ICS29.240.01
F21
備案號:53939-2016
準(zhǔn)
T/CEC167—2018
直流配電網(wǎng)與交流配電網(wǎng)互聯(lián)
技術(shù)要求
TechnicalrequirementsforinterconnectionbetweenDCdistribution
networkandACdistributionnetwork
2018-01-24發(fā)布2018-04-01實施
中國電力企業(yè)聯(lián)合會發(fā)布
T/CEC167—2018
目次
前言···································································································································································II
直流配電網(wǎng)與交流配電網(wǎng)互聯(lián)技術(shù)要求·········································································································1
1范圍······························································································································································1
2規(guī)范性引用文件··········································································································································1
3術(shù)語和定義··················································································································································1
4一般規(guī)定······················································································································································2
5技術(shù)要求······················································································································································2
5.1交直流互聯(lián)方式·········································································································································2
5.2交直流互聯(lián)電壓·········································································································································3
5.3交直流互聯(lián)裝置·········································································································································4
5.4無功配置要求············································································································································5
5.5保護(hù)配合···················································································································································5
5.6接地要求···················································································································································6
I
T/CEC167—2018
前言
本標(biāo)準(zhǔn)按照GB/T1.1—2009《標(biāo)準(zhǔn)化工作導(dǎo)則第1部分:標(biāo)準(zhǔn)的結(jié)構(gòu)和編寫》給出的規(guī)則
起草。
請注意本標(biāo)準(zhǔn)的某些內(nèi)容可能涉及專利。本標(biāo)準(zhǔn)的發(fā)布機(jī)構(gòu)不承擔(dān)識別這些專利的責(zé)任。
本標(biāo)準(zhǔn)由中國電力企業(yè)聯(lián)合會歸口。
本標(biāo)準(zhǔn)主要起草單位:中國電力科學(xué)研究院有限公司、國網(wǎng)江蘇省電力有限公司(電力科學(xué)研究
院、常州供電分公司)、國網(wǎng)湖北省電力有限公司(經(jīng)濟(jì)技術(shù)研究院)、南瑞集團(tuán)有限公司(中電普瑞
科技有限公司)、國網(wǎng)山東省電力有限公司(泰安供電分公司)、西安交通大學(xué)、北京交通大學(xué)。
本標(biāo)準(zhǔn)主要起草人:吳鳴、孫麗敬、侯義明、李蕊、張海、焦在濱、王軒、陳亮、盛萬興、劉海濤、
蔡杰、羅國敏、季宇、呂志鵬、黃強(qiáng)、袁曉冬、李強(qiáng)、陸政、張偉、宋振浩、單來支。
本標(biāo)準(zhǔn)為首次發(fā)布。
本標(biāo)準(zhǔn)在執(zhí)行過程中的意見或建議反饋至中國電力企業(yè)聯(lián)合會標(biāo)準(zhǔn)化管理中心(北京市白廣路二
條一號,100761)。
II
T/CEC167—2018
直流配電網(wǎng)與交流配電網(wǎng)互聯(lián)技術(shù)要求
1范圍
本標(biāo)準(zhǔn)規(guī)定了直流配電網(wǎng)與交流配電網(wǎng)互聯(lián)技術(shù)涉及的交直流互聯(lián)方式、交直流互聯(lián)電壓、交直
流互聯(lián)裝置、無功配置、保護(hù)配合、接地等技術(shù)要求。
本標(biāo)準(zhǔn)適用于標(biāo)稱電壓±100kV及以下直流配電網(wǎng)與頻率為50Hz、標(biāo)稱電壓110kV及以下交流配
電網(wǎng)的互聯(lián)。
2規(guī)范性引用文件
下列文件對于本文件的應(yīng)用是必不可少的。凡是注日期的引用文件,僅注日期的版本適用于本文
件。凡是不注日期的引用文件,其最新版本(包括所有的修改單)適用于本文件。
GB/T156標(biāo)準(zhǔn)電壓
GB/T2900.50電工術(shù)語發(fā)電、輸電及配電通用術(shù)語
GB/T12325—2008電能質(zhì)量供電電壓偏差
GB/T12326電能質(zhì)量電壓波動和閃變
GB/T14285繼電保護(hù)和安全自動裝置技術(shù)規(guī)程
GB/T14549電能質(zhì)量公用電網(wǎng)諧波
GB/T15543電能質(zhì)量三相電壓不平衡
GB/T15945電能質(zhì)量電力系統(tǒng)頻率偏差
GB/T24337電能質(zhì)量公用電網(wǎng)間諧波
GB/T20989高壓直流換流站損耗的確定
GB/T30553基于電壓源換流器的高壓直流輸電
GB/T34139柔性直流輸電換流器技術(shù)規(guī)范
IEC62747用于高壓直流(HVDC)系統(tǒng)的電壓源換流器(VSC)術(shù)語[TerminologyforVoltage-
sourcedConverters(VSC)forHighVoltageDirectCurrent(HVDC)Systems]
T/CEC107直流配電電壓
DL/T836(所有部分)供電系統(tǒng)供電可靠性評價規(guī)程
DL/Z1697柔性直流配電系統(tǒng)用電壓源換流器技術(shù)導(dǎo)則
3術(shù)語和定義
下列術(shù)語和定義適用于本文件。
3.1
系統(tǒng)標(biāo)稱電壓systemnominalvoltage
用以標(biāo)志或識別系統(tǒng)電壓的給定值。
3.2
電壓偏差voltagedeviation
實際運(yùn)行電壓對系統(tǒng)標(biāo)稱電壓的偏差相對值,以百分?jǐn)?shù)表示。
[GB/T12325—2008,定義3.4]
1
T/CEC167—2018
3.3
交直流電壓轉(zhuǎn)換比AC/DCconversionratio
交直流互聯(lián)系統(tǒng)交流端口標(biāo)稱電壓幅值與直流端口標(biāo)稱電壓之比。計算公式為:
2Uac
Mac/dc=
Udc
式中:
Mac/dc——交直流電壓轉(zhuǎn)換比;
Uac——交流端口標(biāo)稱電壓有效值,單位為伏(V);
Udc——直流端口標(biāo)稱電壓,單位為伏(V)。
注:如直流側(cè)采用對稱單極母線結(jié)構(gòu),直流端口標(biāo)稱電壓指正直流母線與負(fù)直流母線之間電壓差的絕對值。
4一般規(guī)定
4.1直流配電網(wǎng)與交流配電網(wǎng)互聯(lián)應(yīng)保障交流配電網(wǎng)、直流配電網(wǎng)的安全、可靠、高效運(yùn)行。
4.2直流配電網(wǎng)與交流配電網(wǎng)互聯(lián)運(yùn)行時,應(yīng)能夠各自獨立隔離故障,降低互聯(lián)影響。
4.3直流配電網(wǎng)與交流配電網(wǎng)互聯(lián)宜遵循電壓匹配、傳輸容量相互適應(yīng)的原則。
4.4交直流互聯(lián)電壓的確定需要考慮現(xiàn)有交流電壓和直流電壓序列、分布式電源及用戶的便利接入。
4.5交直流互聯(lián)裝置技術(shù)要求的確定需要綜合考慮技術(shù)發(fā)展和設(shè)備制造水平等因素。
4.6直流配電網(wǎng)與交流配電網(wǎng)互聯(lián)配置的繼電保護(hù)應(yīng)滿足可靠性、選擇性、靈敏性和速動性的要求。
4.7直流配電系統(tǒng)的接地方式應(yīng)與交流系統(tǒng)接地方式、交直流換流器類型、換流器拓?fù)浣Y(jié)構(gòu)以及對直
流系統(tǒng)的可靠性要求與絕緣設(shè)計相互協(xié)調(diào),統(tǒng)籌考慮。
5技術(shù)要求
5.1交直流互聯(lián)方式
5.1.1交直流典型互聯(lián)方式如下:
a)經(jīng)單向功率傳輸換流器直接互聯(lián);
b)經(jīng)1:1聯(lián)接(換流)變壓器與單向功率傳輸換流器隔離互聯(lián);
c)經(jīng)升壓/降壓聯(lián)接(換流)變壓器與單向功率傳輸換流器隔離互聯(lián);
d)經(jīng)雙向功率傳輸換流器直接互聯(lián);
e)經(jīng)1:1聯(lián)接(換流)變壓器與雙向功率傳輸換流器隔離互聯(lián);
f)經(jīng)升壓/降壓聯(lián)接(換流)變壓器與雙向功率傳輸換流器隔離互聯(lián)。
5.1.2交直流互聯(lián)典型拓?fù)浣Y(jié)構(gòu)如下:
a)AC-DC。適用于交流型負(fù)荷和分布式電源所占比重較大,且存在一定數(shù)量的直流型負(fù)荷和分
布式電源的配電區(qū)域。典型拓?fù)浣Y(jié)構(gòu)如圖1所示。
b)DC-AC。適用于直流型負(fù)荷和分布式電源所占比重較大,且存在一定數(shù)量的交流型負(fù)荷和分
布式電源的配電區(qū)域。典型拓?fù)浣Y(jié)構(gòu)如圖2所示。
c)AC-DC-AC。可適用于兩個交流配電網(wǎng)互聯(lián)合環(huán)運(yùn)行的配電區(qū)域,也可適用于直流型負(fù)荷和分
布式電源較為集中的高可靠型供電區(qū)域。典型拓?fù)浣Y(jié)構(gòu)如圖3所示。
其他互聯(lián)的拓?fù)浣Y(jié)構(gòu)一般是AC-DC、DC-AC、AC-DC-AC三種典型結(jié)構(gòu)的組合。
5.2交直流互聯(lián)電壓
在本標(biāo)準(zhǔn)5.1.1給出的d)、e)兩種互聯(lián)方式下,直流配電網(wǎng)與交流配電網(wǎng)對應(yīng)的標(biāo)稱電壓,如表
1所示。
2
T/CEC167—2018
圖1交直流互聯(lián)AC-DC典型拓?fù)浣Y(jié)構(gòu)示意圖
圖2交直流互聯(lián)DC-AC典型拓?fù)浣Y(jié)構(gòu)示意圖
圖3交直流互聯(lián)AC-DC-AC典型拓?fù)浣Y(jié)構(gòu)示意圖
表1交直流互聯(lián)電壓
直流標(biāo)稱電壓交流標(biāo)稱電壓
kVkV
±100110
±50(備選)—
±3535
±2020
±10
10
20
±6(備選)6
±33
±1.51.5
3
T/CEC167—2018
表1(續(xù))
直流標(biāo)稱電壓交流標(biāo)稱電壓
kVkV
3
0.75(0.4對應(yīng)單相交流系統(tǒng))0.38(0.22單相)
注1:標(biāo)稱電壓20kV的單極母線結(jié)構(gòu)的直流配電網(wǎng)與標(biāo)稱電壓±10kV的對稱單極結(jié)構(gòu)的直流配電網(wǎng)均可與10kV交
流配電網(wǎng)互聯(lián)。
注2:標(biāo)稱電壓3kV的單極母線結(jié)構(gòu)的直流配電網(wǎng)與標(biāo)稱電壓±1.5kV的對稱單極結(jié)構(gòu)的直流配電網(wǎng)均可與1.5kV交
流配電網(wǎng)互聯(lián)。
注3:標(biāo)稱電壓400V的直流配電網(wǎng)可與單相220V交流配電網(wǎng)互聯(lián)。
注4:標(biāo)稱電壓±50kV的直流配電網(wǎng)推薦采用降壓變壓器與標(biāo)稱電壓35kV的交流配電網(wǎng)互聯(lián),也推薦采用升變壓器與
標(biāo)稱電壓66kV的交流配電網(wǎng)互聯(lián)。
5.3交直流互聯(lián)裝置
5.3.1交直流互聯(lián)裝置一般包括聯(lián)接(換流)變壓器、換流器、直流電抗器、濾波電抗器、直流斷路
器等主要部件。交直流互聯(lián)裝置可以是由獨立完成單一功能的多個部件組成,也可以是多個功能集成
的單個部件。
5.3.2容量要求
交直流互聯(lián)裝置容量序列推薦值
依據(jù)不同直流配電電壓傳輸容量范圍的推薦值,交直流互聯(lián)裝置容量序列推薦值如表2所示。
表2交直流互聯(lián)裝置容量序列推薦值
傳輸容量交直流互聯(lián)裝置容量
直流配電標(biāo)稱電壓
(推薦范圍)(推薦序列)
kV
MWMW
±10045~24040,50,63,80,100,160,200,250
±50(備選)23~6220,31.5,40,50,63
±3516~4416,20,31.5,40,50
±208~228,10,16,20,25
±104~124,5,6.3,10,12.5
±6(備選)2~72,3.15,4,5,6.3,8
±30.8~3.50.8,1,1.6,2,3.15,4
±1.50.5~20.5,0.63,1,1.6,2
0.750.2~0.80.5,0.63,0.8
交流配電系統(tǒng)最小短路容量要求
采用電網(wǎng)換相換流器技術(shù)時,應(yīng)進(jìn)行換流母線短路電流水平校核,滿足換相所需最小短路容量要
求;交直流互聯(lián)裝置采用電壓源換流器技術(shù)時,必要時宜考慮換流母線短路電流水平。
5.3.3控制功能要求
交直流互聯(lián)裝置宜采用雙向功率傳輸?shù)膿Q流器;直流配電網(wǎng)與交流配電網(wǎng)無雙向功率交互需求
時,可采用單向功率傳輸?shù)膿Q流器。
交直流互聯(lián)裝置應(yīng)根據(jù)互聯(lián)需求,合理配置定交流側(cè)電壓、定交流側(cè)功率、定直流側(cè)電壓、定直
流側(cè)功率等控制功能。
4
T/CEC167—2018
5.3.4損耗
基于電壓源換流器的交直流互聯(lián)裝置損耗要求應(yīng)符合GB/T30553的有關(guān)規(guī)定;基于電網(wǎng)換相換流
器的交直流互聯(lián)裝置損耗要求應(yīng)符合GB/T20989的有關(guān)規(guī)定。
5.3.5電能質(zhì)量
交直流互聯(lián)裝置交流接入點的電壓、電流應(yīng)滿足相應(yīng)國家標(biāo)準(zhǔn)GB/T12325—2008、GB/T
14549、GB/T12326、GB/T15543、GB/T24337、GB/T15945的有關(guān)要求。
交直流互聯(lián)裝置直流母線電壓應(yīng)滿足:
a)±10kV(含)~±100kV(含)等級的直流電壓偏差應(yīng)不大于±3%;
b)1500V(含)~±10kV等級的直流電壓偏差應(yīng)不大于±5%;
c)1500V以下等級的直流電壓偏差限值應(yīng)為5%,-7%。
5.3.6可靠性
a)交直流互聯(lián)裝置的可靠性評價指標(biāo)按照DL/T836的要求計算。根據(jù)運(yùn)行需要和設(shè)備技術(shù)水
平,由供方和需方共同協(xié)商確定交直流互聯(lián)裝置年利用率和年強(qiáng)迫停運(yùn)次數(shù)。
b)交直流互聯(lián)裝置換流器功率部件的冗余度應(yīng)根據(jù)系統(tǒng)總體失效率估算;在冗余范圍內(nèi),換流器
功率部件發(fā)生故障時不應(yīng)對裝置功能產(chǎn)生影響。
5.3.7其他要求
a)交直流互聯(lián)裝置的絕緣設(shè)計應(yīng)考慮對交流電壓、直流電壓、操作沖擊電壓、雷電沖擊電壓、陡
波前沖擊電壓的耐受能力;絕緣配合設(shè)計時應(yīng)全面考慮造價、維修費(fèi)用以及故障損失三個方面
因素。
b)交直流互聯(lián)裝置應(yīng)校驗導(dǎo)體和電器動穩(wěn)定、熱穩(wěn)定以及電器開斷電流所用的短路電流,應(yīng)按系
統(tǒng)最大運(yùn)行方式下可能流經(jīng)被校驗導(dǎo)體和電器的最大短路電流。
5.4無功配置要求
5.4.1采用電壓源換流器互聯(lián)時,一般可不配置無功補(bǔ)償裝置。
5.4.2采用電網(wǎng)換相換流器互聯(lián)時,應(yīng)配置相應(yīng)無功補(bǔ)償,AC-DC互聯(lián)拓?fù)浣Y(jié)構(gòu)所需的無功補(bǔ)償
容量一般為直流功率的30%~50%,DC-AC互聯(lián)拓?fù)浣Y(jié)構(gòu)所需的無功補(bǔ)償容量一般為直流功率的
40%~60%。
5.5保護(hù)配合
5.5.1直流配電網(wǎng)與交流配電網(wǎng)互聯(lián)的繼電保護(hù)應(yīng)覆蓋的范圍包括:
a)聯(lián)接變壓器(如有)、換流變壓器(如有)、接地變壓器(如有);
b)交流濾波器及無功補(bǔ)償裝置(如有);
c)交流換流母線;
d)換流器;
e)直流母線;
f)直流側(cè)的電容器及電抗器;
h)直流接地裝置及線路;
i)直流配電線路;
j)其他。
5.5.2直流配電網(wǎng)的繼電保護(hù)應(yīng)合理、可靠并能夠與交流配電網(wǎng)繼電保護(hù)相互配合。
5.5.3交直流互聯(lián)配電網(wǎng)的每一保護(hù)區(qū)應(yīng)與相鄰保護(hù)區(qū)重疊,避免存在保護(hù)死區(qū)。
5.5.4交流保護(hù)、直流保護(hù)與互聯(lián)裝置控制策略間的配合應(yīng)滿足所有運(yùn)行方式。
5.5.5直流配電線路主保護(hù)宜選用“全線速動”的保護(hù)元件;實現(xiàn)“全線速動”困難時,可采用階段
5
T/CEC167—2018
式保護(hù),時間定值的確定需考慮互聯(lián)裝置動、熱穩(wěn)定性和故障切除時間對故障恢復(fù)過程的影響。
5.5.6交直流互聯(lián)配電網(wǎng)應(yīng)配置后備保護(hù),根據(jù)系統(tǒng)需求,配置近后備保護(hù)或遠(yuǎn)后備保護(hù)。
5.5.7直流配電網(wǎng)的繼電保護(hù)系統(tǒng)應(yīng)設(shè)置斷路器等直流開斷裝置失靈保護(hù)。
5.5.8直流配電網(wǎng)宜依據(jù)系統(tǒng)運(yùn)行要求、直流斷路器等直流開斷裝置的技術(shù)條件設(shè)置自動重合閘
功能。
5.6接地要求
5.6.1當(dāng)直流系統(tǒng)采用雙極結(jié)構(gòu)時,接地系統(tǒng)的設(shè)計應(yīng)考慮單極運(yùn)行時接地電流對交流輸配電系統(tǒng),
鄰近的各類管道,以及通信、有線電視和市政等弱電系統(tǒng)的影響。
5.6.2當(dāng)額定電壓±1.5kV以上的直流系統(tǒng)采用對稱單極結(jié)構(gòu)時,且通過聯(lián)接變壓器與交流配電網(wǎng)
互聯(lián)時,應(yīng)在直流系統(tǒng)構(gòu)建接地點;當(dāng)互聯(lián)裝置采用兩電平/三電平換流器時,宜直接將直流電容
中點接地;若直流電容中點引出困難,或互聯(lián)裝置為模塊化多電平換流器(MMC)時,直流側(cè)可
經(jīng)電阻接地。
5.6.3當(dāng)額定電壓±1.5kV以上直流系統(tǒng)采用對稱單極結(jié)構(gòu)時,且在互聯(lián)裝置中無聯(lián)接變壓器時,直流
配電網(wǎng)接地方式的選擇應(yīng)考慮交流系統(tǒng)的接地方式。
a)當(dāng)交流側(cè)為非有效接地系統(tǒng),應(yīng)在直流系統(tǒng)構(gòu)建接地點,當(dāng)互聯(lián)裝置為兩電平/三電平換流器
時,宜直接將直流電容中點接地;若直流電容中點引出困難,或互聯(lián)裝置為模塊化多電平
(MMC)類型時,直流側(cè)可經(jīng)電阻接地。
b)當(dāng)交流側(cè)為非有效接地系統(tǒng),且互聯(lián)裝置為模塊化多電平(MMC)類型時,可通過采用曲
折型變壓器的方式在交流側(cè)構(gòu)建接地點,此時直流系統(tǒng)可不接地。電阻值的選取計算參見附
錄C。
c)若交流側(cè)直接接地或低電阻接地時,直流系統(tǒng)可不設(shè)置接地點,但應(yīng)根據(jù)限制直流系統(tǒng)單極接
地故障的短路電流值來計算交流側(cè)零序電阻值,以保證系統(tǒng)的正常運(yùn)行。電阻值的選取計算參
見附錄C。
6
T/CEC167—2018
附錄A
(資料性附錄)
由典型拓?fù)浣Y(jié)構(gòu)組合的交直流互聯(lián)系統(tǒng)結(jié)構(gòu)實例說明
本標(biāo)準(zhǔn)5.1.2中規(guī)定的AC-DC、DC-AC、AC-DC-AC為典型基本結(jié)構(gòu),可根據(jù)基本結(jié)構(gòu)組合多種
互聯(lián)方式,如圖A.1所示,利用電力電子變壓器的多端口,組合互聯(lián)形式AC-DC/DC-DC,適用于光伏
發(fā)電、風(fēng)力發(fā)電等交直流類型可再生能源分布較為集中以及直流負(fù)荷應(yīng)用較為廣泛的區(qū)域。
本拓?fù)浣Y(jié)構(gòu)的結(jié)構(gòu)特點:
a)交直流微電網(wǎng)呈對等的關(guān)系;
b)通過電力電子變壓器實現(xiàn)大電網(wǎng)—交流配電網(wǎng)—直流配電網(wǎng);
c)3者之間的能量雙向調(diào)控。
圖A.1交直流互聯(lián)AC-DC/DC-DC典型拓?fù)浣Y(jié)構(gòu)示意圖
7
T/CEC167—2018
附錄B
(資料性附錄)
交直流電壓轉(zhuǎn)換比計算說明
交直流電壓轉(zhuǎn)換比可參考式(B.1)、式(B.2)來推算。當(dāng)直流配電網(wǎng)與三相交流配電網(wǎng)互聯(lián)時,
交直流互聯(lián)系統(tǒng)交流端口電壓為線電壓,宜參考式(B.1);當(dāng)直流配電網(wǎng)與單相220V交流配電網(wǎng)互聯(lián)
時,交直流互聯(lián)系統(tǒng)交流端口電壓為相電壓,宜參考式(B.2)。
2Uac2UAB
Mac/dc==(B.1)
UUdcdc
22UUacAN
Mac/dc==(B.2)
UUdcdc
式中:
Mac/dc——交直流電壓轉(zhuǎn)換比,數(shù)值范圍一般為0.7~0.95;
UAB——交流端口線電壓有效值,單位為伏(V);
UAN——交流端口相電壓有效值,單位為伏(V);
Udc——直流端口標(biāo)稱電壓,單位為伏(V)。
8
T/CEC167—2018
附錄C
(規(guī)范性附錄)
交直流互聯(lián)系統(tǒng)交流側(cè)變壓器中性點的電阻選取計算公式
在直流配電網(wǎng)與交流配電網(wǎng)互聯(lián)系統(tǒng)中,交流側(cè)系統(tǒng)變壓器中性點的電阻原則應(yīng)考慮變流器電壓
控制及電力電子設(shè)備可以耐受的最大的短路電流,滿足式(C.1)。
U
dciminRs
Rt≥-+(C.1)
23Igmaxi
式中:
Igmaxi——換流器橋臂允許流過的最大零序電流,單位為安(A);
Rs——交流系統(tǒng)等效阻抗,單位為歐(?);
Udcimin——直流系統(tǒng)允許的極-極電壓的最小值,單位為伏(V)。
9
2018
—
167
T/CEC
中國電力企業(yè)聯(lián)合會標(biāo)準(zhǔn)
直流配電網(wǎng)與交流配電網(wǎng)互聯(lián)技術(shù)要求
T/CEC167—2018
*
中國電力出版社出版、發(fā)行
(北京市東城區(qū)北京站西街19號100005)
北京九天眾誠印刷有限公司印刷
*
2018年月第一版2018年月北京第一次印刷
880毫米×1230毫米16開本印張千字
*
統(tǒng)一書號155198·901定價0.00元
版權(quán)專有侵權(quán)必究
本書如有印裝質(zhì)量問題,我社發(fā)行部負(fù)責(zé)退換
T/CEC167—2018
目次
前言···································································································································································II
直流配電網(wǎng)與交流配電網(wǎng)互聯(lián)技術(shù)要求·········································································································1
1范圍······························································································································································1
2規(guī)范性引用文件··········································································································································1
3術(shù)語和定義··················································································································································1
4一般規(guī)定······················································································································································2
5技術(shù)要求······················································································································································2
5.1交直流互聯(lián)方式·········································································································································2
5.2交直流互聯(lián)電壓·········································································································································3
5.3交直流互聯(lián)裝置·········································································································································4
5.4無功配置要求············································································································································5
5.5保護(hù)配合···················································································································································5
5.6接地要求···········································································································
溫馨提示
- 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
- 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
- 5. 人人文庫網(wǎng)僅提供信息存儲空間,僅對用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對任何下載內(nèi)容負(fù)責(zé)。
- 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時也不承擔(dān)用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。
最新文檔
- 2024年幼兒園食品安全管理協(xié)議書
- 合作投資合同書示例
- 廣州市勞動合同范本參考
- 2024燈飾采購合同范文
- 安徽省淮南市七年級上學(xué)期語文期中試題3套【附答案】
- 提升機(jī)租賃合同樣式
- 2024抵押貸款合同協(xié)議書樣式
- 6.2 共筑生命家園(導(dǎo)學(xué)案) 2024-2025學(xué)年統(tǒng)編版道德與法治九年級上冊
- 購房合同協(xié)議書范本
- 倉庫租賃合同樣本
- 有色金屬熔煉與鑄錠課件
- 阻生牙拔除的護(hù)理
- 安徽省蕪湖市七年級上學(xué)期語文期中試卷(含答案)
- 兩癌知識科普課件
- 食用菌現(xiàn)代高效農(nóng)業(yè)示范園區(qū)建設(shè)項目建議書
- 東營港加油、LNG加氣站工程環(huán)評報告表
- 2024年日歷(打印版每月一張)
- 車用動力電池回收利用 管理規(guī)范 第2部分:回收服務(wù)網(wǎng)點征求意見稿編制說明
- 新劍橋少兒英語第六冊全冊配套文本
- 科學(xué)預(yù)測方案
- 職業(yè)生涯規(guī)劃網(wǎng)絡(luò)與新媒體專業(yè)
評論
0/150
提交評論