供電公司電網(wǎng)事故應急預案二0O七年十月目錄第1章總則··················································11.1目的和依據(jù)············································11.2適用范圍··············································11.3處置原則··············································1第2章組織結(jié)構(gòu)與職責········································32.1應急領(lǐng)導小組··········································32.2電網(wǎng)調(diào)度機構(gòu)··········································3第3章應急分級··············································63.1應急分級··············································63.2預警狀態(tài)··············································63.3應急狀態(tài)··············································8第4章應急響應··············································94.1應急啟動程序··········································94.2應急處理·············································104.3預警控制·············································114.4事故搶險·············································114.5電網(wǎng)恢復·············································12第5章應急處置·············································135.1電網(wǎng)應急處置要求·····································135.2電網(wǎng)應急處置結(jié)束·····································145.3信息匯報制度與信息發(fā)布規(guī)定···························14第6章后期處置·············································156.1事故調(diào)查············································156.2改進措施············································15第7章應急保障·············································167.1電網(wǎng)應急保障體系·····································167.2安全和技術(shù)保障·······································167.3資金保障和物資準備···································177.4人員保障·············································18第8章附錄·················································18附件1:電網(wǎng)調(diào)度運行突發(fā)事件應急處理啟動程序圖·········19附件2:電網(wǎng)調(diào)度運行突發(fā)事件應急處理工作流程程序圖·····20附件3:110kv線路故障掉閘及110kv變電站停電處理預案········21附件4:電網(wǎng)三大電源點黑故障分析及事故處理預案·········32附件5:35kV變電站停電事故預案·····························36附件6:35kV變電站、線路及10kv線路調(diào)電預案···············52第1章總則1.1目的和依據(jù)1.1.1目的為不斷提高電網(wǎng)預防和控制突發(fā)事件的能力,在可以預見的范圍內(nèi),制度化、規(guī)范化地迅速響應和組織、正確處理電力系統(tǒng)在調(diào)度運行中出現(xiàn)的突發(fā)事件,最大限度地減少電力系統(tǒng)突發(fā)事件對電網(wǎng)安全穩(wěn)定運行的影響,維護電力生產(chǎn)的正常秩序。1.1.2依據(jù)依據(jù)國務(wù)院頒發(fā)的《電網(wǎng)調(diào)度管理條例》、《國家電網(wǎng)公司大面積停電應急預案(試行)》、《省應對大面積停電應急預案》、《電力系統(tǒng)調(diào)度運行突發(fā)事件應急處理工作規(guī)范》、《電網(wǎng)調(diào)度規(guī)程》、《電網(wǎng)調(diào)度規(guī)程》、《電網(wǎng)調(diào)度規(guī)程》、以及電力行業(yè)的有關(guān)規(guī)程、標準。1.2適用范圍1.2.1本工作規(guī)范適用于電網(wǎng)應對和處理因電力生產(chǎn)嚴重故障、電力設(shè)施(包括電網(wǎng)調(diào)度運行必須的工作場所、通信、自動化、信息網(wǎng)絡(luò)、調(diào)度指揮場所等)遭受嚴重破壞、重大自然災害、電力供應持續(xù)危機等對電力系統(tǒng)調(diào)度運行進而對區(qū)社會穩(wěn)定和安全構(gòu)成或可能構(gòu)成重大影響和嚴重威脅的各類突發(fā)事件。1.2.2本工作規(guī)范適用于電網(wǎng)調(diào)度管轄范圍內(nèi)的發(fā)電廠(包括自備電廠)、變電站及用戶的輸變電設(shè)備的調(diào)度運行突發(fā)事件應急處理工作。1.3處置原則1.3.1電網(wǎng)堅持“安全第一、預防為主”的原則,加強電網(wǎng)運行安全管理,堅持常備不懈的做好電網(wǎng)危險點分析,提前做好對電網(wǎng)突發(fā)事件的預防和控制措施。定期進行安全檢查,及時發(fā)現(xiàn)和處理設(shè)備缺陷,有效防止電網(wǎng)重特大生產(chǎn)事故發(fā)生;避免發(fā)生電力供應持續(xù)危機;組織開展有針對性的電網(wǎng)反事故演習,提高電網(wǎng)對重特大突發(fā)事件應急處理及快速恢復對區(qū)工農(nóng)業(yè)生產(chǎn)及人民生活供電的能力。1.3.2統(tǒng)一指揮分層管理的原則電網(wǎng)對重特大突發(fā)事件應急處理按照“統(tǒng)一指揮、快速反應、組織落實、措施得力”的原則,在區(qū)人民政府應對大面積停電應急領(lǐng)導小組以及電力系統(tǒng)突發(fā)事件應急處理領(lǐng)導小組的統(tǒng)一指揮和協(xié)調(diào)下,電網(wǎng)調(diào)度應急處理工作組、組織指揮、協(xié)調(diào)電網(wǎng)突發(fā)事件的處理和電網(wǎng)運行的恢復工作。1.3.3電網(wǎng)調(diào)度應急處理工作組按照“分層分區(qū)、相互協(xié)調(diào)、各負其責”的原則,在電網(wǎng)調(diào)度管轄范圍內(nèi)建立各相關(guān)用戶變電站、地方小發(fā)電突發(fā)事件應急處理體系,各有關(guān)單位要制定防止和處置突發(fā)事件,維護電力生產(chǎn)正常運行的應急預案。各有關(guān)單位應根據(jù)電網(wǎng)調(diào)度管轄范圍,制定本電網(wǎng)的“黑啟動”預案,電網(wǎng)調(diào)度機構(gòu)督促檢查地方小發(fā)電完善?!皬S用電”措施,地方小發(fā)電應確保機組的啟動能力和電廠自身的安全,保證電網(wǎng)在突發(fā)事件發(fā)生后盡快恢復供電。各有關(guān)單位負責向電網(wǎng)調(diào)度機構(gòu)工作場所(調(diào)度室、自動化機房、通信機房)供電保障的單位及部門應制定“電網(wǎng)調(diào)度機構(gòu)工作場所供電電源保障及搶修預案”。1.3.4電網(wǎng)調(diào)度應急處理工作組在突發(fā)事件應急處理過程中,遵循“保人身、保電網(wǎng)、保設(shè)備”的原則,將保證電網(wǎng)安全放在第一位,在突發(fā)事件中采取一切必要手段,限制突發(fā)事件范圍擴大,防止發(fā)生電網(wǎng)系統(tǒng)崩潰和瓦解。在電網(wǎng)恢復中,優(yōu)先恢復熱電廠的廠用電源及重要輸變電設(shè)備的供電,努力提高電網(wǎng)的恢復速度和效率。在電網(wǎng)供電恢復過程中,優(yōu)先恢復區(qū)政府機關(guān)及重要用戶的供電,盡快恢復區(qū)社會工農(nóng)業(yè)生產(chǎn)正常供電秩序。1.3.5電網(wǎng)調(diào)度工作組應定期開展電網(wǎng)事故預案及電網(wǎng)危險點分析,加強電網(wǎng)建設(shè)和改造,合理配置電源布點,構(gòu)建靈活可靠的電網(wǎng)結(jié)構(gòu),研究采用新技術(shù)、新裝備提高電網(wǎng)安全控制水平,開展電網(wǎng)大面積停電恢復控制研究,統(tǒng)籌考慮電網(wǎng)恢復方案,制定科學有效的“電網(wǎng)黑啟動”預案。提高電網(wǎng)安全運行水平。第2章組織機構(gòu)與職責2.1應急領(lǐng)導小組電網(wǎng)調(diào)度應急領(lǐng)導小組組長:調(diào)度所主任副組長:調(diào)度所副主任成員:調(diào)度所安全專工、自動化班長、通訊班長、調(diào)度班班長、運行方式專工、綜合專工、繼電保護專工。2.2電網(wǎng)調(diào)度機構(gòu)2.2.1機構(gòu)設(shè)置:電網(wǎng)調(diào)度機構(gòu)是電網(wǎng)事故處理的指揮中心,調(diào)度所現(xiàn)有電網(wǎng)調(diào)度、運行方式、調(diào)度自動化、總機、通訊等專業(yè)。調(diào)度所主任、書記、副主任各1名。專工組成為:繼電保護專工、安全專工、運行方式,綜合專工各1名。班組為調(diào)度班、自動化班、通訊班三個班組。2.2.1.1調(diào)度所主任:電網(wǎng)事故發(fā)生時,負責現(xiàn)場指揮;事故后及時組織有關(guān)人員分析事故,并及時提出處理意見及改進措施.2.2.1.2調(diào)度所副主任:協(xié)助主任組織制定反事故和安全技術(shù)措施,按照上級部署組織開展季節(jié)性的安全檢查活動,并組織事故處理和事故調(diào)查,總結(jié)經(jīng)驗教訓,保證安全生產(chǎn)。2.2.1.3安全專工:本車間發(fā)生的一切事故、障礙、異常負責調(diào)查,并寫出事故報告。同時開好事故分析會,按照“四不放過”的原則制定事故防范措施。2.2.1.4繼電保護專工:電網(wǎng)發(fā)生事故后進行保護事故分析,撰寫事故分析報告,對新上設(shè)備進行定值核算,對電網(wǎng)繼電保護運行中存在的問題,提出改進意見。2.2.1.5綜合專工及通信班:指揮通信事故搶修工作,保證公司通信系統(tǒng)安全穩(wěn)定運行。負責調(diào)度通信各專業(yè)運行、檢修、故障處理工作,主管通信交換機、調(diào)度錄音及附屬設(shè)備的運行、檢修和維護,負責光纜通信、載波通信網(wǎng)絡(luò)的運行、檢修和維護,負責電力通信線路、光纜線路的基建施工、大修、技改、維護工作,從事電力通信線路、光纜線路的運行管理。2.2.1.6自動化班:指導班組的遠動自動化系統(tǒng)的事故處理,協(xié)助和會同公司有關(guān)部門分析事故原因,負責主站系統(tǒng)運行、維護,遠動缺陷消除,配網(wǎng)系統(tǒng)運行、維護,遠動缺陷消除.2.2.1.7調(diào)度班:負責指揮電網(wǎng)運行、操作及事故處理.2.2.1.8運行方式專工:主管電網(wǎng)調(diào)度運行的管理工作,組織審查電網(wǎng)事故預案、反事故措施、應急預案、黑啟動方案。負責指揮電網(wǎng)的事故處理,協(xié)助和會同公司有關(guān)部門分析事故原因、制定反事故措施并監(jiān)督實施。2.2.2電網(wǎng)調(diào)度機構(gòu)在重要變電站、發(fā)電廠全停應急處理中的主要職責:(1)掌握電網(wǎng)運行狀態(tài),根據(jù)故障現(xiàn)象判斷事故發(fā)生性質(zhì)及其影響范圍;(2)正確下達調(diào)度命令,指揮電網(wǎng)事故處理,控制事故范圍,有效防止事故進一步擴大;(3)采取一切必要手段,保證主網(wǎng)安全和重點地區(qū)、重要城市的電力供應;(4)協(xié)調(diào)電網(wǎng)、電廠、用戶之間的恢復,提出合理可行的恢復方案和恢復步驟;(5)指揮電網(wǎng)操作,恢復電網(wǎng)供電和電網(wǎng)接線方式,使其盡快恢復正常;(6)及時將重要變電站、發(fā)電廠全停有關(guān)情況向本企業(yè)應急領(lǐng)導小組匯報。第3章應急分級3.1應急分級突發(fā)事件是指電網(wǎng)在運行過程中,突受外界自然災害或電網(wǎng)內(nèi)部設(shè)備及其它因素影響,造成或發(fā)生電網(wǎng)大面積停電或電網(wǎng)穩(wěn)定破壞、輸變電設(shè)施大范圍受損等事故對電網(wǎng)運行產(chǎn)生嚴重影響的事件。突發(fā)事件分級按照突發(fā)事件的嚴重程度和對社會的影響,將突發(fā)事件分為預警和應急兩個等級(電網(wǎng)突發(fā)事件分類暫分為預警和應急兩個等級)。3.2預警狀態(tài)當電網(wǎng)發(fā)生下列情況之一時,電網(wǎng)進入電網(wǎng)安全預警狀態(tài):3.2.1在電網(wǎng)運行中110千伏重要輸電線路、110千伏重要變電站發(fā)生重特大事故,造成電網(wǎng)大面積停電或限電拉路造成網(wǎng)供減負荷達到事故前總負荷的15%及以上;3.2.2.在電網(wǎng)運行中因電網(wǎng)供電設(shè)備發(fā)生重特大事故,造成區(qū)重要政治、經(jīng)濟用戶減供負荷達到事故前總負荷的30%及以上時;3.2.3.因外界嚴重自然災害引起電力設(shè)施大范圍破壞,造成區(qū)電網(wǎng)減供負荷達到事故前的20%及以上時;3.2.4.網(wǎng)內(nèi)重要輸變電設(shè)備損壞,長時間(10天及以上)不能恢復,運行設(shè)備不能滿足負荷供應,造成對外大面積限電影響電網(wǎng)安全運行及負荷供應時;3.2.5.網(wǎng)內(nèi)重要發(fā)電廠、重要變電站、重要輸變電設(shè)備遭受破壞或打擊,對區(qū)域電網(wǎng)安全穩(wěn)定運行構(gòu)成威脅時;3.2.6在電網(wǎng)運行中電網(wǎng)與電網(wǎng)非正常解列,造成電網(wǎng)孤立網(wǎng)運行時;3.2.7電網(wǎng)調(diào)度自動化系統(tǒng)及通信二次系統(tǒng)(包括廠站端)受到病毒、黑客攻擊、人為破壞等,影響系統(tǒng)的正常工作時;3.2.8調(diào)度通信電源故障等或其他人為破壞等致使通信通道中斷時間較長,影響繼電保護、自動化數(shù)據(jù)使用時;3.2.9.調(diào)度機構(gòu)工作場所(調(diào)度室、自動化機房、通信機房)失去外部供電電源時間較長或因其他原因,影響調(diào)度機構(gòu)正常工作時;3.2.10.因外界嚴重自然災害造成調(diào)度運行等相關(guān)人員因故不能正常值班時;3.2.11根據(jù)地方政府及上級領(lǐng)導的要求,對于社會突發(fā)性事件需要供電公司啟動電網(wǎng)應急處理預案時;3.2.12.因突發(fā)特大自然災害,社會穩(wěn)定和應急搶險要求提供電力供應保障時;3.2.13按照《應對大面積停電應急預案》及上級領(lǐng)導的有關(guān)規(guī)定,達到啟動電網(wǎng)“預警狀態(tài)”的其它事件時。3.3應急狀態(tài)3.3.1在電網(wǎng)運行中因電網(wǎng)供電設(shè)備發(fā)生重特大事故,引發(fā)局部電網(wǎng)連鎖反應,造成電網(wǎng)與電網(wǎng)非正常解列及區(qū)域電網(wǎng)大面積停電,減供負荷達到事故前總負荷的30%及以上;3.3.2在電網(wǎng)運行中因電網(wǎng)供電設(shè)備發(fā)生重特大事故,造成區(qū)重要政治、經(jīng)濟用戶減供負荷達到事故前總負荷的40%及以上時3.3.3因嚴重自然災害引起電力設(shè)施大范圍破壞,造成電網(wǎng)大面積停電,減供負荷達到事故前的40%及以上,并且造成重要發(fā)電廠停電、重要輸變電設(shè)備受損,對電網(wǎng)、跨區(qū)電網(wǎng)安全穩(wěn)定運行構(gòu)成嚴重威脅;3.3.4因系統(tǒng)發(fā)電廠發(fā)電燃料供應短缺、水源不足等原因引起嚴重電力供應嚴重危機,造成電網(wǎng)拉限負荷達到正常值40%及以上,在電網(wǎng)進入“預警狀態(tài)”時,電網(wǎng)供電設(shè)備發(fā)生重特大事故,對電網(wǎng)安全運行構(gòu)成嚴重影響時;3.3.5網(wǎng)內(nèi)重要輸變電設(shè)備損壞,長時間(10天及以上)不能恢復,運行設(shè)備不能滿足負荷供應,并且對區(qū)域電網(wǎng)造成非正常解列及對外大面積限電影響電網(wǎng)安全運行時;3.3.6網(wǎng)內(nèi)重要發(fā)電廠、重要變電站、重要輸變電設(shè)備遭受毀滅性破壞或打擊,造成電網(wǎng)大面積停電,減供負荷達到事故前的40%及以上,對區(qū)黨政軍重要用戶安全供電構(gòu)成嚴重威脅時;3.3.7調(diào)度機構(gòu)工作場所(調(diào)度室、自動化機房、通信機房)失去外部電源時間較長或因其他原因造成調(diào)度機構(gòu)工作場所不能使用,致使調(diào)度機構(gòu)無法正常工作的時;3.3.8因外界嚴重自然災害造成調(diào)度運行等相關(guān)人員因故不能正常值班;影響其對電網(wǎng)實時運行的正常監(jiān)視和實施控制時;3.3.9按照《區(qū)應對大面積停電應急預案》的規(guī)定及上級領(lǐng)導的指示達到啟動電網(wǎng)“應急狀態(tài)”的其它事件時。第4章應急響應4.1應急啟動程序4.1.1當電網(wǎng)發(fā)生突發(fā)重大故障、電力設(shè)施遭受重大破壞、二次系統(tǒng)發(fā)生嚴重故障或受到攻擊、遭遇嚴重自然災害、電力供應發(fā)生持續(xù)危機時,電網(wǎng)調(diào)度機構(gòu)應立即啟動應急處理機制。值班調(diào)度員應將故障狀態(tài)、停電范圍、影響負荷、發(fā)展趨勢等有關(guān)情況盡快報告電網(wǎng)應急處理工作組。4.1.2應急領(lǐng)導小組在接到有關(guān)事故報告之后,根據(jù)事故影響范圍、停電區(qū)域、嚴重程度、可能后果和應急處理的需要等,判斷是否進入預警狀態(tài)或緊急狀態(tài),并將有關(guān)情況報告本企業(yè)應急領(lǐng)導小組,通知相關(guān)部門。4.1.3應急領(lǐng)導小組在接到因重要變電站、發(fā)電廠全停而造成大面積停電報告之后,根據(jù)嚴重程度,召集緊急會議,研究決定是否進入預警狀態(tài)或應急狀態(tài),并就有關(guān)重大應急問題做出決策和部署,啟動相應應急預案。各單位、各部門按職責分工,立即組織開展應急處理工作。4.1.4應急領(lǐng)導小組在研究決定進入預警狀態(tài)或應急狀態(tài)之后,應立即將有關(guān)情況報告地方政府及上一級應急指揮機構(gòu),并就應急救援與處理工作接受領(lǐng)導,視情況請求給予必要的支持和援助。4.2應急處理4.2.1當電網(wǎng)對外重要聯(lián)絡(luò)線非正常解列或孤立運行時,電網(wǎng)調(diào)度機構(gòu)運行方式、繼電保護等專業(yè)人員應了解事故情況并對系統(tǒng)恢復提出指導意見,必要時到達調(diào)度室或工作崗位,為故障處理提供技術(shù)支持。4.2.2當電網(wǎng)調(diào)度機構(gòu)通信系統(tǒng)、調(diào)度自動化系統(tǒng)發(fā)生異常,影響實時調(diào)度運行時,通信、調(diào)度自動化專業(yè)有關(guān)人員應到達設(shè)備機房或工作崗位,進行故障處理或指揮協(xié)調(diào)廠站端設(shè)備的異常處理。4.2.3當電網(wǎng)發(fā)生電力生產(chǎn)故障減供負荷數(shù)額達到預警狀態(tài)時,調(diào)度機構(gòu)分管領(lǐng)導和運行方式、繼電保護等有關(guān)人員應到達調(diào)度室或工作崗位,為電網(wǎng)事故處理提供技術(shù)支持。4.2.4當電網(wǎng)發(fā)生電力生產(chǎn)嚴重故障,減供負荷數(shù)額達到應急狀態(tài)或造成大面積停電或電網(wǎng)瓦解時,調(diào)度機構(gòu)主要負責人及有關(guān)人員應到達調(diào)度室,組織指揮應急處理工作。4.3預警控制審查已有的應急預案是否符合應急要求;必要時修改已有應急預案或編制對應的突發(fā)事件應急預案。4.3.3電網(wǎng)管轄范圍內(nèi)各發(fā)、供電單位在重要發(fā)、供電設(shè)備發(fā)生缺陷并可能因缺陷發(fā)展退出運行時,應及時向管轄該設(shè)備的調(diào)度機構(gòu)匯報。管轄該設(shè)備的調(diào)度機構(gòu)應及時做好事故預想,影響電網(wǎng)安全運行時應向上級調(diào)度機構(gòu)匯報。4.3.4當電網(wǎng)發(fā)生電力供應持續(xù)嚴重危機、電網(wǎng)調(diào)度機構(gòu)采取措施并缺乏有效的控制手段,有可能導致電網(wǎng)大面積停電時,應提請供電公司應急處理指揮部研究決定實施特殊時期限電方案。4.3.5在電網(wǎng)緊急情況下,為保證主網(wǎng)安全穩(wěn)定和重點地區(qū)、重要用戶的安全供電,電網(wǎng)值班調(diào)度員有權(quán)采取拉路限負荷、解列電網(wǎng)、解列發(fā)電機組等一切必要手段,控制事態(tài)進一步發(fā)展和擴大。電網(wǎng)內(nèi)各級運行值班人員必須嚴格服從電網(wǎng)調(diào)度命令,正確執(zhí)行調(diào)度操作指令。任何單位和個人不得干擾、阻礙調(diào)度及運行值班人員進行事故處理。4.4事故搶險4.4.1電網(wǎng)發(fā)生重大電力生產(chǎn)故障、嚴重自然災害、電力設(shè)施大范圍破壞時,調(diào)度機構(gòu)應通知供電公司有關(guān)單位。有關(guān)單位應迅速組織事故搶險隊伍,盡快趕赴事故現(xiàn)場,排除險情,修復故障設(shè)備。4.4.2負責電力事故搶險搶修的有關(guān)單位應向調(diào)度機構(gòu)報告設(shè)備損壞、預計恢復時間、對調(diào)度的要求等,以便調(diào)度機構(gòu)對運行方式等做出必要的安排和調(diào)整。4.4.3在電網(wǎng)調(diào)度機構(gòu)場所失去電源的情況下,除啟動相應預案外,調(diào)度機構(gòu)應迅速通知調(diào)度機構(gòu)電源管理單位組織搶修。4.4.4當電網(wǎng)調(diào)度主干通信網(wǎng)絡(luò)或調(diào)度自動化系統(tǒng)癱瘓時,調(diào)度機構(gòu)應迅速組織專業(yè)人員搶修,通知有關(guān)單位及廠站端設(shè)備管理單位組織人員搶修。當廠站端二次設(shè)備發(fā)生嚴重故障,影響電網(wǎng)調(diào)度運行時,調(diào)度機構(gòu)相關(guān)專業(yè)應迅速組織事故搶修隊伍,盡快趕赴事故現(xiàn)場,修復故障設(shè)備。4.4.5在電力事故搶險過程中,企業(yè)視情況請求地方政府部門及相關(guān)單位提供交通、通訊、醫(yī)療、物資、人員等方面的保障和支持,必要時請求軍隊給予支持。4.5電網(wǎng)恢復4.5.1在電網(wǎng)發(fā)生大面積停電后,要快速、有效的恢復電網(wǎng)運行,盡量減少停電損失恢復電網(wǎng)供電,保持社會穩(wěn)定、恢復正常生產(chǎn)生活秩序至關(guān)重要。4.5.2在電網(wǎng)恢復過程中,要優(yōu)先恢復電廠和仍能保持熱態(tài)啟動能力機組的廠用電源。具備自啟動能力小發(fā)電,應根據(jù)情況自行啟動發(fā)電機組。4.5.3在電網(wǎng)恢復過程中,要協(xié)調(diào)好電網(wǎng)、電廠、用戶之間的恢復次序,保證電網(wǎng)安全穩(wěn)定留有一定裕度。在電網(wǎng)恢復過程中,要防止發(fā)生過電壓,避免造成新的設(shè)備損壞和停電。4.5.4在對停電發(fā)電廠和變電站恢復送電之后,要盡快有步驟地恢復對重要負荷的電力供應。電網(wǎng)分區(qū)恢復的,在條件具備時應盡快實現(xiàn)聯(lián)網(wǎng)運行。4.5.5在電網(wǎng)恢復過程中,各有關(guān)發(fā)電廠應嚴格按照電網(wǎng)調(diào)度命令恢復機組并網(wǎng)運行,調(diào)整發(fā)電出力。電力用戶應嚴格按照調(diào)度指令按時分步恢復用電。第5章應急處置5.1電網(wǎng)應急處置要求5.1.1電網(wǎng)各變電站和發(fā)電單位應制定相應的突發(fā)事件應急預案。當電力系統(tǒng)發(fā)生突發(fā)事件時,按照事先制訂的預案采取應急措施。應急處理期間,各變電站和發(fā)電單位要堅決執(zhí)行調(diào)度機構(gòu)下達的指令,準確及時地反饋現(xiàn)場實際情況,將主要精力投入對突發(fā)事件的緊急處置,確實履行保電網(wǎng)、保電廠設(shè)備安全的職責。5.1.2供電公司應急處理指揮部宣布電網(wǎng)啟動應急機制后,電網(wǎng)調(diào)度運行突發(fā)事件應急處理工作組可視需要,通過公司應急工作領(lǐng)導小組請求區(qū)政府應急領(lǐng)導小組啟動社會援助保障體系。當電網(wǎng)需要大面積限電時,區(qū)調(diào)應及時報請上級部門啟動緊急限電措施,確保電網(wǎng)安全運行。5.2電網(wǎng)應急處置結(jié)束電網(wǎng)滿足下列條件時,由電網(wǎng)調(diào)度應急工作組提請公司應急處理指揮部研究決定,宣布解除電網(wǎng)安全預警狀態(tài):5.2.1電網(wǎng)接線恢復正常方式,電網(wǎng)運行參數(shù)保持在穩(wěn)定限額之內(nèi);5.2.2電網(wǎng)事故停電負荷及事故拉限負荷全部恢復供電;5.2.3對電網(wǎng)安全穩(wěn)定運行和正常電力供應存在重大影響或嚴重威脅的事件及因素消除。5.2.4電網(wǎng)滿足下列條件時,由電網(wǎng)調(diào)度應急工作組提請公司應急處理指揮部研究決定,宣布解除電網(wǎng)安全緊急狀態(tài):5.2.5電網(wǎng)主網(wǎng)架基本恢復正常接線方式,電網(wǎng)運行參數(shù)保持在穩(wěn)定限額之內(nèi),主要發(fā)電廠機組運行穩(wěn)定;5.2.6停電負荷恢復90%及以上,重要用戶供電負荷恢復95%及以上;5.2.7對電網(wǎng)安全穩(wěn)定存在重大影響或嚴重威脅的各類事件及因素消除。5.3信息匯報制度與信息發(fā)布規(guī)定5.3.1建全電網(wǎng)調(diào)度運行突發(fā)事件匯報制度,當電網(wǎng)發(fā)生突發(fā)事件時電網(wǎng)調(diào)度系統(tǒng)應建全嚴格的電網(wǎng)調(diào)度運行突發(fā)事件匯報制度和暢通的突發(fā)事件信息網(wǎng)絡(luò)。5.3.2電網(wǎng)管轄范圍內(nèi)發(fā)生突發(fā)事件時信息匯報內(nèi)容要求準確、詳實,電網(wǎng)調(diào)度系統(tǒng)各級調(diào)度、運行值班人員均須根據(jù)相關(guān)電網(wǎng)調(diào)度機構(gòu)的調(diào)度管轄/許可范圍,立即向上級電網(wǎng)調(diào)度機構(gòu)的值班調(diào)度員匯報在其調(diào)度管轄/許可范圍內(nèi)發(fā)生的突發(fā)事件任何單位和個人均不得瞞報緩報并及時向本單位部門領(lǐng)導匯報。各有關(guān)單位領(lǐng)導按本規(guī)定原則向其上級領(lǐng)導匯報。5.3.3電網(wǎng)管轄范圍內(nèi)電力生產(chǎn)發(fā)生突發(fā)事件時,突發(fā)事件信息發(fā)布由供電公司有關(guān)部門統(tǒng)一對外發(fā)布信息,必要時經(jīng)供電公司授權(quán),電網(wǎng)調(diào)度運行突發(fā)事件應急處理工作組可以向媒體或公眾發(fā)布信息。第6章后期處置6.1事故調(diào)查因重要變電站、發(fā)電廠全停而造成大面積停電之后,除按照國家政府部門要求配合進行事故調(diào)查外,供電公司組成事故調(diào)查組進行事故調(diào)查。事故調(diào)查應堅持實事求是、尊重科學的原則,客觀、公正、準確、及時地查清事故原因、發(fā)生過程、恢復情況、事故損失、事故責任等,提出防范措施和事故責任處理意見。6.2改進措施6.2.1大面積停電之后,企業(yè)應及時組織生產(chǎn)、運行、科研等部門聯(lián)合攻關(guān),研究事故發(fā)生機理,分析事故發(fā)展過程,吸取事故教訓,提出具體措施,進一步完善和改進大面積停電應急預案。6.2.2企業(yè)應及時總結(jié)因重要變電站、發(fā)電廠全停而造成大面積停電應急工作的經(jīng)驗和教訓,進一步完善和改進大面積停電應急救援、事故搶險與緊急處置體系。第7章應急保障7.1電網(wǎng)應急保障體系7.1.1電網(wǎng)調(diào)度系統(tǒng)應急準備工作要求各單位遵循“統(tǒng)一領(lǐng)導、分工協(xié)作、快速反映、措施果斷”的原則,結(jié)合電網(wǎng)情況,針對電網(wǎng)突發(fā)事件的不同類別,組織、落實常備應急搶修隊伍和物資儲備,建立供電公司安全生產(chǎn)保障體系及突發(fā)事件應急保障體系。該保障體系包括電網(wǎng)調(diào)度運行、事故搶修、技術(shù)方案、交通運輸、后勤保障支持等方面。7.1.2電網(wǎng)調(diào)度應急保障體系各單位應按“安全第一、預防為主”的原則,對突發(fā)事件的應急準備按照本工作規(guī)范有關(guān)規(guī)定,按突發(fā)事件的分級和類別,制定科學的、可操作的應急處理預案,該預案要求覆蓋突發(fā)事件發(fā)生的全過程,并結(jié)合突發(fā)事件的類別和規(guī)律,制定有效的控制措施。7.1.3電網(wǎng)各級調(diào)度機構(gòu)應根據(jù)電網(wǎng)實際運行方式,綜合考慮氣候、工作內(nèi)容、季節(jié)性事故特點等各種因素影響,適時做出相應事故預想,做好啟動相應預案的準備。7.2安全和技術(shù)保障7.2.1電網(wǎng)企業(yè)和發(fā)電企業(yè)應結(jié)合電力生產(chǎn)特點和事故規(guī)律,建立覆蓋電力生產(chǎn)事故發(fā)生、發(fā)展、處理、恢復全過程的事故應急預案,制定并落實防止大面積停電的預防性措施、緊急控制措施和電網(wǎng)恢復措施,完善常態(tài)機制,建立預警機制,健全應急機制。7.2.2電網(wǎng)調(diào)度機構(gòu)組織每年有針對性的進行一次聯(lián)合反事故演習,制定防止大電網(wǎng)停電事故的處理預案,并由相關(guān)單位予以落實。并網(wǎng)發(fā)電廠應按照要求積極參加聯(lián)合反事故演習,制定保廠用電措施,落實電網(wǎng)事故處理預案的有關(guān)要求。7.2.3各類電力用戶應根據(jù)突然停電可能帶來的影響、損失或危害,制定外部電源突然中斷情況下的應急保安措施和救援預案。對礦井、醫(yī)院、地鐵、金融、通訊中心、新聞媒體、高層建筑等特別重要用戶,必須自備保安電源。7.2.4區(qū)調(diào)定期聘請由上級領(lǐng)導、電力生產(chǎn)運行、技術(shù)管理、安全管理、等各方面專家組成的應急處理專家組,調(diào)研和檢查電力系統(tǒng)調(diào)度運行突發(fā)事件應急預案的制定和落實情況,發(fā)現(xiàn)問題及時組織整改。7.2.5學習和借鑒國內(nèi)外先進現(xiàn)代化科學技術(shù),加快建設(shè)電網(wǎng)在線事故預警、電網(wǎng)事故信息處理及電網(wǎng)突發(fā)事件應急防治系統(tǒng)。7.3資金保障和物資準備7.3.1電網(wǎng)內(nèi)各有關(guān)單位每年應安排專項資金,用于處置突發(fā)事件的應急設(shè)施、設(shè)備、物資及人員培訓等專項費用。該項資金應??顚S茫唇?jīng)各級應急指揮機構(gòu)的批準,任何部門不得擅自挪為它用。7.3.2各有關(guān)單位應對突發(fā)事件的應急設(shè)施、設(shè)備、器械等物資儲備應定置存放、定期檢查、及時補充,保證在緊急情況下各保障體系的快速反應及物流暢通。7.4人員保障7.4.1應加強電網(wǎng)調(diào)度、運行值班、檢修維護、生產(chǎn)管理、事故搶修的隊伍建設(shè)和人員技能培訓,通過模擬演練等手段提高各類人員的應急處理能力。7.4.2全社會應加強電力生產(chǎn)、電網(wǎng)運行和電力安全知識的科普宣傳和教育,采用各種通俗易懂方式普及停電后的正確處理方法和應對辦法,提高公眾應對停電的能力。第8章附錄附件1:電網(wǎng)調(diào)度運行突發(fā)事件應急處理啟動程序圖附件2:電網(wǎng)調(diào)度運行突發(fā)事件應急處理工作流程程序圖附件3:110kv線路故障掉閘及110kv變電站停電處理預案附件4:電網(wǎng)三大電源點黑故障分析及事故處理預案·附件5:35kV變電站事故處理預案·附件6:35kV變電站、線路及10kv線路調(diào)電預案附件1:電網(wǎng)調(diào)度運行突發(fā)事件應急處理啟動程序圖通知有關(guān)部門是是根據(jù)電網(wǎng)調(diào)度規(guī)程及事故報告制度,匯報有關(guān)領(lǐng)導、上級調(diào)度機構(gòu)突發(fā)事件應急處理結(jié)果后總結(jié)評價啟動相應應急預案應急處理工作組決定是否進入預警或應急狀態(tài)匯報公司應急處理指揮部判斷是否進入預警或應急狀態(tài)報告應急處理工作組根據(jù)電網(wǎng)調(diào)度規(guī)程及事故報告制度,匯報有關(guān)領(lǐng)導、上級調(diào)度機構(gòu)啟動電網(wǎng)事故處理預案判斷是否為突發(fā)事件或電網(wǎng)重大事故電網(wǎng)區(qū)調(diào)調(diào)度機構(gòu)有關(guān)單位應急處理指揮機構(gòu)發(fā)電廠、變電站、有關(guān)調(diào)度機構(gòu)值班員電網(wǎng)調(diào)度運行突發(fā)事件發(fā)生(電網(wǎng)重大故障、電力設(shè)施遭受破壞、嚴重自然災害…………)是通知有關(guān)部門是是根據(jù)電網(wǎng)調(diào)度規(guī)程及事故報告制度,匯報有關(guān)領(lǐng)導、上級調(diào)度機構(gòu)突發(fā)事件應急處理結(jié)果后總結(jié)評價啟動相應應急預案應急處理工作組決定是否進入預警或應急狀態(tài)匯報公司應急處理指揮部判斷是否進入預警或應急狀態(tài)報告應急處理工作組根據(jù)電網(wǎng)調(diào)度規(guī)程及事故報告制度,匯報有關(guān)領(lǐng)導、上級調(diào)度機構(gòu)啟動電網(wǎng)事故處理預案判斷是否為突發(fā)事件或電網(wǎng)重大事故電網(wǎng)區(qū)調(diào)調(diào)度機構(gòu)有關(guān)單位應急處理指揮機構(gòu)發(fā)電廠、變電站、有關(guān)調(diào)度機構(gòu)值班員電網(wǎng)調(diào)度運行突發(fā)事件發(fā)生(電網(wǎng)重大故障、電力設(shè)施遭受破壞、嚴重自然災害…………)是根據(jù)突發(fā)事件匯報制度,向區(qū)市政府和根據(jù)突發(fā)事件匯報制度,向區(qū)市政府和供電公司應急處理指揮機構(gòu)報告附件2:電網(wǎng)調(diào)度運行突發(fā)事件應急處理工作流程程序圖制訂反措,修訂預案必要時請求政府或上級領(lǐng)導支援事故搶險啟動應急預案評價應急處理應急處理總結(jié)進入應急狀態(tài)可能出現(xiàn)嚴重限電時報請政府或上級領(lǐng)導采取措施評估故障影響,審視修訂已有預案,制訂新預案各單位落實預警措施,啟動預警預案進入預警狀態(tài)新聞發(fā)布解除應急機制,終止執(zhí)行預案向上級報告啟動應急處理機制電網(wǎng)事故處理應急處理指揮部應急處理工作組電網(wǎng)調(diào)度機構(gòu)(受理報告,反饋事故處理進度,向工作小組匯報)電網(wǎng)調(diào)度運行突發(fā)事件發(fā)生制訂反措,修訂預案必要時請求政府或上級領(lǐng)導支援事故搶險啟動應急預案評價應急處理應急處理總結(jié)進入應急狀態(tài)可能出現(xiàn)嚴重限電時報請政府或上級領(lǐng)導采取措施評估故障影響,審視修訂已有預案,制訂新預案各單位落實預警措施,啟動預警預案進入預警狀態(tài)新聞發(fā)布解除應急機制,終止執(zhí)行預案向上級報告啟動應急處理機制電網(wǎng)事故處理應急處理指揮部應急處理工作組電網(wǎng)調(diào)度機構(gòu)(受理報告,反饋事故處理進度,向工作小組匯報)電網(wǎng)調(diào)度運行突發(fā)事件發(fā)生附件3:110kv線路故障掉閘、110KV變電站停電處理預案一、許寺變電站全站停電事故處理預案處理步驟:許寺變?nèi)就k姇r,請示地調(diào),要求將崮山變、變及馬山變負荷調(diào)肥馬線供電。(屬于地調(diào)管轄設(shè)備、具體操作由地調(diào)負責)二、110KV長馬線故障掉閘事故預案(一)110KV長馬線故障掉閘,馬山變備投動作肥馬線帶全站負荷運行方式:長馬線供110KVI、II母線及#1主變供6KV全部負荷,#II主變供35KV全部負荷。肥馬線備用。110KV備自投。事故象征:長馬線線路故障掉閘,110KV備投動作肥馬線帶全站負荷。事故處理:馬山變停用110KV備投。(二)110KV長馬線故障掉閘,馬山變備投不動作全站停電運行方式:長馬線供110KVI、II母線及#1主變供6KV全部負荷,#II主變供35KV全部負荷。肥馬線備用。110KV備自投。事故象征:長馬線線路故障掉閘,110KV備投不動作馬山變?nèi)就k?。事故處理?、請示地調(diào)要求拉開馬山變長馬線3811開關(guān),合上肥馬線3815開關(guān)。停用110KV備投。2、通知有關(guān)單位速去檢查處理3、匯報有關(guān)領(lǐng)導,做好相關(guān)記錄(三)110KV長馬線故障掉閘,肥馬線停電檢修馬山變?nèi)就k姷氖鹿暑A案運行方式:長馬線供110KVI、II母線及#1主變供6KV全部負荷,#II主變供35KV全部負荷。肥馬線停電檢修。事故象征:110KV長馬線故障掉閘,馬山變?nèi)就k?、通知修驗廠速到馬山變處理。2、匯報有關(guān)領(lǐng)導,做好記錄。(四)110KV長馬線故障掉閘,變方式變化運行方式:許長線供110KVI、II母線及#I、#II主變供10KV、35KV負荷,110KV線路備投。35KV及10KV分段備投。事故象征:110KV長馬線故障掉閘事故處理:變停用110KV線路備投(五)110KV長馬線故障掉閘,崮山變由許崮線單電源供電。三、110KV肥馬線故障掉閘事故預案(一)110KV肥馬線故障掉閘,馬山變方式變化運行方式:長馬線供110KVI、II母線及#1主變供6KV全部負荷,#II主變供35KV全部負荷。肥馬線備用。110KV備自投。事故象征:肥馬線線路故障掉閘事故處理:馬山變停用110KV備投。(二)110KV肥馬線故障掉閘,長馬線停電檢修馬山變?nèi)就k姷氖鹿暑A案運行方式:肥馬線供110KVI、II母線及#1主變供6KV全部負荷,#II主變供35KV全部負荷。長馬線停電檢修。事故象征:110KV肥馬線故障掉閘,馬山變?nèi)就k?、匯報地調(diào)速到馬山變處理。2、匯報有關(guān)領(lǐng)導,做好記錄。四、110KV許長線故障掉閘事故預案(一)110KV許長線故障掉閘,變備投動作長馬線帶全站負荷運行方式:許長線供110KVI、II母線及#I、#II主變供10KV、35KV負荷,110KV線路備投長馬線。35KV及10KV分段備投。事故象征:許長線線路故障掉閘,110KV備投動作長馬線帶全站負荷。事故處理:變停用110KV線路備投。(二)110KV許長線故障掉閘,變備投不動作全站停電運行方式:許長線供110KVI、II母線及#I、#II主變供10KV、35KV負荷,110KV線路備投長馬線。35KV及10KV分段備投。事故象征:許長線線路故障掉閘,110KV備投不動作變?nèi)就k?。事故處理?、令變檢查站內(nèi)設(shè)備。2、變匯報站內(nèi)設(shè)備經(jīng)查無問題后,命令停用110KV備投,拉開許長線3412開關(guān),合上長馬線3411開關(guān)送電。3、匯報地調(diào)通知修驗場、線路工區(qū)處理4、匯報領(lǐng)導,做好記錄。(三)110KV許長線故障掉閘,長馬線停電檢修變?nèi)就k姷氖鹿暑A案運行方式:許長線供110KVI、II母線及#I、#II主變供10KV、35KV負荷,長馬線停電檢修。35KV及10KV分段備投。事故象征:許長線線路故障掉閘,變?nèi)就k?。事故處理?、拉開35KV及10KV所屬全部開關(guān)。2、35KVII母線由許清線送電。3、經(jīng)領(lǐng)導同意35kvⅡ母線負荷可由許清線送電。4、匯報地調(diào)速派人處理。5、匯報有關(guān)領(lǐng)導,做好記錄。五、110KV許崮線故障掉閘事故預案(一)地調(diào)告110KV許崮線故障掉閘,通知操作隊做好崮山變、潘農(nóng)變調(diào)電準備。(三)110KV許崮線故障掉閘,崮山變電站、潘農(nóng)變?nèi)就k姟#ㄋ模?10kV變事故停電,熱電廠解網(wǎng)時的事故處理110kV變失電,熱電廠解網(wǎng)時,系統(tǒng)若短時間不能恢復,應請示地調(diào)拉開許長線、長馬線開關(guān)、刀閘。熱電廠解網(wǎng)運行,拉開變#Ⅰ、#Ⅱ主變35kv側(cè)3422、3421開關(guān)、刀閘,10kv側(cè)042、041開關(guān)及刀閘,合上變35kv分段3430開關(guān),10kv分段050開關(guān),由35kV長熱線供變35kV母線,10kv長團線倒供變10kv母線,保證城區(qū)及鄉(xiāng)鎮(zhèn)重要用戶供電,負荷維持5500kW以下。系統(tǒng)恢復時,為防止非同期并網(wǎng),變先停電,變恢復系統(tǒng)供電后,由熱電廠恢復并網(wǎng)。七、崮山變電站事故預案崮山變電站:許崮線帶110KVⅠⅡ段母線,#Ⅰ主變,#Ⅰ主變帶35KVⅠⅡ段母及10KV各出線負荷,長馬線101開關(guān)熱備用。(一)崮山變:35KV張夏線307開關(guān)掉閘故障事故預想事故象征:35KV張夏線故障,張夏線307開關(guān)掉閘,重合不成功。處理步驟:

1、將35KV張夏線所帶負荷倒35KV萬德線供電;2、查看張夏線開關(guān)掉閘次數(shù),通知檢修公司查線;3、根據(jù)查線結(jié)果處理;

4、處理完畢后,恢復原運行方式;5、匯報領(lǐng)導并做好記錄和錄音。(二)崮山變:35KV母線故障事故預想

運行方式:110KV許崮線供110KV1、2段母線,2號變帶35kV1、2段母線及10kV1、2段母線負荷,1號變熱備用。事故象征:35KV母線接地,C相電壓到零。處理步驟:

1、通知用戶做好試拉線路準備;2、試拉萬德線信號消失;3、令操作一隊將35KV萬德線所帶萬德變及武莊變負荷倒35KV張夏線供電;4、通知檢修公司帶電巡萬德線;5、處理完畢后,恢復原運行方式;(三)35KV萬德線速斷掉閘,重合一次不成功。事故象征:崮山變35KV萬德線速斷保護動作306開關(guān)掉閘,重合不成功1、將萬德線的負荷倒張夏線供電2、查看萬德線開關(guān)掉閘次數(shù),通知檢修公司查線。3、根據(jù)查線結(jié)果及時處理。4、處理完畢后恢復原運行方式。5、匯報領(lǐng)導及做好記錄和錄音。(四)崮山變電站非正常方式下事故應急處理預案八、潘農(nóng)變電站事故處理預案((二)潘農(nóng)變電站:35KV母線故障事故預想事故象征:35KV母線接地,C相電壓到零(運行方式:長馬線供110KVI,II母線及#1主變,#1主變供全站負荷。、#Ⅱ主變備用、肥馬線備用,110KV備自投。(一)馬山變110KV母線故障事故預案運行方式:長馬線供110KVI,II母線及#1主變,#1主變供全站負荷。肥馬線備用,110KV備自投。處理步驟:通知操作隊到馬山變現(xiàn)場檢查設(shè)備,確定母線故障,110KV一條母線不能送電時,請示地調(diào)派修驗速處理,根據(jù)地調(diào)命令馬山變將故障母線隔離。1、如I母線故障,故障隔離后,用肥馬線將110KVII母線、#II主變送電2、如II母線故障,故障隔離后,許寺變將長馬線送電,馬山變送110KVI母線及#I主變(二)馬山變#II主變停電檢修,#I主變掉閘全站停電事故處理運行方式:長馬線供110KVI、II母線及#1主變供全站負荷。肥馬線備用。110KV備自投,#2變停電檢修。處理步驟:若#I主變事故掉閘。1、匯報地調(diào)通知修驗廠速到馬山變處理。2、匯報有關(guān)領(lǐng)導,做好記錄。(三)馬山變#II主變掉閘事故處理運行方式:長馬線供110KVI、II母線及#1主變供6KV全部負荷,#II主變供35KV全部負荷。肥馬線備用。110KV備自投。處理步驟:若#II主變事故掉閘。檢查35KV母線無問題后,由#I主變送電(送電后注意#I主變負荷情況)。2、請示地調(diào)派修驗廠速到馬山變處理。3、匯報有關(guān)領(lǐng)導,做好記錄。肥馬線備用,110KV備自投。附件4電網(wǎng)三大電源點“黑故障”分析及事故處理預案前言:電網(wǎng)目前具有三處電源點:一是220kV許寺變電站。110kV許長線接入110kV變電站110kVⅡ母線;110kV許崮線接入110kV崮山變電站110kVⅡ母線;110kV許崮線接入110kV潘農(nóng)變電站110kVⅠ母線;110kV長馬線接入110kV馬山變電站110kVⅠ母線;二是110kV肥馬線做為備用電源。三是熱電廠發(fā)電機組自發(fā)電,通過35kV長熱線與系統(tǒng)并網(wǎng)運行。所謂電源點“黒故障”指上述廠(站)由于某種原因造成全廠(站)停電(包括發(fā)電機組、變壓器和母線在內(nèi)的電氣元件全部退出電網(wǎng)運行)。為防止上述停電對系統(tǒng)造成電網(wǎng)全部或局部瓦解、崩潰及發(fā)生大面積停電事故,本預案對上述電源點在極端情況下的電網(wǎng)狀態(tài)及事故處理進行了分析,以期達到縮短故障停電時間、分析電網(wǎng)薄弱環(huán)節(jié)、保障電網(wǎng)安全運行的目的。1.110kV許長線系統(tǒng)(1)正常運行方式:110kV許長線帶變電站#1主變帶35kVⅠ段母線和10kVⅠ段母線及供#2主變帶35kVⅡ段母線和10kVⅡ段母線。(2)失電后設(shè)備狀態(tài):變#1主變、#2主變?nèi)齻?cè)開關(guān)熱備用,35kV長熱線3438開關(guān)熱備用。(3)電網(wǎng)大面積停電時事故征象:許長線失電,#1主變、#2主變失電,35kV長熱線301開關(guān)低周低壓解列掉閘。(4)處理思路:首先與地調(diào)取得聯(lián)系,得知系統(tǒng)短時間不能恢復供電;其次與電廠取得聯(lián)系,如果電廠系統(tǒng)瓦解,則只能等待系統(tǒng)送電;如果電廠系統(tǒng)鍋爐、汽機運行正常,能夠帶負荷,在保住廠用電的前提下,逐步向部分重要用戶供電。(5)處理過程:按地調(diào)指令執(zhí)行,并通知歸德變、孝里變、熱電廠,系統(tǒng)出現(xiàn)事故,全網(wǎng)已停電,系統(tǒng)隨時有恢復供電的可能,要求各廠站按照“黑啟動”方案的步驟和要求進行處理。同時注意監(jiān)視直流電壓和監(jiān)視來電?;謴退碗姴襟E:按地調(diào)指令執(zhí)行。2、110kV許崮線系統(tǒng)110kV崮山變:(1)正常運行方式:110kV許崮線供110kV崮山變#2主變帶35kV及10kV全部負荷;(2)失電后設(shè)備狀態(tài):崮山變#2主變?nèi)齻?cè)開關(guān)熱備用。(3)事故征象:許崮線失電,崮山變、萬德變、張夏變、五峰變、武莊變、銘峰變失電。(4)處理過程:令崮山變斷開101開關(guān)。通知張夏變、萬德變、五峰變、武莊變、銘峰變,系統(tǒng)出現(xiàn)事故,全網(wǎng)已停電,系統(tǒng)隨時有恢復供電的可能,要求各廠站按照“黑啟動”方案的步驟和要求進行處理。同時注意監(jiān)視直流電壓和監(jiān)視來電?;謴退碗姴襟E:合上崮山變101開關(guān);以上恢復送電操作大約5分鐘。110kV潘農(nóng)變:(1)正常運行方式:110kV許崮線供110kV潘農(nóng)變#1主變帶35kV及10kV全部負荷;(2)失電后設(shè)備狀態(tài):潘農(nóng)變#1主變?nèi)齻?cè)開關(guān)熱備用。(3)事故征象:許崮線失電,潘農(nóng)變失電。(4)處理過程:令潘農(nóng)變斷開101開關(guān)。要求潘農(nóng)變按照“黑啟動”方案的步驟和要求進行處理。同時注意監(jiān)視直流電壓和監(jiān)視來電?;謴退碗姴襟E:合上潘農(nóng)變101開關(guān);以上恢復送電操作大約5分鐘。3、110kV長馬線系統(tǒng)(1)正常運行方式:110kV長馬線供110kV馬山變#1主變帶35kV及10kV全部負荷;(2)失電后設(shè)備狀態(tài):馬山變#1主變?nèi)齻?cè)開關(guān)熱備用。(3)事故征象:長馬線失電,馬山變、馬鄉(xiāng)變、雙泉變失電。(4)處理過程:按地調(diào)指令執(zhí)行,并通知馬鄉(xiāng)變、雙泉變,系統(tǒng)出現(xiàn)事故,全網(wǎng)已停電,系統(tǒng)隨時有恢復供電的可能,要求各廠站按照“黑啟動”方案的步驟和要求進行處理。同時注意監(jiān)視直流電壓和監(jiān)視來電?;謴退碗姴襟E:按地調(diào)指令執(zhí)行。附件535KV變電站停電處理預案一、魯能工業(yè)園變事故預案10KVI母線故障的事故預案運行方式:35KV許園I線供35KVI母線及#I主變帶10KVI母線運行;35KV許園II線供35KVII母線帶10KVII母線運行。事故象征:#I主變10KV側(cè)002開關(guān)跳閘,10KVI母線失電。處理步驟:通知操作隊到站檢查設(shè)備。令魯能工業(yè)園變:停用10KV分段備投,將10KVI母線破壞備用。匯報地調(diào)派修驗場速處理。告營銷部通知好用戶,匯報領(lǐng)導,做好記錄。10KV魯平線線路故障,開關(guān)據(jù)動的事故預案運行方式:35KV許園I線供35KVI母線及#I主變帶10KVI母線運行;35KV許園II線供35KVII母線帶10KVII母線運行。事故象征:#I主變10KV側(cè)002開關(guān)跳閘,10KVI母線失電,10KV魯平線008開關(guān)保護動作信號發(fā)出。處理步驟:通知操作隊到站檢查設(shè)備。(1)若10KVI母線確無故障,則將10KV魯平線停電;(2)合上#I主變10KV側(cè)002開關(guān),將10KVI母線及所屬出線送電。告文昌所帶電巡線。匯報領(lǐng)導及通知好客戶服,做好記錄。10KV魯平線線路故障,保護據(jù)動的事故預案運行方式:35KV許園I線供35KVI母線及#I主變帶10KVI母線運行;35KV許園II線供35KVII母線帶10KVII母線運行。事故象征:#I主變10KV側(cè)002開關(guān)跳閘,10KVI母線失電。處理步驟:通知一隊到站檢查設(shè)備。經(jīng)查:10KVI母線確無故障,即令其將10KVI母線所屬出線停電。合上#I主變10KV側(cè)002開關(guān),將10KVI母線送電;送電良好后,將10KVI母線所屬出線逐一送電。當10KV魯平線送電時,重復上述故障,即令其:將10KV魯平線停電。告檢修公司速處理,通知文昌所帶電巡線匯報領(lǐng)導及客服,做好記錄。二、萬德變電站事故預案運行方式:35KV萬德線帶35KVⅠⅡ段母線,,帶#Ⅱ主變,帶10KVⅠⅡ段母線全部負荷,#Ⅰ主變熱備用,張夏線3104開關(guān)熱備用。(一)萬德線故障跳閘事故處理處理步驟:萬德變由萬德線調(diào)張夏線供電(二)#Ⅱ主變差動動作兩側(cè)開關(guān)掉閘故障事故處理1、令操作隊#Ⅰ主變送電2、10KV全部負荷調(diào)I#主變供電3、通知檢修公司速到萬德變處理#Ⅱ主變差動故障4、匯報公司領(lǐng)導、做好錄音和記錄(三)35kvII母線故障事故處理1、令操作隊將35kvI母線故障點隔離2、立即將萬德變負荷由萬德線調(diào)張夏線供電3、令操作隊將#Ⅰ主變送電4、10KV全部負荷由#Ⅱ主變調(diào)I#主變供電5、通知檢修公司立即處理35kvⅡ母線故障6、匯報公司領(lǐng)導、做好錄音和記錄三、張夏變電站事故預案運行方式:35kV張夏線供35kV1段母線帶#2主變供10kV全部負荷。35kV萬德線熱備用,#1主變備用。(一)張夏線故障跳閘事故處理處理步驟:張夏變?nèi)矩摵捎蓮埾木€調(diào)萬德線供電(二)#Ⅱ主變差動動作兩側(cè)開關(guān)掉閘故障事故處理1、令操作隊將#Ⅰ主變送電2、10KV全部負荷調(diào)I#主變供電3、通知檢修公司速到張夏變處理#Ⅱ主變差動故障4、匯報公司領(lǐng)導、做好錄音和記錄張夏變#1主變帶10kv全部負荷時將出現(xiàn)過負荷運行,此時應按以下原則進行限電:1)先通知供電所按下面的10kV線路限負荷順序表對用戶進行限電。2)緊急時刻,可按照區(qū)經(jīng)濟委員會和供電公司聯(lián)合下發(fā)的《2007年電網(wǎng)限電拉路序位和事故拉路序位方案》進行限電拉路。四、馬鄉(xiāng)變電站事故預案運行方式:(一)馬鄉(xiāng)線故障跳閘事故處理處理步驟:馬鄉(xiāng)變?nèi)矩摵捎神R鄉(xiāng)線調(diào)馬五線線供電(二)#Ⅰ主變重瓦斯動作兩側(cè)開關(guān)掉閘故障事故處理1、令操作隊將#Ⅱ主變送電2、10KV全部負荷由#Ⅰ主變調(diào)#Ⅱ主變供電3、通知檢修公司速到馬鄉(xiāng)變處理#Ⅰ主變故障4、匯報公司領(lǐng)導、做好錄音和記錄5、告營銷部通知好用戶(三)35kvI母線故障事故處理1、令操作隊將35kvI母線故障點隔離2、令操作隊將#Ⅱ主變送電3、將10KV全部負荷由#I主變調(diào)#Ⅱ主變供電4、通知檢修公司立即處理35kvⅠ母線故障5、匯報公司領(lǐng)導、做好錄音和記錄馬鄉(xiāng)變五、五峰變電站事故預案運行方式:35kV五峰線供35kV1、2段母線帶#1、#Ⅱ主變,#1主變供10kvⅠ母線負荷,#Ⅱ主變供10kvⅡ母線負荷,35kv馬五線3902開關(guān)備用(一)五峰線故障跳閘事故處理處理步驟:五峰變?nèi)矩摵捎?5kv五峰線調(diào)35kv馬五線供電(二)#Ⅰ主變差動動作兩側(cè)開關(guān)掉閘故障事故處理1、令操作隊將10kvⅠ母線負荷由#Ⅰ主變調(diào)#Ⅱ供電2、通知檢修公司速到五峰變處理#Ⅰ主變故障4、匯報公司領(lǐng)導、做好錄音和記錄5、告營銷部通知好用戶(三)35kvI母線故障事故處理1、令操作隊將35kvI母線故障點隔離2、即令操作隊將五峰變?nèi)矩摵捎?5kv五峰線調(diào)35kv馬五線供電3、將10KVⅠ母線負荷由#I主變調(diào)#Ⅱ主變供電4、通知檢修公司立即處理35kvⅠ母線故障5、匯報公司領(lǐng)導、做好錄音和記錄此時五峰變會出現(xiàn)#Ⅱ主變過負荷時,按以下原則處理:1)先通知供電所按下面的10kV線路限負荷順序表對用戶進行限電。2)緊急時刻,可按照區(qū)經(jīng)濟委員會和供電公司聯(lián)合下發(fā)的《2007年電網(wǎng)限電拉路序位和事故拉路序位方案》進行限電拉路。3)五峰變限電拉路及事故拉路序位表:序號線路名稱電壓等級

(kV)線路最大負荷

(kW)用戶性質(zhì)1宋村線101400農(nóng)業(yè)客戶2紙坊線10420農(nóng)業(yè)客戶3張莊線10540農(nóng)業(yè)客戶4仙莊線10300風景區(qū)5鎮(zhèn)直線101250鎮(zhèn)政府駐地4)10kV線路限負荷順序表序號線路名稱限負荷順序(按從前到后順序)1宋村線拉148支1ZK、拉14FK2紙坊線拉52FK3張莊線拉49FK4仙莊線令用戶限負荷5鎮(zhèn)直線拉2支6ZK、拉9FK六、雙泉變電站事故預案運行方式:35kV馬崮線供35kV1、2段母線帶#2主變供10kV全部負荷,#1主變熱備用,35kv雙孝線304開關(guān)冷備用(一)馬崮線故障跳閘事故處理處理步驟:雙泉變?nèi)矩摵捎?5kv馬崮線調(diào)35kv雙孝線供電(二)#Ⅱ主變重瓦斯保護動作兩側(cè)開關(guān)掉閘故障事故處理1、令操作隊將#Ⅰ主變送電2、將#Ⅱ主變?nèi)控摵捎?Ⅱ主變調(diào)#Ⅰ供電3、#Ⅱ主變重瓦斯動作掉閘不能送電通知檢修公司速到雙泉變處理#Ⅱ主變故障4、匯報公司領(lǐng)導、做好錄音和記錄5、告營銷部通知好用戶(三)35kv分段300-1刀閘于35kvI段母線連接處嚴重放電1、令操作隊將35kvI母線停電隔離2、即令操作隊將雙泉變?nèi)矩摵捎?5kv馬崮線調(diào)35kv雙孝線供電3、通知檢修公司立即處理35kvⅠ母線放電4、匯報公司領(lǐng)導、做好錄音和記錄此時雙泉變會出現(xiàn)#Ⅰ主變過負荷時,按以下原則處理:1)先通知供電所按下面的10kV線路限負荷順序表對用戶進行限電。2)緊急時刻,按照《2007年電網(wǎng)限電拉路序位和事故拉路序位方案》進行限電拉路。3)雙泉變限電拉路及事故拉路序位表:序號線路名稱電壓等級

(kV)線路最大負荷

(kW)用戶性質(zhì)1雙安線10950農(nóng)業(yè)客戶2雙馬線103000農(nóng)業(yè)客戶3雙龍線10800鎮(zhèn)政府駐地4)10kV線路限負荷順序表序號線路名稱限負荷順序(按從前到后順序)1雙安線拉61FK、拉32FK2雙馬線拉29支0ZK、拉50FK3雙龍線拉92支0ZK、拉74支0ZK、拉18FK七、變電站事故預案運行方式:35kV長劉線供35kV1、2段母線帶#1、#Ⅱ主變,#1主變供10kvⅠ母線負荷,#Ⅱ主變供10kvⅡ母線負荷,35kv長紅線302開關(guān)備用(一)長劉線故障跳閘事故處理處理步驟:歸德變?nèi)矩摵捎?5kv長劉線調(diào)35kv長紅線供電(二)#Ⅰ主變差動保護動作002開關(guān)、303開關(guān)掉閘1、令操作隊將10kvⅠ母線負荷由#Ⅰ主變調(diào)#Ⅱ供電2、通知檢修公司速到歸德變處理#Ⅰ主變故障4、匯報公司領(lǐng)導、做好錄音和記錄5、告營銷部通知好用戶(三)歸德變長劉線301-3刀閘嚴重放電1、令操作隊將歸德變電站全站負荷由長劉線調(diào)長紅線供電.2、將長劉線301開關(guān)停電.3、注意檢查長紅線負荷情況4、通知檢修公司速到歸德變處理.5、匯報領(lǐng)導做好記錄和錄音。(四)35kvI母線故障事故處理1、令操作隊將35kvI母線故障點隔離2、即令操作隊將歸德變?nèi)矩摵捎?5kv長劉線調(diào)35kv長紅線供電3、將10KVⅠ母線負荷由#I主變調(diào)#Ⅱ主變供電4、通知檢修公司立即處理35kvⅠ母線故障5、匯報公司領(lǐng)導、做好錄音和記錄歸德變一臺主變運行將出現(xiàn)過負荷或事故處理原則:1)先通知供電所按下面的10kV線路限負荷順序表對用戶進行限電。2)緊急時刻,可按照區(qū)經(jīng)濟委員會和供電公司聯(lián)合下發(fā)的《2007年電網(wǎng)限電拉路序位和事故拉路序位方案》進行限電拉路。八、孝里變電站事故預案運行方式:35kV長紅線供35kV1、2段母線及雙孝線帶#1主變及10kv全部負荷,#Ⅱ主變備用。(一)長紅線故障跳閘事故處理處理步驟:孝里變?nèi)矩摵捎?5kv長紅線調(diào)35kv雙孝線供電(二)#Ⅰ主變重瓦斯保護動作1601開關(guān)、3601開關(guān)掉閘1、令操作隊將孝里變#Ⅱ主變送電2、將10kv全部負荷由#Ⅰ主變調(diào)#Ⅱ主變供電3、通知檢修公司速到孝里變處理#Ⅰ主變故障4、匯報公司領(lǐng)導、做好錄音和記錄5、告營銷部通知好用戶(三)孝里變35kvⅡ母線故障事故處理1、令操作隊拉開35kv分段3600-1,3600-2刀閘將35kvⅡ母線故障點隔離2、通知檢修公司速到孝里變處理35kvⅡ母線故障5、匯報領(lǐng)導做好記錄和錄音。孝里變電站#Ⅱ主變運行時將出現(xiàn)主變過負荷:1)先通知供電所按下面的10kV線路限負荷順序表對用戶進行限電。2)緊急時刻,按照區(qū)經(jīng)濟委員會和供電公司

溫馨提示

  • 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
  • 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
  • 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會有圖紙預覽,若沒有圖紙預覽就沒有圖紙。
  • 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
  • 5. 人人文庫網(wǎng)僅提供信息存儲空間,僅對用戶上傳內(nèi)容的表現(xiàn)方式做保護處理,對用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對任何下載內(nèi)容負責。
  • 6. 下載文件中如有侵權(quán)或不適當內(nèi)容,請與我們聯(lián)系,我們立即糾正。
  • 7. 本站不保證下載資源的準確性、安全性和完整性, 同時也不承擔用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。

最新文檔

評論

0/150

提交評論