytheelectricshockrescue.Theyshallreceivetheoreticalandoperationaltrainingfrom

specializedtraininginstitutions,passrelevantexaminationsandholdrelevantcertificates.

4.1.2Thepersoninchargeofthework(orthesafetyguardian)shallhaveatleast3yearsofactualworking

experienceinliveworkingonpowertransmissionlines,befamiliarwithequipmentconditions,havecertain

organizationalcapabilityandaccidenthandlingability,andpasstheexaminationafterspecialtraining.

4.2Institutionalrequirements

AccordingtoGB26859andthisstandard.

4.3Meteorologicalrequirements

4.3.1Liveworkingshallbecarriedoutingoodweather.Incaseofthunder,rain,snowandfog,liveworkingshall

notbecarriedout.Whenthewindforceisgreaterthanlevel5(10m/s),liveworkingshouldnotbecarriedout.

4.3.2Ifliveworkingisrequiredinweatherwithrelativehumiditygreaterthan80%,insulatingtoolswith

moisture-proofperformanceshallbeadopted,andthepossibilityofinsulationdegradationoftheinsulatingtools

underhighhumidityshallbeconsidered.

4.3.3Underspecialoremergentconditions,whenemergentlive-linerepairmustbecarriedoutinharshclimate,

relevantengineeringandtechnicalpersonnelandallworkingpersonnelshallbeorganizedtofullydiscussand

formulatereliablesafetymeasuresaccordingtothesiteclimateandworkingconditions,andtheemergentlive-line

repaircanbecarriedoutonlyaftertheapprovalofthechiefengineeroftheunitortheleaderinchargeof

productionoftheunit.Sufficientlightingfacilitiesshallbeprovidedfornightwork.

4.3.4Incaseofasuddenchangeofweatherduringliveworking,whichcanendangerpersonalorequipmentsafety,

theworkshallbestoppedimmediately.Undertheconditionofensuringpersonalsafety,thenormalworking

conditionsoftheequipmentshallberestoredassoonaspossibleorotherprotectivemeasuresshallbetaken.

4.4Otherrequirements

3

4.4.1Fornewliveworkingprojectsthataremorecomplicatedandmoredifficultandnewdevelopedtools,

scientifictestsshallbeconductedtoconfirmsafetyandreliability,andsafetymeasuresandoperationprocessplans

shallbeestablished,andthetoolscanbeoperatedonequipmentonlyaftertheapprovalofthechiefengineerofthe

unitortheleaderinchargeofproductionoftheunit.

4.4.2Thepersoninchargeofliveworkingshallcontactthedispatcherbeforetheworkstarts,andtheworkcanbe

startedonlyaftercontacting.WhenitisnecessarytodisableDCrestartprotectiondevices,thelicenseformalities

shallbeperformed.Aftertheworkisfinished,reportingtothedispatchershallbedoneintime.Itisstrictly

prohibitedtostoporresumetherestartprotectiondevicesatanappointedtime.

5Technicalrequirements

5.1Groundpotentialworking

5.1.1Whentheworkerworksatgroundpotential,theminimumworkingdistancebetweentheworkeratground

potentialonthetowerandtheliveconductorsshallmeettheprovisionsofTable1.

Table1Minimumworkingdistanceofgroundpotentialworking

Altitude/mMinimumworkingdistance/m

≤5004.2

500~10004.5

1000~15004.7

1500~20005.0

Note:Thevaluesinthetabledonotincludethespaceoccupiedbythehumanbody,whichshallnotbelessthan

0.5mandshallbeconsideredatwork.

5.1.2Theminimumeffectiveinsulationlengthofinsulatingtools,devicesandequipmentshallmeettheprovisions

ofTable2.

Table2Minimumeffectiveinsulationlengthofinsulatingtools,devicesandequipment

Altitude/mMinimumworkingdistance/m

≤5005.0

500~10005.3

1000~15005.6

1500~20005.9

4

5.2Barehandworking

5.2.1Duringbarehandworking,theminimumworkingdistancebetweentheequipotentialworkerandtheearthing

conductorsshallmeettheprovisionsofTable3.

Table3Minimumworkingdistanceofbarehandworking

Minimumworkingdistance/m

Distancebetweenthe

Distancebetweenthe

Altitude/mequipotentialworkerand

equipotentialworkerand

thetopcrossarmorthe

thesidetowerframe

topframe

≤5004.24.8

500~10004.55.1

1000~15004.75.3

1500~20005.05.6

Note:Thevaluesinthetabledonotincludethespaceoccupiedbythehumanbody,whichshallnotbeless

than0.5mandshallbeconsideredatwork.

5.2.2Whentheworkerentersorleavesequipotentialviainsulatingtoolsoralonginsulatorstrings,theminimum

combinedgapshallmeettheprovisionsofTable4.

Table4Minimumcombinedgap

Altitude/mMinimumcombinedgap/m

≤5004.3

500~10004.6

1000~15004.8

1500~20005.1

Note:Thevaluesinthetabledonotincludethespaceoccupiedbythehumanbody,whichshallnotbelessthan

0.5mandshallbeconsideredatwork.

5.2.3Whentheequipotentialworkerentersorleavesequipotentialalongtensioninsulatorstrings,thenumberof

insulatorsshort-circuitedbythehumanbodyshouldnotbemorethan4.Theminimumnumberofgoodinsulators

shallmeettheprovisionsofTable5afterthenumberofinsulatorsshort-circuitedbythehumanbodyandbad

insulatorsisdeductedfromthetensioninsulatorstrings.

5

Table5Minimumcombinedgapandtheminimumnumberofgoodinsulators

MinimumtotallengthoftheStructureheightofeachTheminimumnumberofgood

Altitude/m

goodinsulatorstring/minsulator/mminsulators

17026

19523

≤5004.4

20522

24019

17028

19525

500~10004.7

20523

24020

17030

19526

1000~15005.0

20525

24021

17032

19528

1500~20005.3

20526

24023

5.3Safetyprotection

5.3.1TheequipotentialworkershallwearTypeIIconductiveclothingandflameresistantunderwearaccordingto

GB/T6568.

5.3.2Theworkeratgroundpotentialonthetowershallwearafullsetofelectrostaticprotectiveclothingor

conductiveclothing.

5.3.3Theinsulatedoverheadgroundwireshallberegardedasaliveconductor,andtheworkersshallkeepa

distanceof0.6mfromit.Ifitisnecessarytoworkontheoverheadgroundwire,itshallbegroundedwellthrougha

dedicatedearthingcable.Themethodsandstepsforhangingordismantlingthededicatedearthingcableonthe

overheadgroundwirearethesameasthoseforhangingordismantlingtheearthingcableonapower-offline.After

hangingupthededicatedearthingcableandwearingafullsetofelectrostaticprotectiveclothingorconductive

clothing,theworkersmaycarryoutmaintenance.

5.3.4Foranopticalfibercompositeoverheadgroundwire(OPGW)groundedbyeachtowerfoundationorother

directlygroundedoverheadgroundwires,theworkersmaydirectlycarryoutmaintenanceworkbywearingafull

6

setofelectrostaticprotectiveclothingorconductiveclothing.Ifitisnecessarytodisconnectthedirectlygrounded

overheadgroundwiresfromtheground,theoverheadgroundwiresshallbehungwithearthingcablesbefore

maintenance.

5.3.5Beforeoverhaulinginthemiddleoftheoverheadgroundwirespan,inordertoensurehis/hersafety,the

workershallcheckwhethertheverticaldistancebetweenhim/herandtheliveconductorsbelowmeetsthe

minimumworkingdistancerequirementsaftertheoverheadgroundwireintheworklocationisloadedbyhim/her,

andwhetherthemechanicalstrengthoftheoverheadgroundwiremeetsrelevantrequirements.

5.3.6Whenworkingontheuni-polarpower-offside(theotherpoleisrunning),theworkershallwearafullsetof

electrostaticprotectiveclothingorconductiveclothing.

5.3.7Whenusinginsulatingropestotransferlargemetalobjects,theworkeratgroundpotentialoronthetower

shallgroundthemetalobjectsbeforetouchingthem.

5.3.8Withregardtolargemetalobjects(e.g.automobiles,etc.)insulatedfromthegroundandplacednearstrong

electricfields,attentionshallbepaidtoprotectingpeoplefrominducedelectricalinjury.Themetalobjectsmustbe

groundedbeforetheycanbetouched.

5.4Potentialtransfer

5.4.1Theequipotentialworkershallobtainpermissionfromthepersoninchargeoftheworkbeforepotential

transferandshallnotlosetheprotectionofthesafetybelt.

5.4.2ForpotentialtransferofDCtransmissionlines,thepotentialrodshouldbeused,whichshallbeinreliable

contactwithliveconductors.Beforeenteringequipotential,theworkershallcontactthepotentialrodquicklywith

theliveconductorsatadistanceofabout0.4mfromthem.Whenleavingequipotential,theworkershallcontactthe

potentialrodwiththeliveconductorsfirst,andthenwithdrawthepotentialrodquicklyafterleavingthelive

conductors0.4maway.

5.4.3Duringpotentialtransfer,theactionshallbesmooth,accurateandfast.

7

6Enterorleaveequipotential

6.1Enterorleaveequipotentialonasuspensiontower

6.1.1Whenenteringorleavingequipotentialonasuspensiontower,theworkershallnotenterorleave

equipotentialverticallyfromthecrossarmsoralongtheinsulatorstrings.Thehangingbasket(hangingchairand

hangingladder)method,theinsulatingflexibleladdermethodandothermethodsmaybeusedtoenterandleave

equipotential.

6.1.2Whentheworkerentersorleavesequipotential,alltheelectricalgapdistances(includingtheworking

distancesandthecombinedgaps)betweentheworkerandtheearthingconductorsandtheliveconductorsshall

meettherequirementsofTables3andTable4.

6.1.3Thehangingbaskets(hangingchairsandhangingladders)shallbestablysuspendedbyinsulatingslings,and

themovingspeedshallbestrictlycontrolledbyinsulatingpulleysetstoachieveauniformandslowspeed.The

lengthoftheinsulatingslingsforfixingshallbeaccuratelycalculatedoractuallymeasuredtoensurethatthe

highestpartofthehumanbodyshallnotexceedtheupperedgeofthegradingringontheconductorsidewhenthe

workerentersorleavesequipotential.

6.2Enterorleaveequipotentialonatensiontower

6.2.1Whenenteringorleavingequipotentialonatensiontower,theworkermayenterorleaveequipotentialalong

horizontaltensioninsulatorstringsorviaothermethods.

6.2.2Whentheworkermovesalongthehorizontaltensioninsulatorstrings,thepositionsofhis/herhandsandfeet

mustbekeptconsistent,andthenumberofgoodinsulatorsshort-circuitedbythehumanbodyandtoolsshallmeet

therequirementsofTable5.

6.2.3Theworker’ssafetyprotectionropeshallbetiedtotheinsulatorstringheldbyhis/herhandsandshallmove

synchronouslywithhim/her.

6.2.4Whenenteringorleavingequipotential,theworkershalltransferpotentialwhenmovingtoadistanceof

about0.4m(2~3insulators)fromtheliveconductorsbeforecarryingoutsubsequentoperations.

8

6.2.5Alltheelectricalgapdistances(includingtheworkingdistancesandthecombinedgaps)betweentheworker

andtheearthingconductorsandtheliveconductors,andthenumberofgoodinsulatorsshort-circuitedbythe

humanbodyortoolsshallmeettherequirementsofTable5.

7Mattersneedingattentionatwork

7.1Theworkersshallavoidexcessivebodymovementsduringliveworking.

7.2Insulatingtoolsshallbeusedtotransferarticlesbetweentheequipotentialworkerandthegroundpotential

worker.TheeffectivelengthoftheinsulatingtoolsshallmeettherequirementsofTable2.

7.3Theconductiveclothingshallbefreefromdamageandholes,andallpartsofitshallbeconnectedwelland

reliably.Whendamageandburrsarefound,itshallberepairedintime,anditcanbeusedonlyafterpassingthe

test.

7.4Beforetheinsulatingtoolsareused,aninsulationresistancetestershallbeusedtoconductsegmented

insulationtests.Thewidthofthemeasuringelectrodesis2cm,anditisrequiredthattheinsulationresistance

betweenevery2cmofmeasuringelectrodesshallnotbelessthan700MΩ.

7.5Theinsulatingtoolsshallbeprotectedfrommoistureandsurfacedamageanddirtwhenused.Theinsulating

toolstobeusedshallbeplacedonclean,dryandmoisture-proofpads.Whenfounddampenedorsurface-damaged

orsurface-dirty,theyshallbehandledintimeandcanbeusedonlyafterpassingthetest.

7.6Duringthework,bearingtoolsshallbefixedandreliableandhavebackupprotection.

7.7Ifdeterioratedorlowresistanceinsulatorsarefoundduringlivetestingofinsulators,theyshallberetested2-3

timestoavoidmisjudgment.

7.8Whenthefirstinsulatornearthecrossarmisdismantledorinstalled,itmustbeshort-circuitedbeforeoperation.

8Testoftools,devicesandequipment

8.1Thedesignofliveworkingtools,devicesandequipmentshallconformtotherequirementsofGB/T18037.

9

Conductiveclothing,insulatingropes,insulatingrods,insulatorholders,etc.,shallpasstypetestsandleaving

factorytestsinaccordancewiththerequirementsofGB/T6568,GB/T13035,GB13398,DL/T463,DL/T878.

8.2Thetools,devicesandequipmentshallbesubjectedtoelectricaltestsandmechanicaltestsonaregularbasis

accordingtothetestmethodsofDL/T976.Thetestcyclesareasfollows:

a)electricaltests.Preventivetestsshallbeconductedonceayear,andinspectiontestsshallbeconductedoncea

year,andtheintervalbetweentwotestsshallbehalfayear.

b)mechanicaltests.Preventivetestsshallbeconductedonceeverytwoyearsforinsulatingtoolsandonceevery

yearformetaltools.

8.3Preventivetests

8.3.1DCwithstandvoltagetest:theinsulationlengthofthetestsamplebetweenthetestelectrodesshallbe4.8m;

thewithstandvoltageshallbe755kV;thetimesh

溫馨提示

  • 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
  • 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
  • 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
  • 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
  • 5. 人人文庫網(wǎng)僅提供信息存儲(chǔ)空間,僅對用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對任何下載內(nèi)容負(fù)責(zé)。
  • 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請與我們聯(lián)系,我們立即糾正。
  • 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。

最新文檔

評論

0/150

提交評論