![畢業(yè)設(shè)計(jì)(論文)110KV降壓變電所電氣部分的設(shè)計(jì)_第1頁(yè)](http://file2.renrendoc.com/fileroot_temp3/2021-8/23/b3342595-dd48-4dca-818a-689391c0183e/b3342595-dd48-4dca-818a-689391c0183e1.gif)
![畢業(yè)設(shè)計(jì)(論文)110KV降壓變電所電氣部分的設(shè)計(jì)_第2頁(yè)](http://file2.renrendoc.com/fileroot_temp3/2021-8/23/b3342595-dd48-4dca-818a-689391c0183e/b3342595-dd48-4dca-818a-689391c0183e2.gif)
![畢業(yè)設(shè)計(jì)(論文)110KV降壓變電所電氣部分的設(shè)計(jì)_第3頁(yè)](http://file2.renrendoc.com/fileroot_temp3/2021-8/23/b3342595-dd48-4dca-818a-689391c0183e/b3342595-dd48-4dca-818a-689391c0183e3.gif)
![畢業(yè)設(shè)計(jì)(論文)110KV降壓變電所電氣部分的設(shè)計(jì)_第4頁(yè)](http://file2.renrendoc.com/fileroot_temp3/2021-8/23/b3342595-dd48-4dca-818a-689391c0183e/b3342595-dd48-4dca-818a-689391c0183e4.gif)
![畢業(yè)設(shè)計(jì)(論文)110KV降壓變電所電氣部分的設(shè)計(jì)_第5頁(yè)](http://file2.renrendoc.com/fileroot_temp3/2021-8/23/b3342595-dd48-4dca-818a-689391c0183e/b3342595-dd48-4dca-818a-689391c0183e5.gif)
版權(quán)說(shuō)明:本文檔由用戶提供并上傳,收益歸屬內(nèi)容提供方,若內(nèi)容存在侵權(quán),請(qǐng)進(jìn)行舉報(bào)或認(rèn)領(lǐng)
文檔簡(jiǎn)介
1、 摘摘 要要 電力已成為人類(lèi)歷史發(fā)展的主要?jiǎng)恿Y源,要科學(xué)合理的使用及分配電力,必 須從工程的設(shè)計(jì)來(lái)提高電力系統(tǒng)的安全性、可靠性和運(yùn)行效率,從而達(dá)到降低成本, 提高經(jīng)濟(jì)效益的目的。變電站是電力系統(tǒng)配電傳輸不可缺少的重要組成部分,它直 接影響整個(gè)電力網(wǎng)絡(luò)的安全和電力運(yùn)行的經(jīng)濟(jì)成本,是聯(lián)系發(fā)電廠和用戶的中間環(huán) 節(jié),起著變換和分配電能的作用。電氣主接線是發(fā)電廠變電所電氣部分的主體,電 氣主接線的擬定直接關(guān)系著全廠(所)電氣設(shè)備的選擇、配電裝置的布置、繼電保 護(hù)和自動(dòng)裝置方式的確定,對(duì)電力系統(tǒng)的安全、可靠、經(jīng)濟(jì)運(yùn)行起著決定的作用。 本設(shè)計(jì)針對(duì) 110kv 降壓變電站進(jìn)行電氣部分設(shè)計(jì),電壓等級(jí) 110k
2、v/35kv/10kv;設(shè)計(jì)內(nèi)容包括:變壓器臺(tái)數(shù)和容量的選擇、主接線的選擇、短路 電流的計(jì)算、主要電器設(shè)備的選擇和校驗(yàn)、繼電保護(hù)及變電站防雷等。 設(shè)計(jì)中依據(jù)電力工程設(shè)計(jì)手冊(cè),電氣一次部分 、 發(fā)電廠、變電站電氣部分 , 電力繼電保護(hù)原理 中小型變電所實(shí)用設(shè)計(jì)手冊(cè) 電氣設(shè)備設(shè)計(jì)計(jì)算手冊(cè) 交流高壓斷路器訂貨技術(shù)條件 、 交流電氣裝置的過(guò)電壓保護(hù)和絕緣配合 、 高 壓配電裝置設(shè)計(jì)技術(shù)規(guī)程等國(guó)家和電力行業(yè)有關(guān) 110kv 變電所設(shè)計(jì)、標(biāo)準(zhǔn)、規(guī)程、 規(guī)范及國(guó)家有關(guān)安全、環(huán)保等強(qiáng)制性標(biāo)準(zhǔn)。 關(guān)鍵詞:降壓關(guān)鍵詞:降壓 變電站變電站 電氣電氣 設(shè)計(jì)設(shè)計(jì) 目目 錄錄 第一章第一章緒緒 論論1 第一節(jié)第一節(jié)選題背
3、景選題背景1 第二節(jié)第二節(jié)選題意義選題意義1 第三節(jié)第三節(jié)變電站發(fā)展概況變電站發(fā)展概況1 第四節(jié)第四節(jié)設(shè)計(jì)原始資料設(shè)計(jì)原始資料2 一、一、變電站的出線變電站的出線2 二、二、負(fù)荷情況負(fù)荷情況2 三、三、線路長(zhǎng)度線路長(zhǎng)度2 第二章第二章電氣主接線設(shè)計(jì)及短路電流計(jì)算電氣主接線設(shè)計(jì)及短路電流計(jì)算3 第一節(jié)第一節(jié)電氣主接線設(shè)計(jì)及主變壓器容量選擇電氣主接線設(shè)計(jì)及主變壓器容量選擇3 一、一、電氣主接線方案初選電氣主接線方案初選3 二、二、主接線方案比較主接線方案比較3 三、三、主變壓器的選擇主變壓器的選擇4 四、四、站用變壓器的選擇站用變壓器的選擇5 第二節(jié)第二節(jié)短路電流計(jì)算短路電流計(jì)算5 一、一、短路電
4、流的計(jì)算目的短路電流的計(jì)算目的5 二、二、短路電流計(jì)算點(diǎn)的確定短路電流計(jì)算點(diǎn)的確定6 三、三、計(jì)算步驟計(jì)算步驟6 四、四、變壓器、線路及電抗器的參數(shù)計(jì)算變壓器、線路及電抗器的參數(shù)計(jì)算6 五、五、系統(tǒng)網(wǎng)絡(luò)化簡(jiǎn)系統(tǒng)網(wǎng)絡(luò)化簡(jiǎn)8 六、六、110kv 母線短路點(diǎn)母線短路點(diǎn) 1 k的短路計(jì)算的短路計(jì)算8 七、七、35kv 母線母線短路點(diǎn)路點(diǎn) 2 k的短路計(jì)算的短路計(jì)算 10 八、八、10kv 母線短路點(diǎn)母線短路點(diǎn) 3 k的短路計(jì)算的短路計(jì)算11 九、九、10kv 出線短路點(diǎn)出線短路點(diǎn) 4 k的短路計(jì)算的短路計(jì)算 12 第三章第三章電氣主設(shè)備的選擇及校驗(yàn)電氣主設(shè)備的選擇及校驗(yàn)14 第一節(jié)第一節(jié)選擇原則及規(guī)定
5、選擇原則及規(guī)定14 一、一、一般原則一般原則14 二、二、校核電器的基本使用條件校核電器的基本使用條件14 三、三、各回路最大持續(xù)工作電流各回路最大持續(xù)工作電流14 第二節(jié)第二節(jié)主設(shè)備選擇及校驗(yàn)主設(shè)備選擇及校驗(yàn)15 一、一、斷路器的選擇及校驗(yàn)斷路器的選擇及校驗(yàn)15 二、二、隔離開(kāi)關(guān)的選擇及校驗(yàn)隔離開(kāi)關(guān)的選擇及校驗(yàn)18 三、三、電流互感器的選擇及校驗(yàn)電流互感器的選擇及校驗(yàn)21 四、四、電壓互感器的選擇電壓互感器的選擇26 五、五、避雷器的選擇及檢驗(yàn)避雷器的選擇及檢驗(yàn)28 六、六、母線的選擇及校驗(yàn)?zāi)妇€的選擇及校驗(yàn)30 七、七、熔斷器的選擇熔斷器的選擇32 第四章第四章主變保護(hù)整定計(jì)算及防雷接地計(jì)算
6、主變保護(hù)整定計(jì)算及防雷接地計(jì)算34 第一節(jié)第一節(jié)變壓器繼電保護(hù)變壓器繼電保護(hù)34 一、一、變壓器差動(dòng)保護(hù)計(jì)算變壓器差動(dòng)保護(hù)計(jì)算34 二、二、變壓器過(guò)流保護(hù)及過(guò)負(fù)荷保護(hù)計(jì)算變壓器過(guò)流保護(hù)及過(guò)負(fù)荷保護(hù)計(jì)算36 第二節(jié)第二節(jié)防雷接地計(jì)算防雷接地計(jì)算37 一、一、防雷計(jì)算防雷計(jì)算37 二、二、接地計(jì)算接地計(jì)算39 總總 結(jié)結(jié)41 致致 謝謝42 參參考考文文獻(xiàn)獻(xiàn)43 附錄附錄 a a 主接線方案圖主接線方案圖44 附錄附錄 b b 系統(tǒng)正序等值圖系統(tǒng)正序等值圖46 附錄附錄 c c 設(shè)備選擇參照?qǐng)D設(shè)備選擇參照?qǐng)D47 附錄附錄 d d 短路電流計(jì)算結(jié)果表短路電流計(jì)算結(jié)果表48 附錄附錄 e e 變電所主
7、體設(shè)備型號(hào)一覽表變電所主體設(shè)備型號(hào)一覽表49 第一章第一章緒緒 論論 第一節(jié)第一節(jié) 選題背景選題背景 電力已成為人類(lèi)歷史發(fā)展的主要?jiǎng)恿Y源,要科學(xué)合理的使用及分配電力,必 須從工程的設(shè)計(jì)來(lái)提高電力系統(tǒng)的安全性、可靠性和運(yùn)行效率,從而達(dá)到降低成本, 提高經(jīng)濟(jì)效益的目的。變電站是電力系統(tǒng)配電傳輸不可缺少的重要組成部分,它直 接影響整個(gè)電力網(wǎng)絡(luò)的安全和電力運(yùn)行的經(jīng)濟(jì)成本,是聯(lián)系發(fā)電廠和用戶的中間環(huán) 節(jié),起著變換和分配電能的作用。電氣主接線是發(fā)電廠變電所電氣部分的主體,電 氣主接線的擬定直接關(guān)系著全廠(所)電氣設(shè)備的選擇、配電裝置的布置、繼電保 護(hù)和自動(dòng)裝置方式的確定,對(duì)電力系統(tǒng)的安全、可靠、經(jīng)濟(jì)運(yùn)行
8、起著決定的作用。 目前,110kv、35kv 常規(guī)變電站在城農(nóng)網(wǎng)中仍占有較大的比重,其一次、二次 設(shè)備都比較落后,繼電保護(hù)裝置多為電磁式繼電器組合而成,一般只具有當(dāng)?shù)乜刂?功能,多為有人值班運(yùn)行方式。隨著電網(wǎng)運(yùn)行自動(dòng)化系統(tǒng)的提高,變電站綜合自動(dòng)化 系統(tǒng)發(fā)揮著越來(lái)越強(qiáng)大的作用,少人或無(wú)人值守變電站將成為今后變電運(yùn)行的主流方 式,對(duì)原有電站及新建電站實(shí)現(xiàn)無(wú)人值守勢(shì)在必行。對(duì)設(shè)計(jì)人員來(lái)講,我們只有不 斷提高自身素質(zhì),才能跟得上電力系統(tǒng)的飛速發(fā)展,為電力事業(yè)的興盛盡一點(diǎn)微薄 之力。 第二節(jié)第二節(jié) 選題意義選題意義 變電站是電力系統(tǒng)中變換電壓、接受和分配電能、控制電力的流向和調(diào)整電壓 的電力設(shè)施,它通過(guò)
9、其變壓器將各級(jí)電壓的電網(wǎng)聯(lián)系起來(lái)。變電站起變換電壓作用 的設(shè)備是變壓器,除此之外,變電站的設(shè)備還有開(kāi)閉電路的開(kāi)關(guān)設(shè)備,匯集電流的 母線,計(jì)量和控制用互感器、儀表、繼電保護(hù)裝置和防雷保護(hù)裝置、調(diào)度通信裝置 等,有的變電站還有無(wú)功補(bǔ)償設(shè)備。 本設(shè)計(jì)針對(duì)變電站進(jìn)行設(shè)計(jì),設(shè)計(jì)內(nèi)容包括:變壓器臺(tái)數(shù)和容量的選擇、主接 線的選擇、短路電流的計(jì)算、主要電器設(shè)備的選擇和校驗(yàn)、繼電保護(hù)及變電站防雷 等。通過(guò)對(duì) 110kv 降壓變電所電氣部分的設(shè)計(jì),使我明白其目的在于使我們通過(guò)這 次畢業(yè)設(shè)計(jì),能夠得到各方面的充分訓(xùn)練,結(jié)合畢業(yè)設(shè)計(jì)任務(wù)加深了對(duì)所學(xué)知識(shí)內(nèi) 在聯(lián)系的理解,并能靈活的運(yùn)用。 第三節(jié)第三節(jié) 變電站發(fā)展概況變
10、電站發(fā)展概況 隨著計(jì)算機(jī)技術(shù)的飛速發(fā)展,微型計(jì)算機(jī)技術(shù)在電力系統(tǒng)中得到了越來(lái)越廣泛 的應(yīng)用,它集變電站中的控制、保護(hù)、測(cè)量、中央信號(hào)、故障錄波等功能于一身, 替代了原常規(guī)的突出式和插件式電磁保護(hù)、晶體管保護(hù)、集成電路保護(hù)。常規(guī)控制、 保護(hù)裝置已逐步從電力系統(tǒng)中退出,取而代之的則是這種新型的微機(jī)監(jiān)控方式,它 運(yùn)用了自動(dòng)控制技術(shù)、微機(jī)及網(wǎng)絡(luò)通信技術(shù),經(jīng)過(guò)功能的重新組合和優(yōu)化設(shè)計(jì),組 成計(jì)算機(jī)的軟硬件設(shè)備代替人工,利用變電站中的遠(yuǎn)動(dòng)終端設(shè)備來(lái)完成對(duì)站中設(shè)備的 遙信、遙測(cè)、遙調(diào)、遙控即四遙功能。這就為實(shí)現(xiàn)變電站無(wú)人值守提供了前提條件。 變電站、所綜合自動(dòng)化和無(wú)人值守是當(dāng)今電網(wǎng)調(diào)度自動(dòng)化領(lǐng)域中熱門(mén)的話題
11、,在當(dāng) 今城、農(nóng)網(wǎng)建設(shè)改造中正被廣泛采用。 第四節(jié)第四節(jié) 設(shè)計(jì)原始資料設(shè)計(jì)原始資料 一、一、變電站的出線變電站的出線 變電站的電壓等級(jí)為 110kv/35kv/10kv,設(shè)兩臺(tái)主變,變電站最終規(guī)模的進(jìn)出 線回路數(shù)為: 110kv:2 回(雙電源進(jìn)線) 35kv:6 回(終端用戶) 10kv: 12 回(終端用戶) 二、二、負(fù)荷情況負(fù)荷情況 35kv、10kv 負(fù)荷情況見(jiàn)下表。 表 1-1 負(fù)荷情況表 電壓等級(jí)負(fù)荷級(jí)別最大負(fù)荷(mw)合計(jì)負(fù)荷(mw) i8 ii835kv iii4 20 i7 ii510kv iii4 16 站用電 i0.60.6 三、三、線路長(zhǎng)度線路長(zhǎng)度 110kv: 架空線
12、,170 公里 35kv: 架空線,76 公里 10kv: 架空線,27 公里 3 第二章第二章電氣主接線設(shè)計(jì)及短路電流計(jì)算電氣主接線設(shè)計(jì)及短路電流計(jì)算 第一節(jié)第一節(jié)電氣主接線設(shè)計(jì)及主變壓器容量選擇電氣主接線設(shè)計(jì)及主變壓器容量選擇 一、一、電氣主接線方案初選電氣主接線方案初選 根據(jù) gb50059-9235110kv 變電站設(shè)計(jì)規(guī)范 ,設(shè)計(jì)任務(wù)書(shū)中站給資料中要 求,變電站的主接線,應(yīng)根據(jù)變電站在電力網(wǎng)中的地位,出線回路數(shù),設(shè)備特點(diǎn)及 負(fù)荷性質(zhì)等條件確定,并應(yīng)滿足供電可靠,運(yùn)行靈活,操作檢修方便,節(jié)約投資和 便于擴(kuò)建,同時(shí)應(yīng)滿足以下條件: 1當(dāng)能滿足運(yùn)行要求時(shí),變電站高壓側(cè)宜采用斷路器較少或不用
13、斷路器的接線。 235110kv 線路為兩回以下時(shí),宜采用橋形,線路變壓器組線路分支接線。 3當(dāng)變電站裝有兩臺(tái)主變時(shí),610kv 側(cè)宜采用分段單母線。線路 12 回及以 下時(shí),變電站 10kv 可用雙母線;當(dāng)不許停電檢修斷路器時(shí),可裝設(shè)旁路設(shè)施。 4接在母線上的:避雷器和電壓互感器可合用一組隔離開(kāi)關(guān),對(duì)接在變壓器引 出線上的避雷器,不宜裝設(shè)隔離開(kāi)關(guān)。 根據(jù)以上要求初步選擇主接線如下: (一)方案一(接線圖見(jiàn):附錄 a) 1110kv 側(cè)、35kv 側(cè)和 10kv 側(cè)均采用單母分段的接線方式。 2主變?nèi)萘考芭_(tái)數(shù)的選擇:2 臺(tái)主變?nèi)萘肯嗤?(二)方案二(接線圖見(jiàn):附錄 a) 1110kv 側(cè)采用
14、橋形接線,35kv 側(cè)和 10kv 側(cè)采用單母分段的接線。 2主變?nèi)萘考芭_(tái)數(shù)的選擇:2 臺(tái)主變?nèi)萘客桨敢弧?二、二、主接線方案比較主接線方案比較 綜上所述,由于方案二采用橋形接線,使用的斷路器比方案一少。主變臺(tái)數(shù)、 型號(hào)、參數(shù)均相同,同時(shí)又不降低用電和供電可靠性,又符合現(xiàn)場(chǎng)實(shí)際和設(shè)計(jì)規(guī)程 的要求,從經(jīng)濟(jì)角度考慮選擇方案二比較合適,達(dá)到了工程造價(jià)較低,同時(shí)考慮了 變電站隨著負(fù)荷的增加,進(jìn)行擴(kuò)建和增容的可能性,因?yàn)闃蚴浇泳€在負(fù)荷增加時(shí), 可很方便的改造為單母線分段,以適應(yīng)負(fù)荷增加和供電可靠性的要求。 同時(shí),從技術(shù)角度,方案一中斷路器 3、斷路器 4 之間及母線發(fā)生短路,則斷 路器 3、斷路器 4
15、、斷路器 5 分別跳閘,即所有負(fù)荷由 1 號(hào)主變承擔(dān);方案二中當(dāng)斷 路器 3 至變壓器繞組內(nèi)及斷路器 2 右側(cè)發(fā)生短路,則斷路器 2、斷路器 3 及變壓器 中、低側(cè)分別跳閘,即所有負(fù)荷由 1 號(hào)主變承擔(dān)。再如,方案一如母線發(fā)生短路, 斷路器 4、斷路器 5、斷路器 3 分別跳閘,2 號(hào)主變停止向負(fù)荷供電;方案二中內(nèi)橋 4 斷路器 2 側(cè)母線發(fā)生短路,斷路器 2、斷路器 3、2 號(hào)主變中、低壓側(cè)分別跳閘,停 止向負(fù)荷供電。 由以上分析,方案一和方案二在技術(shù)上是相當(dāng)?shù)模鴱慕?jīng)濟(jì)上講,方案一比方 案二多用了兩組斷路.兩組隔離開(kāi)關(guān)和母線,所以,最終確定方案二為本設(shè)計(jì)的主接 線。 三、三、主變壓器的選擇
16、主變壓器的選擇 1. 運(yùn)行主變壓器的容量應(yīng)根據(jù)電力系統(tǒng) 1020 年的發(fā)展規(guī)劃進(jìn)行選擇。由于 任務(wù)書(shū)給定的是一個(gè)三個(gè)電壓等級(jí)的變電站,而且每個(gè)電壓等級(jí)的負(fù)荷均較大,故 采用三繞組變壓器 2 臺(tái),運(yùn)行主變壓器的容量應(yīng)根據(jù)電力系統(tǒng) 1020 年的發(fā)展規(guī)劃 進(jìn)行選擇。并應(yīng)考慮變壓器正常運(yùn)行和事故過(guò)負(fù)荷能力,以變壓器正常的過(guò)負(fù)荷能 力來(lái)承擔(dān)變壓器遭受的短時(shí)高峰負(fù)荷,過(guò)負(fù)荷值以不縮短變壓器的壽命為限。通常 每臺(tái)變壓器容量應(yīng)當(dāng)在當(dāng)一臺(tái)變壓器停用時(shí),另一臺(tái)容量至少保證對(duì) 60%負(fù)荷的供 電,并考慮事故過(guò)負(fù)荷能力選擇變壓器容量,亦即短路時(shí)可承擔(dān) 100%的負(fù)荷。 2. 主變?nèi)萘窟x擇 sn0.6sm。(sm為變
17、電站最大負(fù)荷) 3. 兩臺(tái)主變可方便于運(yùn)行維護(hù)和設(shè)備的檢修同時(shí)能滿足站用負(fù)荷的供電要 兩 臺(tái)求。 4.主變壓器形式的選擇: 相數(shù)的確定 為了提高電壓質(zhì)量最好選擇有載調(diào)壓變壓器。 繞組的確定 本站具有三種電壓等級(jí),且通過(guò)主變各側(cè)繞組功率均達(dá)到該變壓器容量的 15% 以上,故選三繞組變壓器。 繞組的連接方式 考慮系統(tǒng)的并列同期要求以及三次諧波的影響,本站主變壓器繞組連接方式選 用 y0/y/11。 采用“”接線的目的就是為三次諧波電流提供通路,保證主磁通和相電勢(shì)接近 正弦波,附加損耗和局過(guò)熱的情況大為改善,同時(shí)限制諧波向高壓側(cè)轉(zhuǎn)移。 5.主變?nèi)萘康拇_定: 考慮變壓器有 1.3 倍事故過(guò)負(fù)荷能力,則
18、 0.6*1.3=78%,即退出一臺(tái)時(shí),可 以滿足 78%的最大負(fù)荷。本站主要負(fù)荷占 60%,在短路時(shí)(2 小時(shí))帶全部主要負(fù) 荷和一半左右類(lèi)負(fù)荷。在兩小時(shí)內(nèi)進(jìn)行調(diào)度,使主要負(fù)荷減至正常水平。 sn=0.6pmax/ (2-1)cos =0.6(22+16)/0.92 =24.783mva=24783kva 選 sspsl-25000 型,選擇結(jié)果如表 2-1: 5 表 2-1 主變壓器參數(shù)表 損耗(kw)阻抗電壓(%) 型號(hào)及容量 (kva) 額定電壓 高/中/低 (kv) 連接組空 載 短路 高 中 高低 中 低 空載 電流 (%) 運(yùn)輸 重量 (t) 備注 sspsl-25000 110
19、/38.5/11 y0/y/-12- 11 38.214810.517-18 61.0 55.1 四、四、站用變壓器的選擇站用變壓器的選擇 由主變壓器容量為 25000kva,站用電率為 0.5%,可選用變壓器容量。 sn=250000.5%=125kva 選 sjl1160 型,選擇結(jié)果如表 2-2: 表 2-2 站用變壓器參數(shù)表 損耗 (kw) 型號(hào)及容量 (kva) 低壓側(cè)額定電壓 (kv) 連接組 空 載 短 路 阻抗電 壓(%) 空載電流 (%) 總重 (t) 備 注 sjl11600.4y/y0-12 0.5 2.9430.81 第二節(jié)第二節(jié)短路電流計(jì)算短路電流計(jì)算 在發(fā)電廠和變電
20、所的電氣設(shè)計(jì)中,短路電流計(jì)算是其中的一個(gè)重要環(huán)節(jié)。其計(jì) 算的目的主要有以下幾個(gè)方面: 在選擇電氣主接線時(shí),為了保證設(shè)備在正常運(yùn)行和故障情況下都能安全、可靠 地工作,同時(shí)又力求節(jié)約資金,這就需要進(jìn)行全面的短路電流計(jì)算。例如:計(jì)算某 一時(shí)刻的短路電流有效值,用以校驗(yàn)開(kāi)關(guān)設(shè)備的開(kāi)斷能力和確定電抗器的電抗值; 計(jì)算短路后較長(zhǎng)時(shí)間短路電流有效值,用以校驗(yàn)設(shè)備的熱穩(wěn)定;計(jì)算短路電流沖擊 值,用以校驗(yàn)設(shè)備動(dòng)穩(wěn)定。 在設(shè)計(jì)屋外高壓配電裝置時(shí),需按短路條件校驗(yàn)軟導(dǎo)線的相間和相對(duì)地的安全 距離。 在選擇繼電保護(hù)方式和進(jìn)行整定計(jì)算時(shí),需以各種短路的短路電流為依據(jù)。接 地裝置的設(shè)計(jì),也需要短路電流。 一、一、短路電流
21、的計(jì)算目的短路電流的計(jì)算目的 1電氣主設(shè)備的選擇和比較 6 2電氣設(shè)備和載流導(dǎo)體的選擇和校驗(yàn) 3繼電保護(hù)整定計(jì)算 二、二、短路電流計(jì)算點(diǎn)的確定短路電流計(jì)算點(diǎn)的確定 1確定原則:計(jì)算短路電流時(shí),短路點(diǎn)的選擇,應(yīng)使站選擇的電氣設(shè)備和載流 導(dǎo)體通過(guò)可能最大的短路電流。 2短路點(diǎn)的確定,根據(jù)以上原則,選擇了 4 個(gè)短路點(diǎn)。 3基準(zhǔn)值的選?。簊b100mvaub取各側(cè)平均額定電壓 三、三、計(jì)算步驟計(jì)算步驟 1選擇計(jì)算短路點(diǎn) 2畫(huà)等值網(wǎng)絡(luò)(次暫態(tài)網(wǎng)絡(luò))圖 首先去掉系統(tǒng)中的所有負(fù)荷分支,線路電容、各元件的電阻,發(fā)電機(jī)電抗用次暫 態(tài)電抗 xd” 3選取基準(zhǔn)容量 sb 和基準(zhǔn)電壓 ub(一般取后級(jí)的平均電壓)
22、4將各元件電抗換算為同一基準(zhǔn)值的標(biāo)么值 5給出等值網(wǎng)絡(luò)圖,并將各元件電抗統(tǒng)一編號(hào) 6化簡(jiǎn)等值網(wǎng)絡(luò),為計(jì)算不同短路點(diǎn)的短路電流值,需將等值網(wǎng)絡(luò)分別化簡(jiǎn)為 以短路點(diǎn)為中心的輻射形等值網(wǎng)絡(luò),并求出各電源與短路點(diǎn)之間的電抗,即轉(zhuǎn)移電 抗 。 nd x 7求計(jì)算電抗。 js x 8由運(yùn)算曲線查出(各電源供給的短路電流周期分量標(biāo)么值運(yùn)算曲線只作到 =3.5) 。 js x 9計(jì)算無(wú)限大容量(或=3)的電源供給的短路電流周期分量。 js x 10計(jì)算短路電流周期分量有名值和短路容量。 11計(jì)算短路電流沖擊值。 12計(jì)算異步電動(dòng)機(jī)攻擊的短路電流。 13繪制短路電流計(jì)算結(jié)果表。 四、四、變壓器、線路及電抗器的參
23、數(shù)計(jì)算變壓器、線路及電抗器的參數(shù)計(jì)算 (一)(一) 變壓器參數(shù)的計(jì)算變壓器參數(shù)的計(jì)算 xb*.1高壓繞組電抗 xb*.2中壓繞組電抗 xb*.3低壓繞組電抗 ud(1-2)%高壓與中壓繞組短路電壓百分值 7 ud(1-3)%高壓與低壓繞組短路電壓百分值 ud(2-3)%中壓與低壓繞組短路電壓百分值 1主變壓器參數(shù)計(jì)算 由表 2-1 查明,選 sspsl25000 型號(hào)參數(shù): ud(1-2)%=10.5 ud(1-3)%=18ud(2-3)%=6.5 ud1%= 1/2(ud(1-2)%+ ud(1-3)%- ud(2-3)%) =1/2(10.5+18-6.5) =11 ud2%= 1/2(u
24、d(1-2)%+ ud(2-3)%- ud(1-3)%) =1/2(10.5+6.5-18) =-0.5 ud3%= 1/2(ud(2-3)%+ ud(1-3)%- ud(1-2)%) =1/2(6.5+18-10.5) =7 xb*.1=0.44 (2-1) 25 100 100 11 100 % 1 n bd s su xb*.2=-0.02 (2-2) 25 100 100 5 . 0 100 % 2 n bd s su xb*.3=-0.28 (2-3) 25 100 100 7 100 % 3 n bd s su 3站用變壓器參數(shù)計(jì)算 由表 2-2 查明:選 sjli160 型號(hào)參數(shù)
25、: ud%=4 xb*.4=8 (2-4) 16 . 0 100 100 4 100 % n bd s su (二)(二) 線路參數(shù)計(jì)算線路參數(shù)計(jì)算 110kv 線路:xl*1 =xol1=168 0.2=0.222 (2-5) 2 b b u s 2 115 100 35kv 線路:xl*2 =xol2=78 0.4=0.236 (2-6) 2 b b u s 2 115 100 10kv 線路:xl*3 =xol3=26 0.4=0.078 (2-7) 2 b b u s 2 115 100 (三)(三) 電抗器的參數(shù)計(jì)算電抗器的參數(shù)計(jì)算 8 1出線電抗器電抗標(biāo)幺值參數(shù)計(jì)算: in= x*
26、n=173.210 a (2-8) 1003 300 3 max, n n u u 所以取 in=200 a 由表 4-2 查得:ib=5.5 a xk.* = xk=1.565 (2-9) 5 . 10 10 200 105 . 5 100 6 3 b n n b u u i i 2分段電抗器電抗標(biāo)幺值參數(shù)計(jì)算: in=200 a xk=10 查表可得:xk.*=2.62 五、五、系統(tǒng)網(wǎng)絡(luò)化簡(jiǎn)系統(tǒng)網(wǎng)絡(luò)化簡(jiǎn) 依據(jù)本變電站選定的接線方式及設(shè)備參數(shù),進(jìn)行網(wǎng)絡(luò)化簡(jiǎn)如下: (系統(tǒng)最大運(yùn)行方式時(shí),歸算到 sb100mva 的等值電抗 xs0.5) 圖 2-2 六、六、110kv 母線短路點(diǎn)母線短路點(diǎn)的短
27、路計(jì)算的短路計(jì)算 1 k 網(wǎng)絡(luò)化簡(jiǎn)如圖 2-3: 9 圖 2-3 x *=xs= xl*1=0.222 xjs=xmd= 0.517 (2-10) 100 233 517 . 0 b n s s 因?yàn)?xjs=0.517 3 所以查表得: * =1.913 i * =1.655 2 . 0 i * =1.953 i * =1.635 1 i = 0.502 ka (2-11) b i 1153 100 3 b b u s =1.170 ka (2-12) n i b i 100 233 502 . 0 b n s s = * =1.9131.170=2.238 ka (2-13) i i n
28、i = * =1.6651.170=1.947 ka (2-14) 2 . 0 i 2 . 0 i n i = * =1.9531.170= 2.285 ka (2-15) i i n i = * =1.6351.170= 1.913 ka (2-16) 1 i 1 i n i ich=2.55=2.552.238=5.707 ka (2-17) i ioh=1.52=1.522.238=3.402 ka (2-18) i =un=2.238110=426.384 mva (2-19)s3 i3 10 七、七、35kv 母線母線短路點(diǎn)路點(diǎn)的短路計(jì)算的短路計(jì)算 2 k 圖 2-4 圖 2-5 網(wǎng)
29、絡(luò)化簡(jiǎn)如圖 2-4、2-5: x *=x3=xs =0.432 (2-20) 2 02 . 0 44 . 0 0222 2 21 xx xjs=xmd=1.007 100 233 432 . 0 b n s s 因?yàn)?xjs=1.007 3 所以查表得: * =0.985 i * =0.910 2 . 0 i * =1.067 i * =1.003 1 i =1.56 ka b i 373 100 3 b b u s = =3.635 ka n i b i 100 233 56. 1 b n s s = * =0.9853.635=3.580 ka i i n i = * =0.9103.63
30、5=3.308 ka 2 . 0 i 2 . 0 i n i = * =1.0673.635=3.879 ka i i n i = * =1.0033.635=3.646 ka 1 i 1 i n i 11 ich=2.55=2.553.580=9.129 ka i ioh=1.52=1.523.580=5.442 ka i =un=3.58035=217.020 mvas3 i3 八、八、10kv 母線短路點(diǎn)母線短路點(diǎn)的短路計(jì)算的短路計(jì)算 3 k 圖 2-6 圖 2-7 網(wǎng)絡(luò)化簡(jiǎn)如圖 2-6、2-7: x *=x4= (2-21) 311331 31131 )( xxxxxx xxxxx x
31、 d d s = 28 . 0 44 . 0 62 . 2 28 . 0 44 . 0 )28 . 0 44 . 0 )(62 . 2 28 . 0 44 . 0 ( 222 . 0 =0.814 xjs=xmd=1.897 100 233 814 . 0 b n s s 因?yàn)?xjs=0.517 3 所以查表得: * =0.540 i * =0.511 2 . 0 i * =0.550 i * =0.550 1 i 12 =5.499 ka b i 5 . 103 100 3 b b u s = =12.812 ka n i b i 100 233 499 . 5 b n s s = * =
32、0.54012.812=2.238 ka i i n i = * =0.51112.812=6.547 ka 2 . 0 i 2 . 0 i n i = * =0.55012.812=7.047 ka i i n i = * =0.55012.812=7.047 ka 1 i 1 i n i ich=2.55=2.556.918=17.641 ka i ioh=1.52=1.526.918=10.515 ka i =un=6.91810=119.820 mvas3 i3 九、九、10kv 出線短路點(diǎn)出線短路點(diǎn)的短路計(jì)算的短路計(jì)算 4 k 網(wǎng)絡(luò)化簡(jiǎn)如圖 2-8、2-9: 圖 2-8 圖 2-9
33、x *=x4= (2-22) 2 311331 31131 )( d d d s x xxxxxx xxxxx x 13 =565 . 1 28 . 0 44 . 0 62 . 2 28 . 0 44 . 0 )28 . 0 44 . 0 )(62 . 2 28 . 0 44 . 0 ( 222 . 0 =2.379 xjs=xmd=5.443 100 233 379 . 2 b n s s 因?yàn)?xjs=0.517 3 所以 *=*=*=*= =0.180 i 2 . 0 i i 1 i js x 1 544 . 5 1 in= ib=4.95ka 100 90 5 . 5 b n s s
34、i= i= i0.2=in= i*in= i0.2*in=0.0724.95=0.355ka i =5.499 ka b i 5 . 103 100 3 b b u s = =12.812 ka n i b i 100 233 499 . 5 b n s s = * =0.18012.812=2.331 ka i 2 . 0 i i 1 i i n i ich=2.55=2.552.331=5.893 ka i ioh=1.52=1.522.331=3.513 ka i =un=2.33110=40.027 mvas3 i3 14 第三章第三章電氣主設(shè)備的選擇及校驗(yàn)電氣主設(shè)備的選擇及校驗(yàn) 第一
35、節(jié)第一節(jié)選擇原則及規(guī)定選擇原則及規(guī)定 一、一、一般原則一般原則 1應(yīng)滿足正常運(yùn)行、檢修、短路和過(guò)電壓情況下的要求,并考慮發(fā)展。 2應(yīng)按當(dāng)?shù)丨h(huán)境條件校核。 3應(yīng)力求技術(shù)先進(jìn)和經(jīng)濟(jì)合理。 4與整個(gè)工程的建設(shè)標(biāo)準(zhǔn)應(yīng)協(xié)調(diào)一致。 5同類(lèi)設(shè)備應(yīng)盡量減少品種。 6選用的新產(chǎn)品均應(yīng)具有可靠的試驗(yàn)數(shù)據(jù),并經(jīng)正式鑒定合格,在特殊情況下, 用未經(jīng)正式鑒定的新產(chǎn)品時(shí),應(yīng)經(jīng)上級(jí)批準(zhǔn)。 二、二、校核電器的基本使用條件校核電器的基本使用條件 1在正常運(yùn)行條件下,各回路的持續(xù)工作電流 ig.max; 2按短路電流的有關(guān)規(guī)定來(lái)驗(yàn)算導(dǎo)體和電器設(shè)備; 3驗(yàn)算 110kv 以下電纜短路熱穩(wěn)定時(shí),所用的計(jì)算時(shí)間,一般采用主保護(hù)的 動(dòng)作
36、時(shí)間加相應(yīng)的斷路器全分閘時(shí)間,斷路器全分閘時(shí)間和電弧燃燒。 三、三、各回路最大持續(xù)工作電流各回路最大持續(xù)工作電流 表 3-1 最大持續(xù)工作電流表 回路名稱(chēng)計(jì)算公式及結(jié)果 110kv 母線 ig.max=0.138 ka 1103 2505 . 1 3 05 . 1 n n u s 110kv 進(jìn)線 ig.max=0.108 ka 92 . 0 1103 2/ )8035( cos3 2/ n u p 35kv 母線 ig.max=0.433 ka 353 2505 . 1 3 05 . 1 n n u s 35kv 出線 ig.max=0.108 ka 92. 0353 6 cos3 n u
37、p 10kv 母線 ig.max=1.516 ka 103 2505 . 1 3 05 . 1 n n u s 10kv 出線 ig.max=0.188 ka 92 . 0 1103 3 cos3 n u p 15 第二節(jié)第二節(jié)主設(shè)備選擇及校驗(yàn)主設(shè)備選擇及校驗(yàn) 一、一、斷路器的選擇及校驗(yàn)斷路器的選擇及校驗(yàn) 斷路器型式的選擇:除需滿足各項(xiàng)技術(shù)條件和環(huán)境條件外,還考慮便于安裝調(diào) 試和運(yùn)行維護(hù),并經(jīng)技術(shù)經(jīng)濟(jì)比較后才能確定。根據(jù)我國(guó)當(dāng)前制造情況,電壓 6220kv 的電網(wǎng)一般選用少油斷路器,電壓 110330kv 電網(wǎng),可選用 sf6或空氣 斷路器,大容量機(jī)組釆用封閉母線時(shí),如果需要裝設(shè)斷路器,宜選用
38、發(fā)電機(jī)專(zhuān)用斷 路器。 (一)(一) 母線斷路器母線斷路器 110 的選擇及校驗(yàn)的選擇及校驗(yàn) 1電壓:因?yàn)?ug=110kvun=110kv所以 ug= un 2電流:查表 3-1 得:ig.max=0.138ka138a 選出斷路器型號(hào)為 sw41101000 型,如表 3-2: 表 3-2 110kv 母線斷路器參數(shù)表 電壓電壓 (kv) 斷開(kāi)容量斷開(kāi)容量 (mva) 極限通過(guò)電極限通過(guò)電 流流(ka) 熱穩(wěn)定電流熱穩(wěn)定電流 (ka) 重合性能重合性能 型號(hào)型號(hào) 額額 定定 最最 大大 額定電額定電 流流(a) 額定斷額定斷 開(kāi)開(kāi) 電流電流 (ka) 額定額定 重新重新*最大最大 有效有效
39、2s 3s 4s 5s 合閘時(shí)合閘時(shí) 間間(s) 固有分閘固有分閘 時(shí)間時(shí)間(s)電流休止電流休止 時(shí)間時(shí)間(s) 重合時(shí)重合時(shí) 間間(s) sw4-110 110 126100018.43500 30005532.210.250.060.30.4 因?yàn)?in=1000aig.max=138a 所以 ig.max in 3開(kāi)斷電流:idtikd (3-1) 因?yàn)?idt=2.238kaikd=18.4ka所以 idtikd 4動(dòng)穩(wěn)定:ichimax (3-2) 因?yàn)?ich =5.707kaimax=55ka所以 ich1s 故 tdz=tz+0.05=1.85+0.050.9792=1.89
40、8 (3-5) 因?yàn)?i tdz=2.28521.898=9.910 itt=2125=2205 所以 i tdzitt 經(jīng)以上校驗(yàn)此斷路器滿足各項(xiàng)要求。 (二)(二) 110kv 進(jìn)線斷路器進(jìn)線斷路器 111、112 的選擇及校驗(yàn)的選擇及校驗(yàn) 16 1電壓:因?yàn)?ug=110kvun=110kv所以 ug= un 2電流:查表 3-1 得:ig.max=0.108ka108a 選出斷路器型號(hào)為 sw41101000 型。 故 ig.max in,此斷路器型號(hào)與斷路器 110 型號(hào)一樣,故這里不做重復(fù)檢驗(yàn)。 (三)(三) 35kv 母線斷路器母線斷路器 130、131、132 的選擇及校驗(yàn)的選
41、擇及校驗(yàn) 1電壓:因?yàn)?ug=35kvun=35kv所以 ug= un 2電流:查表 3-1 得:ig.max=0.433ka433a 選出斷路器型號(hào)為 zw2-35600 型,如表 3-3: 表 3-3 35kv 母線斷路器參數(shù)表 電壓 (kv) 動(dòng)穩(wěn)定電流 (ka) 型號(hào) 額定 額定 電流 (a) 額定斷 開(kāi) 電流 (ka) 峰值 4s 熱 穩(wěn)定電 流 (ka) 合閘 時(shí)間 (s) 固有分 閘時(shí)間 (s) zw2-35 35 6006.6176.60.060.12 因?yàn)?in=600aig.max=433a 所以 ig.max in 3開(kāi)斷電流:idtikd 因?yàn)?idt=3.580kai
42、kd=6.6ka所以 idtikd 4動(dòng)穩(wěn)定:ichimax 因?yàn)?ich =9.129kaimax=17ka所以 ich1s 故 tdz=tz+0.05=1.85+0.050.9232=1.893 因?yàn)?i tdz=3.87921.893=28.483itt=6.624=128 所以 i tdzitt 經(jīng)以上校驗(yàn)此斷路器滿足各項(xiàng)要求。 (四)(四) 35kv 出線斷路器出線斷路器 133 的選擇及校驗(yàn)的選擇及校驗(yàn) 1電壓:因?yàn)?ug=35kvun=35kv所以 ug= un 2電流:查表 3-1 得:ig.max=0.108ka108a 選出斷路器型號(hào)為 zn35630 型 17 故 ig.
43、max in,此斷路器型號(hào)與斷路器 130 型號(hào)一樣,故這里不做重復(fù)檢驗(yàn) (五)(五) 10kv 母線斷路器母線斷路器 120、121、122、的選擇及校驗(yàn)、的選擇及校驗(yàn) 1電壓:因?yàn)?ug=10kvun=10kv所以 ug= un 2電流:查表 3-1 得:ig.max=1.516ka1516a 選出斷路器型號(hào)為 zn12-10-2000 型,如表 3-4: 表 3-4 10kv 母線斷路器參數(shù)表 極限通過(guò)電 流(ka) 熱穩(wěn)定電流 (ka) 型號(hào) 額定 電壓 (kv) 額定電 流(a) 額定斷 開(kāi) 電流 (ka) 額定斷開(kāi) 容量 (mva)峰值1s4s 5s 合閘時(shí) 間(s) 固有分閘 時(shí)
44、間(s) zn12-10102000501800125173 120 850.0650.075 因?yàn)?in=2000aig.max=1516a所以 ig.max in 3開(kāi)斷電流:idtikd 因?yàn)?idt=6.918kaikd=50ka所以 idtikd 4動(dòng)穩(wěn)定:ichimax 因?yàn)?ich =17.641kaimax=125ka所以 ich1s 故 tdz=tz+0.05=1.85+0.050.9822=1.898 因?yàn)?i tdz=7.04721.898=94.255itt=31.524=3969 所以 i tdzitt 經(jīng)以上校驗(yàn)此斷路器滿足各項(xiàng)要求。 (六)(六) 10kv 出線斷
45、路器出線斷路器 123 的選擇及校驗(yàn)的選擇及校驗(yàn) 1電壓:因?yàn)?ug=10kvun=10kv所以 ug= un 2電流:查表 3-1 得:ig.max=0.475ka475a 選出斷路器型號(hào)為 zn1810630 型,如表 3-5: 表 3-5 10kv 出線斷路器參數(shù)表 極限通過(guò)電 流(ka) 熱穩(wěn)定電流 (ka)型號(hào) 額定 電壓 (kv) 額定電 流(a) 額定斷 開(kāi)電流 (ka) 額定斷開(kāi) 容量 (mva)峰值2s3s 4s 合閘時(shí) 間(s) 固有分閘 時(shí)間(s) 18 zn18-1012630205052200.070.06 因?yàn)?in=630aig.max=188a所以 ig.max
46、 in 3開(kāi)斷電流:idtikd 因?yàn)?idt=2.311kaikd=20ka所以 idtikd 4動(dòng)穩(wěn)定:ichimax 因?yàn)?ich =5.893kaimax=50ka所以 ich1s 故 tdz=tz+0.05=1.85+0.0512=1.9 因?yàn)?i tdz=2.31121.9=10.147itt=2024=1600 所以 i tdzitt 經(jīng)以上校驗(yàn)此斷路器滿足各項(xiàng)要求。 二、二、隔離開(kāi)關(guān)的選擇及校驗(yàn)隔離開(kāi)關(guān)的選擇及校驗(yàn) 隔離開(kāi)關(guān)是高壓開(kāi)關(guān)的一種,因?yàn)闆](méi)有專(zhuān)門(mén)的滅弧裝置,所以不能切斷負(fù)荷電 流和短路電流。但是它有明顯的斷開(kāi)點(diǎn),可以有效的隔離電源,通常與斷路器配合 使用。隔離開(kāi)關(guān)型式的
47、選擇,其技術(shù)條件與斷路器相同,應(yīng)根據(jù)配電裝置的布置特 點(diǎn)和使用要求等因素進(jìn)行綜合的技術(shù)經(jīng)濟(jì)比較,然后確定。 對(duì)隔離開(kāi)關(guān)的要求: 有明顯的斷開(kāi)點(diǎn)。為了確切的鑒別電器是否已經(jīng)與電網(wǎng)隔離,隔離開(kāi)關(guān)應(yīng)具 有可以直接看見(jiàn)的斷口。 斷開(kāi)點(diǎn)應(yīng)有可靠的絕緣。隔離開(kāi)關(guān)的斷開(kāi)點(diǎn)的動(dòng)靜觸頭之間,必須有足夠的 絕緣距離,使其在過(guò)電壓或相間閃絡(luò)情況下,也不會(huì)被擊穿而危及工作人員的安全。 具有足夠的動(dòng)穩(wěn)定性和熱穩(wěn)定性。隔離開(kāi)關(guān)在運(yùn)行中,經(jīng)常受到短路電流的 作用,必須能夠承受短路電流熱效應(yīng)和電動(dòng)力沖擊,尤其是不能因電動(dòng)力作用而自 動(dòng)斷開(kāi),否則將引起嚴(yán)重事故。 結(jié)構(gòu)得意動(dòng)作可靠。戶外隔離開(kāi)關(guān)在凍冰的環(huán)境里,也能可靠的分、合閘
48、 工作刀閘與接地刀閘聯(lián)鎖。帶有接地刀閘的隔離開(kāi)關(guān)必須有聯(lián)鎖機(jī)構(gòu),以保 證在合接地之前,必須先斷開(kāi)工作刀閘;在合工和刀閘之前,必須先斷開(kāi)接地刀閘。 (一)(一) 隔離開(kāi)關(guān)隔離開(kāi)關(guān) 110-1、110-2 的選擇及檢驗(yàn)的選擇及檢驗(yàn) 19 1電壓:因?yàn)?ug=110kvun=110kv所以 ug= un 2電流:查表 3-1 得:ig.max=138a 選出 gw2110600 型,如表 3-6: 表 3-6 110kv 隔離開(kāi)關(guān)參數(shù)表 型號(hào)額定電壓(kv)額定電流(a)動(dòng)穩(wěn)定電流(ka)熱穩(wěn)定電流(s)(ka) gw211 0 1106005014(5) 因?yàn)?in=600aig.max=138a
49、所以 ig.max in 3動(dòng)穩(wěn)定:ichimax 因?yàn)?ich =5.707kaimax=50ka所以 ichimax 4熱穩(wěn)定:i tdzitt 前面校驗(yàn)斷路器時(shí)已算出 i tdz =9.910 itt=1425=980 所以 i tdz itt 經(jīng)以上校驗(yàn)此隔離開(kāi)關(guān)滿足各項(xiàng)要求。 (二)(二) 隔離開(kāi)關(guān)隔離開(kāi)關(guān) 111-1、111-2、111-3、112-2、114-1、113-3 的選擇及校驗(yàn)。的選擇及校驗(yàn)。 1電壓:因?yàn)?ug=110kvun=110kv所以 ug= un 2電流:查表 3-1 得:ig.max=108a 選出 gw2110600 型 故 ig.max i ,此隔離開(kāi)
50、關(guān)型號(hào)與隔離開(kāi)關(guān) 110-1 型號(hào)一樣,故這里不做重復(fù)檢 n 驗(yàn) (三)(三) 隔離開(kāi)關(guān)隔離開(kāi)關(guān) 130-1、130-2、131-1、131-2、132-1、132-2 的選擇及檢驗(yàn)的選擇及檢驗(yàn) 1電壓:因?yàn)?ug=35kvun=35kv所以 ug= un 2電流:查表 3-1 得:ig.max=1.475ka433a 選出 gw235600 型,如表 3-7: 表 3-7 35kv 隔離開(kāi)關(guān)參數(shù)表 型號(hào)額定電壓(kv)額定電流(a)動(dòng)穩(wěn)定電流(ka)熱穩(wěn)定電流(s)(ka) gw235356005014(5) 因?yàn)?in=600aig.max=433a所以 ig.max in 3動(dòng)穩(wěn)定:ic
51、himax 因?yàn)?ich =9.129kaimax=50ka所以 ichimax 20 4熱穩(wěn)定:i tdzitt 前面校驗(yàn)斷路器時(shí)已算出 i tdz =28.439 itt=1425=980 所以 i tdz itt 經(jīng)以上校驗(yàn)此隔離開(kāi)關(guān)滿足各項(xiàng)要求。 (四)(四) 隔離開(kāi)關(guān)隔離開(kāi)關(guān) 133-1、133-2 的選擇及校驗(yàn)的選擇及校驗(yàn) 1電壓:因?yàn)?ug=35kvun=35kv所以 ug= un 2電流:查表 3-1 得:ig.max=108a 選出 gw835400 型,如表 3-8: 表 3-8 35kv 隔離開(kāi)關(guān)參數(shù)表 型號(hào)額定電壓(kv)額定電流(a)動(dòng)穩(wěn)定電流(ka)熱穩(wěn)定電流(s)
52、(ka) gw83535400155.6(5) 因?yàn)?in=400aig.max=108a所以 ig.max in 3動(dòng)穩(wěn)定:ichimax 因?yàn)?ich =9.129kaimax=15ka所以 ichimax 4熱穩(wěn)定:i tdzitt 前面校驗(yàn)斷路器時(shí)已算出 i tdz =28.483 itt=5.625=156.8 所以 i tdz itt 經(jīng)以上校驗(yàn)此隔離開(kāi)關(guān)滿足各項(xiàng)要求。 (五)(五) 隔離開(kāi)關(guān)隔離開(kāi)關(guān) 120-1、120-2、121-1、121-2、122-1、122-2 的選擇及校驗(yàn)的選擇及校驗(yàn) 1電壓:因?yàn)?ug=10kvun=10kv所以 ug= un 2電流:查表 3-1
53、得:ig.max=1516a 選出 gn1102000 型,如表 3-9: 表 3-9 10kv 隔離開(kāi)關(guān)參數(shù)表 型號(hào)額定電壓(kv)額定電流(a)動(dòng)穩(wěn)定電流(ka)熱穩(wěn)定電流(s)(ka) gn1101020008536(10) 因?yàn)?in=2000aig.max=1516a所以 ig.max in 3動(dòng)穩(wěn)定:ichimax 因?yàn)?ich =17.641kaimax=85ka所以 ichimax 21 4熱穩(wěn)定:i tditt 前面校驗(yàn)斷路器時(shí)已算出 i tdz=94.255 itt=36210=12960 所以 i tdzitt 經(jīng)以上校驗(yàn)此隔離開(kāi)關(guān)滿足各項(xiàng)要求。 (六)(六) 隔離開(kāi)關(guān)隔
54、離開(kāi)關(guān) 123-1、123-2 的選擇及校驗(yàn)的選擇及校驗(yàn) 1電壓:因?yàn)?ug=10kvun=10kv所以 ug= un 2電流:查表 3-1 得:ig.max=188a 選出 gn110200 型,如表 3-10: 表 3-10 10kv 隔離開(kāi)關(guān)參數(shù)表 型號(hào)額定電壓(kv)額定電流(a)動(dòng)穩(wěn)定電流(ka)熱穩(wěn)定電流(s)(ka) gw110102002510(5) 因?yàn)?in=400aig.max=188a所以 ig.max in 3動(dòng)穩(wěn)定:ichimax 因?yàn)?ich =5.893kaimax=25ka所以 ichimax 4熱穩(wěn)定:i tdzitt 前面校驗(yàn)斷路器時(shí)已算出 i td=10
55、.147 itt=1025=500 所以 i tditt 經(jīng)以上校驗(yàn)此隔離開(kāi)關(guān)滿足各項(xiàng)要求。 三、三、電流互感器的選擇及校驗(yàn)電流互感器的選擇及校驗(yàn) 互感器是發(fā)電廠和變電所的主要設(shè)備之一,它是變換電壓、電流的電氣設(shè)備, 它的主要功能是向二次系統(tǒng)提供電壓、電流信號(hào)以反應(yīng)一次系統(tǒng)的工作狀況,前者 稱(chēng)為電壓互感器,后者稱(chēng)為電流互感器。 1互感器的作用: 對(duì)低電壓的二次系統(tǒng)與高電壓的一次系統(tǒng)實(shí)施電氣隔離,保證工作人員的安 全。 由于互感器原、副繞組除接地點(diǎn)外無(wú)其它電路上的聯(lián)系,因此二次系統(tǒng)的對(duì)地 電位與一次系統(tǒng)無(wú)關(guān),只依賴(lài)于接地點(diǎn)與二次繞組其它各點(diǎn)的電位差,在正常運(yùn)行 情況下處于低壓的狀態(tài),方便于維護(hù)、
56、檢修與調(diào)試。 互感器副繞組接地的目的在于當(dāng)發(fā)生原、副繞組擊穿時(shí)降低二次系統(tǒng)的對(duì)地電 位,接地電阻愈小,對(duì)地電位愈低,從而保證人身安全,因此將其稱(chēng)為保護(hù)接地。 三相電壓互感器原繞組接成星形后中性點(diǎn)接地,其目的在于使原、副繞組的每 一相均反應(yīng)電網(wǎng)各相的對(duì)地電壓從而反應(yīng)接地短路故障,因此將該接地稱(chēng)為工作接 22 地。 將一次回路的高電壓和大電流變?yōu)槎位芈返臉?biāo)準(zhǔn)值,使測(cè)量?jī)x表和繼電器 小型化和標(biāo)準(zhǔn)化;使二次設(shè)備的絕緣水平可按低電壓設(shè)計(jì),從而結(jié)構(gòu)輕巧,價(jià)格便 宜;使所有二次設(shè)備能用低電壓、小電流控制電纜聯(lián)接,實(shí)現(xiàn)用小截面電纜進(jìn)行遠(yuǎn) 距離測(cè)量與控制,并使屏內(nèi)布線簡(jiǎn)單,安裝方便。 取得零序電流、電壓分量供
57、反應(yīng)接地故障的繼電保護(hù)裝置使用。 2電流互感器的配置原則 (1)每條支路的電源側(cè)均應(yīng)裝設(shè)足夠數(shù)量的電流互感器,供該支路的測(cè)量、保 護(hù)使用。此原則同于開(kāi)關(guān)電器的配置原則,因此往往有斷路器與電流互感器緊鄰布 置。配置的電流互感器應(yīng)滿足下列要求: a、一般應(yīng)將保護(hù)與測(cè)量用的電流互感器分開(kāi); b、盡可能將電能計(jì)量?jī)x表互感器與一般測(cè)量用互感器分開(kāi),前者必須使用 0.5 級(jí)互感器,并應(yīng)使正常工作電流在電流互感器額定電流的 2/3 左右; c、保護(hù)用互感器的安裝位置應(yīng)盡量擴(kuò)大保護(hù)范圍,盡量消除主保護(hù)的不保護(hù)區(qū); d、大接地電流系統(tǒng)一般三相配置以反映單相接地的故障;小電流接地系統(tǒng)發(fā)電 機(jī)、變壓器支路也應(yīng)三相配
58、置以便監(jiān)視不對(duì)稱(chēng)程度,其余支路一般配置于 a、c 兩 相。 (2)發(fā)電機(jī)出口配置一組電流互感器供發(fā)電機(jī)自動(dòng)調(diào)節(jié)勵(lì)磁裝置使用,相數(shù)、 變比、接線方式與自動(dòng)調(diào)節(jié)勵(lì)磁裝置的要求相符。 (3)配備差動(dòng)保護(hù)的元件,應(yīng)在元件各端口配置電流互感器,當(dāng)各端口屬于同 一電壓級(jí)時(shí),互感器變比應(yīng)相同,接線方式相同 3電流互感器的選擇 電流互感器的型式應(yīng)根據(jù)使用環(huán)境條件和產(chǎn)品情況選擇。對(duì)于 620kv 屋內(nèi)配 電裝置,可采用瓷絕緣結(jié)構(gòu)或樹(shù)脂澆注絕緣結(jié)構(gòu)的電流互感器。對(duì)于 35kv 及以上 配電裝置,一般采用油浸瓷箱式絕緣結(jié)構(gòu)的獨(dú)立式電流互感器。有條件時(shí),應(yīng)盡量 采用套管式電流互感器。 電流互感器的二次側(cè)額定電流有5a
59、和1a兩種,一般弱電系統(tǒng)用1a,強(qiáng)電系統(tǒng) 用5a,當(dāng)配電裝置距離控制室較遠(yuǎn)時(shí),亦可考慮用1a。 (1)一次額定電流的選擇: 當(dāng)電流互感器用于測(cè)量時(shí),其一次額定電流應(yīng)盡量選擇的比回路中正常工作電 流大1/3左右,以保證測(cè)量?jī)x表有最佳工作,并在過(guò)負(fù)荷時(shí),使儀表有適當(dāng)?shù)闹甘尽?電力變壓器中性點(diǎn)電流互感器的一次額定電流應(yīng)按大于變壓器允許的不平衡電 流選擇,一般情況下,可按變壓器額定電流的1/3進(jìn)行選擇。 23 電纜式零序電流互感器窗中應(yīng)能通過(guò)一次回路的所有電纜。 當(dāng)保護(hù)和測(cè)量?jī)x表共用一組電流互感器時(shí),只能選用相同的一次電流。 (2)準(zhǔn)確級(jí)的選擇: 與儀表連接接分流器、變送器、互感器、中間互感器不低于以
60、下要求: 用于電能測(cè)量的互感器準(zhǔn)確級(jí): 0.5 功電度表應(yīng)配用 0.2 級(jí)互感器;1.0 級(jí)有功電度表應(yīng)配用 0.5 級(jí)互感級(jí);2.0 級(jí)無(wú)功電度表也應(yīng)配用 0.5 級(jí)互感器;2.0 級(jí)有功電度表及 3.0 級(jí)無(wú)功電度表,可配 用 1.0 級(jí)級(jí)互感器;一般保護(hù)用的電流互感器可選用 3 級(jí),差動(dòng)距離及高頻保護(hù)用 的電流互感器宜選用 d 級(jí),零序接地保護(hù)可釆用專(zhuān)用的電流互感器,保護(hù)用電流互 感器一般按 10%倍數(shù)曲線進(jìn)行校驗(yàn)計(jì)算。 (一)(一) 110kv 進(jìn)線電流互感器的選擇及校驗(yàn)進(jìn)線電流互感器的選擇及校驗(yàn) 1一次回路電壓:因?yàn)?ug=110kvun=110kv所以 ug= un 2一次回路電流
溫馨提示
- 1. 本站所有資源如無(wú)特殊說(shuō)明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請(qǐng)下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請(qǐng)聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁(yè)內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒(méi)有圖紙預(yù)覽就沒(méi)有圖紙。
- 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
- 5. 人人文庫(kù)網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對(duì)任何下載內(nèi)容負(fù)責(zé)。
- 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請(qǐng)與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶因使用這些下載資源對(duì)自己和他人造成任何形式的傷害或損失。
最新文檔
- 軟件安全人才隊(duì)伍建設(shè)研究-詳解洞察
- 梧州2025年廣西梧州市事業(yè)單位招聘1257人筆試歷年參考題庫(kù)附帶答案詳解
- 2025年中國(guó)塑鋼垂簾軌市場(chǎng)調(diào)查研究報(bào)告
- 2025年針織橫機(jī)配件項(xiàng)目可行性研究報(bào)告
- 廣州廣東廣州市花都區(qū)花山鎮(zhèn)和郁小學(xué)臨聘教師招聘筆試歷年參考題庫(kù)附帶答案詳解
- 廣東廣東海洋大學(xué)后勤保障部招聘非編制水電維修工(第二次)筆試歷年參考題庫(kù)附帶答案詳解
- 2025年球衣網(wǎng)布項(xiàng)目可行性研究報(bào)告
- 2025年水電解器架項(xiàng)目可行性研究報(bào)告
- 2025至2031年中國(guó)旋風(fēng)式二級(jí)回收裝置行業(yè)投資前景及策略咨詢(xún)研究報(bào)告
- 2025年抗菌防霉乳膠漆項(xiàng)目可行性研究報(bào)告
- 學(xué)校小賣(mài)部承包合同范文
- 普外腹腔鏡手術(shù)護(hù)理常規(guī)
- 2025年湖南鐵道職業(yè)技術(shù)學(xué)院高職單招職業(yè)技能測(cè)試近5年??及鎱⒖碱}庫(kù)含答案解析
- 2024年全國(guó)職業(yè)院校技能大賽(礦井災(zāi)害應(yīng)急救援賽項(xiàng))考試題庫(kù)(含答案)
- 《預(yù)制高強(qiáng)混凝土風(fēng)電塔筒生產(chǎn)技術(shù)規(guī)程》文本附編制說(shuō)明
- 2025年浙江省溫州樂(lè)清市融媒體中心招聘4人歷年高頻重點(diǎn)提升(共500題)附帶答案詳解
- 2025年煤礦探放水證考試題庫(kù)
- C語(yǔ)言程序設(shè)計(jì) 教案
- 農(nóng)業(yè)機(jī)械設(shè)備運(yùn)輸及調(diào)試方案
- 監(jiān)控系統(tǒng)調(diào)試檢驗(yàn)批質(zhì)量驗(yàn)收記錄(新表)
- 室外晾衣架施工方案(共8頁(yè))
評(píng)論
0/150
提交評(píng)論