版權說明:本文檔由用戶提供并上傳,收益歸屬內容提供方,若內容存在侵權,請進行舉報或認領
文檔簡介
目次
1總則·········································································1
2術語·········································································2
3基本規(guī)定··································································6
4查勘評估··································································7
4.1一般規(guī)定···························································7
4.2供水管道查勘與評估··············································7
4.3二次供水泵站查勘與評估·········································9
4.4排水管道查勘與評估············································12
4.5排水泵站查勘與評估············································15
4.6供熱管道查勘····················································18
4.7熱力站查勘·······················································19
4.8供熱系統(tǒng)評估····················································21
4.9燃氣管道查勘與評估············································23
4.10燃氣調壓設施查勘與評估······································24
5改造方案·································································26
5.1一般規(guī)定·························································26
5.2供水管道·························································27
5.3二次供水泵站····················································28
5.4排水管道·························································30
5.5排水泵站·························································34
5.6供熱管道·························································35
5.7熱力站····························································37
5.8燃氣管道·························································39
5.9燃氣調壓設施····················································40
5.10檢測與控制·····················································41
6施工與驗收······························································44
6.1一般規(guī)定·························································44
6.2基坑(槽)施工與質量驗收····································45
6.3管道施工與質量驗收············································45
6.4二次供水泵站、排水泵站、熱力站、燃氣調壓
設施施工與質量驗收·············································46
6.5竣工驗收·························································47
附錄A二次供水泵站質量評估·······································48
附錄B功能性缺陷維護指數(shù)計算····································53
附錄C結構性缺陷修復指數(shù)計算····································55
附錄D排水泵站質量評估·············································58
附錄E排水泵站安全狀況評估········································64
附錄F供熱系統(tǒng)查勘評估指標標準值·······························67
附錄G燃氣管道評估···················································69
附錄H鋼質管道外腐蝕評價級別····································73
附錄I鋼質管道管體腐蝕評價級別··································75
附錄J調壓站、調壓裝置評估·······································76
附錄K排水管道改造技術路線圖····································80
本標準用詞說明····························································81
引用標準名錄·······························································82
條文說明······································································85
Contents
1GeneralProvisions·······················································1
2Terms·······································································2
3BasicRequirements····················································6
4SurveyandAssessment················································7
4.1GeneralRequirements·················································7
4.2SurveyandAssessmentofWaterSupplyPipelines·················7
4.3SurveyandAsssessmentofSecondaryWaterSupply
PumpingStation·······················································9
4.4SurveyandAssessmentofSewerPipelines························12
4.5SurveyandAssessmentofDrainagePumpingStation············15
4.6SurveyofCityHeatingPipelines···································18
4.7SurveyofSubstation·················································19
4.8AssessmentofHeatingSystem······································21
4.9SurveyandAssessmentofGasPipelines··························23
4.10SurveyandAssessmentofGasPressureRegulators·············24
5TransformationScheme···············································26
5.1GeneralRequirements················································26
5.2WaterSupplyPipelines··············································27
5.3SecondaryWaterSupplyPumpingStation·························28
5.4SewerPipelines······················································30
5.5DrainagePumpingStation···········································34
5.6CityHeatingPipelines···············································35
5.7Substation·····························································37
5.8GasPipelines·························································39
5.9GasPressureRegulators·············································40
5.10MeasuringandControl·············································41
6ConstructionandAcceptance········································44
6.1GeneralRequirements················································44
6.2ConstructionandQualityAcceptanceofExcavation
(groove)·····························································45
6.3ConstructionandQualityAcceptanceofPipelines················45
6.4ConstructionandQualityAcceptanceofSecondary
WaterSupplyPumpingStation,DrainagePumping
Station,SubstationandGasPressureRegulator···················46
6.5CompletionAcceptance··············································47
AppendixAQualityAssessmentofSecondaryWaterSupply
PumpingStation··········································48
AppendixBCalculationofMaintenanceIndexofFunctional
Defect·······················································53
AppendixCCalculationofRepairIndexofStructuralDefect
·······························································55
AppendixDQualityAssessmentofDrainagePumpingStation
·······························································58
AppendixESafetyAssessmentofDrainagePumpingStation
·······························································64
AppendixFStandardvalueofSurveyAssessmentIndexof
HeatingSystem···········································67
AppendixGAssessmentofGasPipelines··························69
AppendixHAssessmentGradeofSteelPipelineExternal
Corrosion··················································73
AppendixIAssessmentGradeofSteelPipelineInternal
Corrosion··················································75
AppendixJAssessmentofPressureRegulatingStationand
Equipment··················································76
AppendixKTechnologyRoadmapofSewerPipelines
Reconstruction·············································80
ExplanationofWordinginthisSpecification······················81
ListofQuotedStandards·················································82
ExplanationofProvisions·················································85
1總則
1.0.1為規(guī)范城鎮(zhèn)市政老舊管網改造工程,保障市政老舊管網改造
后的功能與使用安全,制定本標準。
1.0.2本標準適用于城鎮(zhèn)永久性室外供水、排水、供熱和燃氣老舊
管道改造工程。
1.0.3改造工程應采用新技術、新工藝、新材料和新設備,提高管
網質量,保障管網運行安全,節(jié)約能源和資源,降低工程造價和運
行成本。
1.0.4市政老舊管網改造工程除符合本標準的規(guī)定外,尚應符合國
家和河北省現(xiàn)行有關標準的規(guī)定。
1
2術語
2.0.1管道防腐corrosionpreventionofpipes
為減緩或防止管道在內外介質的化學、電化學作用下或由微生
物的代謝活動而被侵蝕和變質的措施。
2.0.2疊壓供水pressuresuperposedwatersupply
利用室外供水管網余壓直接抽水再增壓的二次供水方式。
2.0.3氣壓供水pneumaticwatersupply
由水泵和壓力罐以及一些附件組成,水泵將水壓入壓力罐,依
靠罐內的壓縮空氣壓力,自動調節(jié)供水流量和保持供水壓力的供水
方式。
2.0.4二次供水secondarywatersupply
當民用與工業(yè)建筑生活飲用水對水壓、水量的要求超過城鎮(zhèn)公
共供水或自建設施供水管網能力時,通過儲存、加壓等設施經管道
供給用戶或自用的供水方式。
2.0.5二次供水設施secondarywatersupplyinstallation
為二次供水設置的泵房、水池(箱)、水泵、閥門、電控裝置、
消毒設備、壓力水容器、供水管道等設施。
2.0.6設備完好率equipmentperfectness
完好的生產設備在全部生產設備中的比重。
2.0.7結構性缺陷structuraldefect
排水管道及檢查井結構本身遭受損傷,影響強度、剛度和使用
壽命的缺陷,是地下水等外來水入滲、污水外滲的主要通道。
2.0.8功能性缺陷functionaldefect
導致排水管道及檢查井過水斷面發(fā)生變化,影響通暢性能的缺
2
陷,其中淤泥等沉積物是影響水體環(huán)境質量的主要因素。
2.0.9結構性缺陷修復指數(shù)structuraldefectrehabilitationindex
依據(jù)管道結構性缺陷類型、嚴重程度、數(shù)量以及影響因素計算
得到的數(shù)值。數(shù)值越大表明管道修復的緊迫性越大。
2.0.10功能性缺陷維護指數(shù)functionaldefectmaintenanceindex
依據(jù)功能性缺陷的類型、嚴重程度、數(shù)量以及影響因素計算得
到的數(shù)值。數(shù)值越大表明管道維護的緊迫性越大。
2.0.11截污調蓄池regulatingreservoirofsewageintercepting
用于控制混接污水、初期雨水,以及污染道路清掃、澆灑、綠
化、路邊餐飲、洗車等經雨水口進入,而非直接接入污水的調蓄池。
2.0.12低影響開發(fā)(LID)lowimpactdevelopment
強調城鎮(zhèn)開發(fā)應減少對環(huán)境的沖擊,其核心是基于源頭控制和
延緩沖擊負荷的理念,構建與自然相適應的城鎮(zhèn)排水系統(tǒng),合理利
用景觀空間和采取相應措施對暴雨徑流進行控制,減少城鎮(zhèn)面源污
染。
2.0.13柔性管道flexiblepipeline
在外荷載作用下變形顯著的管道,豎向荷載大部分由管道兩側
土體所產生的彈性抗力所平衡,管道的失效通常由變形造成而不是
管壁的破壞。本標準主要指鋼管、化學建材管和柔性接口的球墨鑄
鐵管管道。
2.0.14柔性接口flexiblejointofpipelines
能承受一定量的軸向線變位和相對角變位的管道接口,如用橡
膠圈等材料密封連接的管道接口。
2.0.15壓實度compactingdensity
土或其他回填材料壓實后的干密度與標準擊實試驗法求得的最
大干密度之比,以百分率表示。
3
2.0.16供熱系統(tǒng)heatingsystem
由熱源通過供熱管網向用戶供應熱能的設施總稱。
2.0.17市政供熱管網districtheatingnetwork
以熱電廠或區(qū)域鍋爐房為熱源,自熱源經市政道路至熱力站的
供熱管網。
2.0.18街區(qū)供熱管網blockheatingnetwork
自熱力站或鍋爐房、熱泵機房等小型熱源至建筑熱力入口的室
外供熱管網。
2.0.19熱力站heatingstation
用來轉換供熱介質種類,改變供熱介質參數(shù),分配、控制及計
量供給熱用戶熱量的綜合體。
2.0.20水力平衡hydraulicbalance
熱水供熱系統(tǒng)運行時供給各熱力站(或熱用戶)的實際流量與
規(guī)定流量數(shù)值的一致性。
2.0.21安全閥safetyvalve
安裝在設備或管道上,當設備或管道中的介質壓力超過規(guī)定值
時能自動開啟卸壓的閥門。
2.0.22除污器strainer
熱水供熱系統(tǒng)中用于阻留、收集并便于清除循環(huán)水中的污物和
雜質的裝置。
2.0.23調壓裝置regulatordevice
將較高燃氣壓力降至所需的較低壓力調壓單元的總稱。包括調
壓器及其附屬設備。
2.0.24調壓站regulatorstation
將調壓裝置放置于專用的調壓建筑物或構筑物中,承擔用氣壓
力的調節(jié)。包括調壓裝置及調壓室的建筑物或構筑物等。
4
2.0.25調壓箱(調壓柜)regulatorbox
將調壓裝置放置于專用箱體,設于用氣建筑物附近,承擔用氣
壓力的調節(jié)。包括調壓裝置和箱體。懸掛式和地下式箱稱為調壓箱,
落地式箱稱為調壓柜。
2.0.26聚乙烯燃氣管道polythylenepipe
由燃氣用聚乙烯管材、管件、閥門及附件組成的管道系統(tǒng)。聚
乙烯管材是用聚乙烯混配料通過擠出成型工藝生產的管材;聚乙烯
燃氣管件是用聚乙烯混配料通過注塑成型等工藝生產的管件。
2.0.27非開挖施工trenchlessinstallation
在管道沿線地面下開挖成形的洞內敷設或澆筑管道(渠)的施
工方法,有頂管法、盾構法、淺埋暗挖法、定向鉆法、夯管法等。
2.0.28非開挖修復更新技術trenchlessrehabilitationandrenewal
采用不開挖或少開挖地表的方法進行管道修復更新的技術。
5
3基本規(guī)定
3.0.1改造工程應采用設計使用年限長、性能好、抗災能力強的主
材和輔材。
3.0.2管道系統(tǒng)的改造應與城市規(guī)劃、道路提升改造、舊城(含城
中村)改造統(tǒng)籌謀劃、系統(tǒng)推進、同步實施。改建管道平面位置和
高程,應根據(jù)地形、土質、地下水位、道路、支線出入情況、現(xiàn)狀
和規(guī)劃地下設施、施工條件以及養(yǎng)護管理條件等因素綜合考慮確定。
3.0.3城市供水、排水、供熱、燃氣工程構筑物和管道的結構必須
進行抗震設計。相應的抗震設防類別及設防標準,應符合現(xiàn)行國家
標準《建筑工程抗震設防分類標準》GB50223的有關規(guī)定。
6
4查勘評估
4.1一般規(guī)定
4.1.1查勘時,應查閱相關圖紙等技術資料;并應現(xiàn)場查勘管道、
設備、建(構)筑物、供配電、安防、檢測控制系統(tǒng)的運行、配置、
能耗、安全等情況。
4.1.2缺乏相關資料時,應采用測量和物探方法查明情況。
4.1.3現(xiàn)場查勘時,應避免對現(xiàn)有管道及設施造成損傷。
4.1.4建(構)筑物的評估應符合現(xiàn)行國家及行業(yè)標準《危險房屋
鑒定標準》JGJ125、《工業(yè)建筑可靠性鑒定標準》GB50144、《既
有混凝土結構耐久性評定標準》GB/T51355的有關規(guī)定。
4.2供水管道查勘與評估
4.2.1查勘應查閱以下資料:
1供水范圍、供水管道管材、管徑、壓力及供水用戶。
2竣工圖紙。
3投入運行時間。
4近2年維修改造記錄。
4.2.2現(xiàn)場應查勘以下項目:
1管道管材、管徑、布置形式和敷設方式。
2管道及附屬設施工作情況、腐蝕情況。
3閥門和計量設施位置、規(guī)格型號、安裝數(shù)量。
4消火栓、消防水鶴位置,控制閥門的嚴密性及工作狀況。
7
5排氣、泄水裝置的設置及工作情況。
6閥門井等附屬設施結構狀況。
7用戶入戶壓力、用水狀況。
4.2.3在查勘基礎上進行綜合評估,并形成評估報告。評估報告應
包括以下內容:
1概述。
2運行狀況評估。
1)運行年限、管材。
2)用戶入戶壓力、用水量。
3)年維修次數(shù)。
4)附屬設施使用及完好狀況。
3風險安全評估。
1)管道在供水系統(tǒng)中的重要性。
2)供水管道基于水質安全的檢驗報告。
3)供水管道運行記錄。
4)系統(tǒng)缺陷及安全隱患分析。
4評估的結論。
4.2.4綜合評估應符合下列規(guī)定:
1供水系統(tǒng)運行狀況良好,各項指標合格,在用管道定期檢查
結果符合有關安全技術規(guī)范及標準的規(guī)定,可不進行改造。
2供水水量、水壓和水質評估不達標的供水系統(tǒng),應進行改造。
3管道存在安全隱患的供水系統(tǒng)應根據(jù)表4.2.4進行評估。評
估為I級時,不進行改造;評估為II級時,應進行局部改造;評估
為III級時,應進行整體或局部改造。
8
表4.2.4供水管道安全隱患評估表
等級
序號評估項目
I級II級III級
嚴重不滿足規(guī)范要
滿足規(guī)范要求,局部不滿足規(guī)范要
1管道敷設位置求,嚴重影響安全
可正常使用求,影響正常使用
和正常使用
防腐層完好,無防腐層基本完好,少銹蝕嚴重,影響正
2管道防腐
銹蝕量銹蝕,不影響使用常使用
發(fā)現(xiàn)2處及以上漏
漏點數(shù)量發(fā)現(xiàn)1處漏點,漏水
3未發(fā)現(xiàn)漏點點,漏水量大于
及漏水量量不大于1.0×10-4m3/s
1.0×10-4m3/s
閥門、排氣閥等無銹蝕,開關靈少量銹蝕,能正常開銹蝕嚴重,影響正
4
附屬設施活有效,無滴漏關,無滴漏常開關,出現(xiàn)滴漏
4.3二次供水泵站查勘與評估
4.3.1查勘應查閱以下資料:
1泵站內供水系統(tǒng)的設計圖紙及竣工圖紙。
2投入運行時間。
3歷年維修改造資料。
4相關設備技術參數(shù)和近2年的運行記錄。
5產權單位、管理方式。
6設備配置、供水范圍、供水人數(shù)、供水量、供水水質、供水
系統(tǒng)分區(qū)及系統(tǒng)劃分、系統(tǒng)運行時間。
7近2年的電耗情況。
4.3.2現(xiàn)場應查勘以下內容:
1二次供水泵站的形式。
2進水量、壓力。
3管道及設備防腐、保溫狀況。
4水泵:
1)水泵型號、臺數(shù)、額定參數(shù)、生產廠家、投入運行
9
時間。
2)水泵實際運行流量、進出口壓力及功率。
3)水泵變頻情況。
5水箱(池):
1)水箱(池)的材質、數(shù)量、生產廠家、衛(wèi)生合格證、投
入運行時間。
2)水箱(池)總容積、有效容積及液位測量方式。
6供配電系統(tǒng):
1)供配電系統(tǒng)結構及負荷。
2)用電設備的額定功率和額定電流、實際運行的耗電量。
3)用電分項計量情況。
4)用電設備運行及使用情況。
5)接地形式。
7自控、安防系統(tǒng):
1)系統(tǒng)變頻情況。
2)信號采集及遠傳情況。
3)視頻監(jiān)控及門禁情況。
8建筑結構:
1)具體位置。
2)建筑修建年代、結構形式及狀況。
3)隔振、降噪、通風設施狀況。
4.3.3在查勘基礎上進行綜合評估,并形成評估報告。評估報告應
包括以下內容:
1概述。
2運行狀況評估。
1)運行年限、使用環(huán)境狀況。
10
2)服務用戶數(shù)量、供水水量、供水水壓。
3)設備年維修次數(shù)。
4)設備使用及完好狀況。
5)水泵的運行效率。
6)系統(tǒng)變頻及信號傳輸完好狀況。
3風險安全評估。
1)在供水系統(tǒng)中的重要性。
2)基于水質安全的檢驗報告。
3)運行記錄。
4)系統(tǒng)缺陷及安全隱患分析。
4評估的結論。
4.3.4綜合評估應符合下列規(guī)定:
1二次供水泵站質量應按本標準附錄A有關規(guī)定進行評估,
控制項評估不達標時,應進行改造。
2控制項達標評分項得分大于等于70分時,二次供水泵站可
不改造。
3控制項達標評分項得分大于等于60分且小于70分時,二次
供水泵站宜進行改造。
4控制項達標評分項得分小于60分時,二次供水泵站應進行
改造。
5二次供水泵站建(構)筑物改造應根據(jù)現(xiàn)行國家及行業(yè)標準
《危險房屋鑒定標準》JGJ125和《既有混凝土結構耐久性評定
標準》GB/T51355有關規(guī)定進行評估。
11
4.4排水管道查勘與評估
4.4.1查勘應查閱以下資料:
1竣工圖紙。
2投入使用時間。
3區(qū)域內的排水管道和其他地下管線資料。
4歷年查勘、維修改造資料。
5近2年的外溢、積水等記錄資料。
4.4.2現(xiàn)場應查勘以下項目:
1區(qū)域內的地物、地貌、交通狀況等周邊環(huán)境條件。
2檢查井位置、管渠埋深、管徑、管材等。
3檢查井、管渠、雨水口、排放口結構狀況及功能狀況。
4雨污水管道混接情況。包括混接點位置、混接點流量和混接
點水質等內容。
5閘門及啟閉設備的嚴密性、控制方式等工作狀況。
4.4.3雨污水管道結構狀況及功能狀況應根據(jù)表4.4.3進行檢查。
表4.4.3雨污水管道狀況檢查內容
檢查類別檢查項目
檢查井、雨水口及排放口積泥,管渠沉積、結垢、障礙物、樹根、洼水、殘
功能狀況
墻、壩頭、浮渣,水位和水流、井蓋缺損、有毒有害氣體等。
管渠脫節(jié)、變形,支管暗接、錯位、滲漏、腐蝕,膠圈脫落、破裂與空洞,
結構狀況
異物侵入,倒坡,塌陷,異管穿入等。
4.4.4雨污水管道檢查方法及適用范圍見表4.4.4。檢測方法及設備
要求應根據(jù)現(xiàn)行行業(yè)標準《城鎮(zhèn)排水管道檢測與評估技術規(guī)程》
CJJ181有關規(guī)定執(zhí)行。對于老舊管道,除開展缺陷檢測查勘外,還
應對其剩余強度進行相關檢測查勘。
12
表4.4.4雨污水管道檢查方法及適用范圍
中小型大型以功能結構
檢查方法倒虹管檢查井
管道上管道狀況狀況
電視檢測√√√—√√
聲吶檢測√√√—√√
管道潛望鏡檢測√√—√√√
潛水檢查—√—√√√
量泥斗檢查———√√—
反光鏡檢查√√—√√—
染色檢查√√√—√—
煙霧檢查√√√—√—
注:表中“√”表示適用,“—”表示不適用。
4.4.5在查勘基礎上進行綜合評估,并形成評估報告。評估報告應
包括以下內容:
1概述。
2缺陷評估。
1)功能性缺陷評估。
2)結構性缺陷評估。
3混接狀況評估。
4評估結論。
4.4.6綜合評估應符合下列規(guī)定:
1排水管道缺陷評估。
1)管道功能性狀況評定應根據(jù)表4.4.6-1進行,表中功能
性缺陷維護指數(shù)MI計算詳見本標準附錄B有關規(guī)定。
13
表4.4.6-1管道功能性狀況等級評定
功能性缺陷維護指數(shù)MIMI<44≤MI<7MI≥7
功能性狀況等級一級二級三級
注:檢查井功能缺陷評估可參照管道功能性缺陷評估進行。
2)管道結構性狀況評定應根據(jù)表4.4.6-2進行,表中結構
性缺陷修復指數(shù)RI計算詳見本標準附錄C有關規(guī)定。
表4.4.6-2管道結構性狀況等級評定
結構性缺陷修復指數(shù)RIRI<44≤RI<7RI≥7
結構性狀況等級一級二級三級
注:檢查井結構缺陷評估可參照管道結構性缺陷評估進行。
3)管道評估應以管段為最小評估單位。當對多個管段或區(qū)
域管道進行檢測時,應列出各評估等級管段數(shù)量占全部
管段數(shù)量的比例。當連續(xù)檢測長度超過5km時,應作
總體評估。
2混接狀況評估。
混接點混接程度分級標準應根據(jù)表4.4.6-3執(zhí)行。按照混接管管
徑、混接水量、混接水質中任一指標高值的原則來確定。
表4.4.6-3單個混接點混接程度分級標準
接入管管徑流入水量污水流入水質
評價參數(shù)
d(mm)Q(m3/d)CODcr(mg/L)
重度混接(3級)d≥600Q>600CODcr>200
中度混接(2級)300≤d<600200<Q≤600100<CODcr≤200
輕度混接(1級)d<300Q≤200CODcr≤100
14
3評估結論。
1)存在功能性缺陷的排水管段:
管道功能性狀況等級為一級時,表現(xiàn)為無或有少量設施
局部超過允許淤積標準,功能狀況總體較好??刹痪S護
或僅對超標管段維護。
管道功能性狀況等級為二級時,表現(xiàn)為有較多設施超過
允許淤積標準,功能狀況總體較差??删植炕蛉婢S護。
管道功能性狀況等級為三級時,表現(xiàn)為大部分設施超過
允許淤泥標準,功能狀況總體很差。應全面維護。
2)存在結構性缺陷的排水管段:
管道結構性狀況等級為一級時,表現(xiàn)為少量或無設施損
壞,結構狀況總體較好??刹恍迯突蚓植啃迯?。
管道結構性狀況等級為二級時,表現(xiàn)為有較多設施損壞
或個別處出現(xiàn)中等或嚴重的缺陷,結構狀況總體較差。
應整體或局部修復,局部修復時,對存在滲漏或導致滲
漏的2級及以上結構缺陷等級管道,必須進行修復。
管道結構性狀況等級為三級時,應緊急修復或翻新。
3)存在混接情況的排水管段:
重度混接的管道必須進行改造。
中度混接的管道,可分期進行改造。
輕度混接的管道,應列入改造計劃。
4.5排水泵站查勘與評估
4.5.1查勘應查閱以下資料:
1產權所屬單位、管理方式。
15
2設計圖紙、竣工圖紙。
3投入運行時間。
4歷年維修改造資料。
5相關設備技術參數(shù)和近2年的運行記錄。
6設備配置、服務面積。
4.5.2現(xiàn)場應查勘以下項目:
1現(xiàn)有排水能力、裝機容量。
2進出水管管徑、標高。
3集水池容積、運行水位、檢修最低水位。
4水泵:
1)水泵型號、類別、額定參數(shù)、臺數(shù)、生產廠家、投入運
行時間。
2)水泵實際運行流量、揚程及輸入功率。
3)水泵配備電機情況。
5格柵:
1)格柵型號、類別、額定參數(shù)、臺數(shù)、生產廠家、投入運
行時間。
2)格柵尺寸、安裝角度及柵條間距。
3)格柵配備電機情況。
6閘門、啟閉機:
1)閘門及啟閉機的型號、規(guī)格、臺數(shù)、安裝位置、生產廠
家、投入運行時間。
2)閘門的材質、止水水頭、密封方式。
3)啟閉機的啟閉方式、啟閉力及配備電機情況。
7供配電系統(tǒng):
1)供配電系統(tǒng)結構及負荷。
16
2)用電設備的額定功率和額定電流、實際運行的耗電量。
3)用電分項計量情況。
4)用電設備運行及使用情況。
5)接地型式。
8建筑結構:
1)具體位置。
2)建筑修建年代、結構形式及狀況。
3)隔振、降噪設施狀況。
4.5.3在查勘基礎上進行綜合評估,并形成評估報告。評估報告應
包括以下內容:
1概述。
2運行質量評估。
1)泵站工藝。
2)電氣機械設備。
3)自控系統(tǒng)。
4)運行管理。
3安全狀態(tài)評估。
1)建、構筑物。
2)電氣機械設備。
4評估的結論。
4.5.4綜合評估應符合下列規(guī)定:
1排水泵站質量評估及安全狀況評估根據(jù)本標準附錄D和附
錄E有關規(guī)定執(zhí)行。
2現(xiàn)有合流泵站,應根據(jù)進出水管道的分流改造同步進行改
造。
3運行質量存在缺陷的排水泵站,應根據(jù)排水泵站質量評估結
17
果進行改造完善,并符合下列規(guī)定:
1)控制性指標存在缺陷的排水泵站,應對控制項進行改造。
2)控制項指標符合要求評分項得分大于等于70分時,排
水泵站可不改造。
3)控制項指標符合要求評分項得分大于等于60分且小于
70分時,排水泵站宜進行改造。
4)控制項指標符合要求評分項得分小于60分時,排水泵
站應進行改造。
4安全狀況存在缺陷的排水泵站,應根據(jù)安全狀況評估結果進
行改造。
1)一類排水泵站,暫不改造。
2)二類排水泵站,宜維修養(yǎng)護。
3)三類排水泵站,應通過大修、加固、拆除重建等方式更
新改造。
4)四類排水泵站,應拆除重建。
4.6供熱管道查勘
4.6.1查勘應查閱以下資料:
1產權所屬單位。
2供熱范圍、實際供熱面積、供熱負荷、供熱半徑、介質種類、
設計參數(shù)、供熱天數(shù)。
3竣工圖紙。
4投入運行時間。
5歷年維修改造資料。
6近2年的運行記錄:包括供回水壓力、溫度、補水量等。
18
4.6.2現(xiàn)場應查勘以下項目:
1管道布置、管徑、敷設方式、熱力站、建筑物分布情況等。
2管道及設備工作情況、腐蝕情況。
3補償器型式、安裝位置、規(guī)格、安裝長度及補償量。
4檢查室及管溝結構狀況。
5支架類型、位置及工作狀況。
6管道及設備保溫狀況。
7管道關閉閥、調控閥位置,閥門嚴密性及工作狀況。
8放氣、放水裝置設置及工作情況。
4.7熱力站查勘
4.7.1查勘應查閱以下資料:
1產權所屬單位。
2設計圖紙及竣工圖紙。
3投入運行時間。
4歷年維修改造資料。
5熱力站內設備配置、供熱范圍、供熱面積、供熱負荷、用熱
單位類型、供熱系統(tǒng)類型、系統(tǒng)運行時間。
6相關設備技術參數(shù)和近2年的運行記錄。
7近2年熱、電、水等能源消耗情況。
4.7.2現(xiàn)場應查勘以下項目:
1熱力站連接形式。
2市政管道、街區(qū)管道供回水溫度、壓力。
3管道及設備保溫狀況。
4換熱器:
19
1)型號、臺數(shù)、額定參數(shù)、生產廠家、投運時間。
2)熱力站實際運行參數(shù),換熱設備與熱負荷的匹配情況。
3)換熱性能。
4)供回水壓力、溫度。
5)工作狀況。
6)保溫狀況。
5水泵:
1)型號、額定參數(shù)、臺數(shù)、生產廠家、投運時間。
2)實際運行流量、進出口壓力及功率。
3)變頻情況。
6補水定壓、水處理設備:
1)補水泵型號、額定參數(shù)、臺數(shù)、生產廠家、投運時間。
2)補水定壓方式、定壓參數(shù)、補水量記錄。
3)水處理額定參數(shù)、容量、出水水質。
4)補水水質。
5)補水箱的類型、容量及液位測量方式。
6)補水計量設備規(guī)格型號。
7供配電系統(tǒng):
1)供配電系統(tǒng)結構及負荷。
2)用電設備的額定功率和額定電流、實際運行的耗電量。
3)用電分項計量情況。
4)用電設備運行及使用情況。
5)接地型式。
8熱計量系統(tǒng):
1)熱計量裝置的計量記錄。
2)熱計量裝置的規(guī)格型號、數(shù)據(jù)存儲及遠傳情況。
20
9自動控制調節(jié)系統(tǒng):
1)監(jiān)測及自動調節(jié)控制設備情況。
2)氣候補償、分時分區(qū)控制情況。
3)循環(huán)水泵調節(jié)控制方式。
4)定壓補水控制方式。
10熱力站建筑結構:
1)具體位置。
2)建筑修建年代、結構形式及狀況。
3)隔振、降噪、通風設施狀況。
11建筑物內供暖系統(tǒng)及戶內熱環(huán)境:
1)建筑物內供暖形式,戶內散熱設備類型及不同類型所占
比例。
2)建筑物戶內供暖設計溫度、實際溫度、用戶測溫記錄。
3)室溫調節(jié)方式。
4)建筑物內水平、垂直熱力失調情況。
5)公共管道狀況及保溫情況。
4.8供熱系統(tǒng)評估
4.8.1在查勘基礎上進行綜合評估,并形成評估報告。評估報告應
包括以下內容:
1概述。
2供熱質量評估。
1)建筑物戶內溫度、室溫調控情況。
2)不同室外溫度時段鍋爐、熱力站供回水溫度及循環(huán)
水量。
21
3)室溫不達標的原因分析,并提出改造內容。
3管道風險安全評估。
1)壓力容器及壓力管道按照國家質量技術監(jiān)督管理部門
的相關要求進行定期檢驗的報告。
2)供熱管道基于風險的全面檢驗報告,管道的全面檢驗
應根據(jù)現(xiàn)行行業(yè)標準《壓力管道定期檢驗規(guī)則公用
管道》TSGD7004的有關要求進行。
3)電力設施及其他特種設備滿足相應特種設備使用的要
求,定期檢查維護,并取得具有相應資質部門出具的
檢定合格報告(證)。
4)供熱系統(tǒng)運行記錄。
5)檢查室及管溝結構等工作狀況,支吊架、固定支架工
作環(huán)境及工作狀況。
4運行能耗評估。
1)供熱期總供熱面積以及對應的總供熱量。
2)供暖期能源總消耗量:熱量、水量、電量。
3)單位面積的能源消耗量:熱量、水量、電量。
4)設備及管道保溫效果測定評估。
5)供熱系統(tǒng)運行效率。
6)供熱系統(tǒng)運行調節(jié)控制水平、水力平衡狀態(tài)。
7)節(jié)能潛力分析。
5評估的結論。
4.8.2供熱系統(tǒng)綜合評估應符合下列規(guī)定:
1供熱系統(tǒng)運行良好,能耗指標合格,管道定期檢查結果符合
有關安全技術規(guī)范及標準,不進行改造。
2供熱質量和能耗評估不達標,管道無安全缺陷的供熱系統(tǒng)進
22
行相應局部改造。
3供熱系統(tǒng)查勘評估指標的標準值見本標準附錄F有關規(guī)定。
4.9燃氣管道查勘與評估
4.9.1查勘應查閱以下資料:
1產權所屬單位、管理方式。
2供氣范圍、核對實際供氣量、供氣壓力、燃氣類別。
3竣工圖。
4投入運行時間。
5歷年維修改造資料。
6最近一次檢查及評估報告。
4.9.2現(xiàn)場應查勘以下項目:
1管道布置、管徑、管材、敷設方式及管線與周圍其他管道、
建(構)筑物間距環(huán)境等情況,判斷地區(qū)等級是否發(fā)生變化。
2支架位置及工作情況。
3閥門(井)位置、井內附件、閥門嚴密性及工作狀況。
4管道運行壓力情況。
5管道防腐及實測腐蝕坑等情況。
6管道防雷、接地有效性情況。
4.9.3在查勘基礎上進行綜合評估,并形成評估報告。評估報告應
包括以下內容:
1概述。
2風險安全評估。
3評估的結論。
4.9.4綜合評估應按下述原則進行:
23
1風險安全評估。
1)根據(jù)《壓力管道定期檢驗規(guī)則公用管道》TSGD7004
的有關要求對燃氣管道進行全面檢驗。
2)根據(jù)本標準附錄G對燃氣管道設施和操作進行檢查評
價。
3)根據(jù)本標準附錄H和附錄I對管道腐蝕情況進行評估。
2評估結論。
1)燃氣管道運行良好、管道定期檢查結果符合相關安全技
術規(guī)范(標準)時,不進行改造。
2)燃氣管道設施和操作評價不合格時,應進行相應部位
改造。
3)管道外腐蝕評價級別為ⅣA級、ⅣB級、Ⅴ級或鋼質管
道管體腐蝕評價級別為第四、五類時,該管道應進行改
造。
4.10燃氣調壓設施查勘與評估
4.10.1查勘應查閱以下資料:
1產權所屬單位、管理方式。
2供氣范圍、設備進出口壓力、燃氣類別等。
3竣工圖。
4歷年檢查及維護記錄。
4.10.2現(xiàn)場應查勘以下內容:
1設備安裝周圍情況是否滿足安全要求。
2閥門嚴密性情況。
3調壓閥調節(jié)靈敏性情況。
24
4調壓設施的安全設施情況。
5防雷、接地情況。
6泄露報警裝置情況。
7當設備有電加熱系統(tǒng)時,應查看供電情況。
4.10.3調壓設施應在勘察基礎上進行綜合評估,并形成評估報告。
評估報告應包括以下內容:
1概述。
2風險安全評估。
3評估的結論。
4.10.4綜合評估應符合下列規(guī)定:
1風險安全評估。
1)調壓設施應按照國家質量技術管理部門的相關要求進
行定期檢驗并取得合格報告。
2)分析說明調壓設施設置是否能滿足相關規(guī)范要求,是
否存在危險因素。
3)根據(jù)本標準附錄J對調壓站、調壓裝置設施與操作進
行評價。
2評估結論。
1)調壓設施運行良好,定期檢查結果符合相關安全技術規(guī)
范(標準)要求時,不進行改造。
2)評估項不符合要求或存在隱患時,進行相應局部改造。
25
5改造方案
5.1一般規(guī)定
5.1.1管道改造方案應根據(jù)管道查勘評估報告、規(guī)劃要求、分析計
算結果、管道統(tǒng)籌情況、現(xiàn)場實施條件等限制因素來確定。
5.1.2管道布置時應避免和減少穿越不容易通過的地帶和建(構)
筑物。當必須穿越時,應采取必要的處理或交叉措施。
5.1.3改造管道通過不允許開挖的城市道路、公路、鐵路、河流、
橋梁時,宜選用非開挖施工技術或非開挖修復更新技術。
5.1.4老舊管道改造工程方案的編制應包括項目概述、分析計算、
設計方案、施工方案、投資等內容。設計、施工方案應對用戶改造
過程中、過程后的影響進行分析,并采取措施。
5.1.5方案分析計算應符合下列規(guī)定:
1供水改造方案包括流量、管徑、設備容積和設備壓力等內容
分析計算。
2排水改造方案包括管徑、流量、設備揚程和構筑物規(guī)模等內
容分析計算。
3供熱改造方案包括熱負荷、管徑、設備、保溫、管道應力和
作用力等內容分析計算。
4燃氣改造方案包括供氣負荷、管徑、設備、管道應力、水力
計算等內容分析計算。
5.1.6改造管道路由應滿足城市規(guī)劃要求,當有管廊建設時,改造
管道應與管廊建設統(tǒng)籌考慮。入廊管線設置應符合現(xiàn)行國家標準《城
市綜合管廊工程設計規(guī)范》GB50838的要求。
26
5.1.7改造工程必須采用質量合格的材料與設備。供水管道工程的
材料與設備還必須滿足衛(wèi)生安全要求。
5.1.8與腐蝕性介質接觸的管道及其接口、構筑物和附屬設施必須
采用耐腐蝕材料或者采取相應的防腐蝕措施。
5.2供水管道
5.2.1供水管道管徑宜采用原有管徑。如果所服務街區(qū)用戶有所變
化,應結合城鎮(zhèn)給水規(guī)劃調整管徑。
5.2.2供水管道材質的選擇,應根據(jù)管徑、內壓、外部荷載和管道
敷設區(qū)的地形、地質、管材的供應情況,按照運行安全、耐久、減
少漏損、施工和維護方便、經濟合理以及供水管道防止二次污染的
原則,進行技術、經濟、安全等綜合分析確定。
5.2.3供水管道的接口應根據(jù)管材不同選擇相應的接口方式,宜采
用柔性接口。
5.2.4金屬管材應采取防腐措施。內防腐宜采用水泥砂漿襯里或飲
用水涂料,外防腐宜采用環(huán)氧煤瀝青、膠粘帶等措施。
5.2.5同一用戶不同性質用水,應分別設置獨立供水管道。
5.2.6居民用水水表應出戶設置,分戶計量。
5.2.7采用非開挖修復更新技術時,應符合現(xiàn)行行業(yè)標準《城鎮(zhèn)給
水管道非開挖修復更新工程技術規(guī)程》CJJ/T244的有關規(guī)定。
5.2.8供水管道施工時,應采取敷設臨時供水管道等措施避免用戶
停水。
5.2.9供水管道改造應采取防止水質污染的措施。
27
5.3二次供水泵站
5.3.1同一用戶用水性質不同時,應分別設置二次供水加壓系統(tǒng)。
5.3.2泵房嚴禁與污水、中水泵房連通。
5.3.3二次供水泵站所用材料、成品、設備應符合衛(wèi)生安全要求,
必須具備省級及以上的涉水產品衛(wèi)生許可批件和質量監(jiān)督部門出具
的產品檢驗報告。
5.3.4二次供水泵站應采取下列安全防范措施:
1應獨立設置,并應有建筑圍護結構。
2應有防凍、防曝曬、防雷擊等有效的防護措施。
3應配備門禁、攝像等安全防范設施。
4儲水裝置應有反恐的技防、物防安全防范措施。
5宜設置遠程監(jiān)控系統(tǒng)。
5.3.5二次供水系統(tǒng)可采用下列供水方式:
1增壓設備和高位水箱(池)聯(lián)合供水。
2變頻調速供水。
3疊壓供水。
4氣壓供水。
5.3.6變頻調速泵組電源應可靠,并宜采用雙電源或雙回路供電方
式。
5.3.7當采用疊壓供水方式時,不得造成該區(qū)域公共供水管網的水
壓低于本地規(guī)定的最低供水服務壓力,并且應得到當?shù)毓┧块T審
查批準。
5.3.8可能對市政供水管網造成回流污染、危害水質的行業(yè)與用戶
不得使用疊壓供水。研究、制造、加工、儲存有毒物質、藥品等危
險化學物質的場所,也不得使用疊壓供水。
28
5.3.9變頻水泵宜采用獨立的變頻調節(jié)裝置。
5.3.10二次供水設備應有銘牌,標明生產單位、注冊商標、生產日
期、出廠編號、執(zhí)行標準、技術參數(shù)等主要內容。
5.3.11水箱和壓力容器材質應采用不銹鋼材料,焊接材料應與水箱
和壓力容器材質
溫馨提示
- 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯(lián)系上傳者。文件的所有權益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網頁內容里面會有圖紙預覽,若沒有圖紙預覽就沒有圖紙。
- 4. 未經權益所有人同意不得將文件中的內容挪作商業(yè)或盈利用途。
- 5. 人人文庫網僅提供信息存儲空間,僅對用戶上傳內容的表現(xiàn)方式做保護處理,對用戶上傳分享的文檔內容本身不做任何修改或編輯,并不能對任何下載內容負責。
- 6. 下載文件中如有侵權或不適當內容,請與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準確性、安全性和完整性, 同時也不承擔用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。
最新文檔
- 2025年二手家電交易策劃合同樣本
- 2025年雙方委托項目投資協(xié)議合同模板
- 2025年醫(yī)院綠化保潔服務長期合同范文
- 2025年企業(yè)解除策劃代理合同書
- 2025年產品檢測與合格認證合同書
- 2025年云計算技術轉讓合同范本
- 2025年雙邊貿易售后服務合同范本
- 2025年企業(yè)環(huán)境藝術施工合同樣本
- 2025年企業(yè)合資經營協(xié)議范本
- 2025年停車場車位使用權互換合同協(xié)議
- 2025年中國郵政招聘筆試參考題庫含答案解析
- 人教版(2024)七年級英語上冊新教材的變化及教學建議課件
- 2025年中考語文一輪復習:九年級上冊知識點梳理
- 2025年新聞部工作計劃
- 中國近代史綱要西安財經大學練習題復習資料
- 中國成人ICU鎮(zhèn)痛和鎮(zhèn)靜治療指南解讀
- 2023年工程質量監(jiān)督人員考試真題模擬匯編(共957題)
- 延長保修服務合同
- 2025中考英語作文19個熱點話題及范文
- 2023三年級英語下冊 Unit 1 How are you第3課時說課稿 湘少版
- 基于人工智能的農產品追溯系統(tǒng)解決方案
評論
0/150
提交評論